Vous êtes sur la page 1sur 7

PROJECT:

Construction of 33kV Substation at NTPC Lara

CUSTOMER: NTPC , LARA

CONTRACTOR C & ELECTRIC LTD

Client PO

PROJECT: Construction Power Package NTPC, Lara

Consultant: DRN. NAME SIGN DATE


PRPD A.K. 25.06.13
M/s. Alif Engineers & Planners, CHKD S.A 25.06.13
Mumbai APPD S.A 25.06.13
TITLE

DOC. NO. REV. NO.


11KV POLE - DESIGN
C&S/LARA/AEP/C/101 0
CALCULATIONS
DESIGN OF THE FOUNDATION FOR THE POLE

INPUT
DETAILS OF POLE
HT DIA OF POLE
h1 2.7 140
h2 2.7 163
h3 5.6 194
Tot Ht 11 m

Self wt of the Pole = 241 kg

Minium depth of embedment = 1/6 x 11 = 1.833 m

Prvide Pedestal of size = 0.7 x 0.7 x 1.95 (150mm above ground)

1.0 WIND LOAD CALCULATION


Calculation of design wind pressure (As per IS:802 )

Basic wind speed Vb = 44 m/s


Reference Wind Speed VR = Vb/Ko = 44 /
Risk Co-efficient k1 = 1.07 (Reliability level -1 )
Terrain category (category-1 and class-A)
k2 = 1 (Category -1)
Design wind Speed Vd = Vb * k1 * k2
= 34.24 m/s
Design Wind Pressure Pd = 0.6 Vz2
= 703 N/m2

Overturning Moment due to the wind on the pole :

M = 70.34 x ( 2.7 x 0.14 ) x 9.65 x 0.6 +


70.34 x ( 2.7 x 0.16 ) x 6.95 x 0.6 +
70.34 x ( 5.6 x 0.19 ) x 2.8 x 0.6 +

= 410.1 kg.mtr

Total weight of pole + foundation = 241 + 0.7 x 0.7 x 1.95 x 2500

Stabilizing Moment = 2630 x 0.35 = 920.4125 Kgm

Factor of Safety = 2.24 > 2 Hence safe


Provide a block of 0.7 x 0.7 x 1.95 m for all pole foundation in 1:3:6 grade Concrete

All foundations shall be minm 500mm below natural grund level.


Wind Zone = 3
1.375 = 32.00 m/s
Reliability level -1 )

Category -1)

= 70.34 kg/m2

= 2629.75 Kg