CALCULATION FOR POWER FACTOR IMPROVEMENT SYSTEM

Toatal Power (kW) 7020 9000

Load factor 0.8

Working load 5616

Current Power Factor (CosΦ1) 0.78

Φ1 38.739424598

Required Power Factor (CosΦ2)


0.998

Φ2 3.624307494

kVAR Rating (at rated system voltage) 4149.8916695

Calculation for capacitance of each unit

Unit capacitance (kVAR) (Standard unit) 150

Rated voltage of each unit (kV) 6.6

Rated current of each unit at rated


voltage (A) 22.727272727

Reactance, Xc (Ω) 290.4

Capacitance, C (μF) 10.961084235

Rated System voltage (kV) 6.6

Rated Capacitor voltage (kV) 7.72

Bank kVAR rating at rated voltage of


capacitor 5677.8444369 5600

Say, selected bank rating (kVAR) 2700

Capacitance per phase (kVAR) 900

Capacitance per star/per phase (in


double star connection) 450

Unit capacitance (kVAR) (Standard unit) 150


No. of units in parallel 3

6% reactance calculation

Factor for compensation of 6% reactance 0.94

%age reactance 0.06

Value of reactor in kVAR 152.28

Reactance / phase (kVAR) 50.76

Capacitor bank current (A) 201.92302161

Max. continuous current 262.49992809

Reactance voltage (V) 251.38292601

Reactance (Ω) 1.2449443556

Inductance, L (mH) 3.9627809612