Generation 4

Slide 3 of 23
15.03.2018
1. Highest Power Density
33W/in3 FP2 3000

25W/in3 Generation 4
FP2 2000
FP2 1800
20W/in3

15W/in3 Generation 3
Flatpack 1800

Flatpack 1500
10W/in3

5W/in3 SMPS 1000

SMPS 60/20
Saves the Generation
customer money by : 1
- More space for customer equipment and/or batteries
- Thus less cabinets and less footprint in the location

Slide 4 of 23
15.03.2018
1. Highest Power Density – FP2 2KW SHELF

Dimensions
Modular Configuration 48 VDC 17.5” Wide –
167A Maximum Per Shelf brackets mount 19”, 21” or 23”
125A Redundant 14.5” Deep
With four rectifiers installed 1U – 1.75” Height

Slide 5 of 23
15.03.2018
1. Highest Power Density – FP2 3KW SHELF

Dimensions
Modular Configuration 48 VDC 17.5” Wide –
250A Maximum Per Shelf brackets mount 19”, 21” or 23”
187,5A Redundant 17” Deep
With four rectifiers installed 1U – 1.75” Height

Slide 6 of 23
15.03.2018
2. Pequeño y ligero

< 1.9 Kg

41.5mm
327 mm

109 mm

Más fácil para dirigir :


- Personal de mantenimiento - especialmente como repuestos
- Logística - un peso más ligero, significa menos costos de envío

Slide 7 of 23
15.03.2018
3. Operación de los ventiladores

2 Fans – Front to back airflow - will work with only one

(Back to front version in design stage)

Ahorros por costos de mantenimiento y operación por :


• Evitar las salidas de llamadas de prioridad (fuera de horas normales)
- Da una alta eficacia del rectificador

Slide 8 of 23
15.03.2018
4. Controles digitales
2 controlador digital : Dan mas supervisión y control.

Ahorro de tiempo y dinero por :


- Dando al operadores una información más en tiempo real del
sistema
- El personal de mantenimiento sabe exactamente qué necesita
hacer con las ayudas.

Slide 9 of 23
15.03.2018
5. Edge connectors
Communications

AC Input
DC Output

Edge-connector
technology

Ahorra tiempo (y dinero) :


- Módulos intercambiables en caliente.
- Reduce fallas de interconexión.

Slide 10 of 23
15.03.2018
6. Amplio Rango de entrada CA

Output Power vs. Input voltage

2000W
1800W

850W Nominal
650W
Input

0W
85V 185 290 300
Red LED Yellow LED Green LED Red LED

Slide 11 of 23
15.03.2018
6. Large AC input range

Mains derating

120

100
> Derating below 176Vac (185Vac
Output Power (%)

80 on 2kW module)
60

40 > 1382W (46%) at 85Vac


20

0
0 50 100 150 200 250 300 350
Voltage (Vac)

FP2 48/2000 FP2 48/3000

Slide 12 of 23
15.03.2018
7. Temperatura De-rating

Temperatura ambiente (max full carga de salida)

2000W
1800W

1400W
Linear 1200W
De-rating Zone
0W
o o
+45 +75

Green LED Yellow LED Red LED

Slide 13 of 23
15.03.2018
7. Temperature
De-rating

Temperature derating

120

100 > Derating above 45 oC


Output Power (%)

80
> 2100W (67%) at 75 oC
60

40
> Delivers 50A at 65 oC
20

0 > Operating down to -40 oC


0 10 20 30 40 50 60 70 80
Ambient temperature

FP2 48/2000 FP248/3000

Slide 14 of 23
15.03.2018
8. Excelente protección en AC/DC

Mains fuse: 2x15 A Varistor across the


(fast) in Live and lines for transient
Neutral protection

Hi -ohmic disconnect
above 290V / 300V AC
(with auto reconnect when in range)

DC Output
· Short circuit proof
(constant current)
· Single or double fan
DC output : Blocking Diode blockage/failure

Slide 15 of 23
15.03.2018
9. Highly Efficient – 2 KW

2000W rectifier : Efficiency at 230Vac input

93

92,5

92

Max
Eff.(%)

91,5

91
Efficiency
90,5
Zone
90
0 200 400 600 800 1000 1200 1400 1600 1800 2000
Pout(W)

Slide 16 of 23
15.03.2018
9. Highly Efficient – 3 KW

> Efficiency above 93% at 40-80% 94

load, 92.4% at 100% load


93

> 10% loss reduction on system


level 92

91
> Low load efficiency also

Efficiency (%)
improved
90

89

88

87
3000W
86 2000W
0 10 20 30 40 50 60 70 80 90 100
Load (% )

Slide 17 of 23
15.03.2018
9. Highly Efficient – 2 KW HE

Slide 18 of 23
15.03.2018
Technical Data – 48 V 1800 W

Slide 19 of 23
15.03.2018
Technical Data – 48 V 2000 W

Slide 20 of 23
15.03.2018
Technical Data – 48 V 3000 W

Slide 21 of 23
15.03.2018
Technical Data – 48 V 2000 W HE

Slide 22 of 23
15.03.2018
Procedimiento de instalación

Handle in
locked
position
Hole to release
the
handle’s spring
mechanism

Handle in
unlocked
position

Slide 23 of 23
15.03.2018
Panel Frontal

Dual Fan Cooling RED Alarm LED

GREEN Power LED YELLOW Warning LED

Slide 24 of 23
15.03.2018
Panel Frontal

Power
(green) ON Rectifier is powered

Smartpack controller accessing information on the


Flashing
rectifier

OFF Mains are unavailable

Slide 25 of 23
15.03.2018
Panel Frontal

Warning Rectifier is in Derating Mode (reduced output power)


(yellow) high internal temperature (+65 to 70 C) or
low input voltage (lower than 176VAC) or
ON single fan failure
The remote Battery Current Limit is activated
AC input voltage is out of range
Rectifier in stand-alone mode (or loss of
communication with the Smartpack controller

Flashing Rectifier is in Over-voltage Protection Mode

OFF No abnormal situation is present

Slide 26 of 23
15.03.2018
Panel Frontal

Alarm Rectifier is in Shut-down Mode due to


(red) low mains (0 – 85VAC) or
high internal temperature (+75 C or higher) or
ON high output voltage (higher than 59.5 VDC)
Internal rectifier failure (malfunction)
Fan failure (double fan malfunction)
Low output voltage (0 to 43.5VDC)
CAN bus failure

OFF No alarm situation is present

Slide 27 of 23
15.03.2018
Unidad de Control

> Scaleable y modular, control flexible para la gama entera de


productos Eltek

Slide 28 of 23
15.03.2018
Unidad de Control
> Front panel backlit LCD (2x16) and key pad

> USB for PC connection and easy FW uploading

> CAN bus para comunicacion con modulos Eltek

> 6 entradas digitales programables

> 6 relay de salidas configurables

> Latched contactor control

> Monitoreo y test de baterias

> Compensacion de carga por temperatura

> 8 symmetry measurements

> log de eventos(10000) con hora y fecha.

> Windows-based PC communication software

Slide 29 of 23
15.03.2018
Pequeño pero de gran alcance

< 300g

44mm

144 mm

109 mm

Slide 30 of 23
15.03.2018
Smartpack Vista Frontal

> ”Top-level alarms” scrolls on display when active


• Battery, Load, Rectifier, Control System & Mains

> Alarm LED (red) = Major Alarm active

> Warning LED (yellow) = Minor Alarm active

> Power LED (green) = Normal status active

Slide 31 of 23
15.03.2018
Panel Trasero
CAN Bus

CAN bus

• ID based serial
bus communications

• Max 8 Smartpack

• Max 50 Rectifiers
Part No : 242100.110
(RoHS compliant)

Slide 32 of 23
15.03.2018
Panel Trasero
Monitoreo de Baterías

Monitoreo de Baterías

Con 4 : Standard
Con 3 : Extended

• Symmetry
measurement

• 8 strings mid point


or
Part No : 242100.110 2 strings 12V block

• Sensor de Temp.
Slide 33 of 23
15.03.2018
Conectividad
Batería
> CON3 & CON4 – Conexiones de baterías Pin Function
1 Symmetry I/P 1
2 Symmetry I/P 2
3 Symmetry I/P 3
4 Symmetry I/P 4
5 Symmetry I/P 5
6 Symmetry I/P 6
Cable Sensor de
7 Symmetry I/P 7
Temperatura
8 Symmetry I/P 8
9-10 Con 3 : Temp sense 2

Con 4 : Temp sense 1


11 - 14 Con 3 – 2nd batt current,
batt fuse

Con 4 : Not used

Slide 34 of 23
15.03.2018
Conectividad - Batería
> CON3 & CON4 – Conexión de batería

Slide 35 of 23
15.03.2018
Panel Trasero
Webpower incluido

Embedded
WebPower

Ethernet interface
of remote
monitoring of
Smartpack
Is possible to
“tunnel”
Powersuite
Part No : 242100.113
remotely also.
(RoHS compliant)

Slide 36 of 23
15.03.2018
Smartpack

Smartpack WEB/SNMP
Alarma I/O

Con 1 (standard):-
2 + 2 relay input /
output

Con 2 (extended):-
4 + 4 relay input /
output

Part No : 242100.118