SITRANS L Level instruments

Point level measurement - Electro-mechanical switches


SITRANS LVL100

■ Overview ■ Configuration

SITRANS LVL100 is a compact vibrating level switch for use in


liquid applications such as overflow, high, low and demand ap-
plications, as well as pump protection. It is ideal for use in con-

5
fined spaces.

■ Benefits
• Proven vibrating level switch technology for liquids
• Compact insertion length of 40 mm (1.57”) for confined space
applications
• Fault monitoring for corrosion, loss of vibration, or line break to
the piezo drive

■ Application
SITRANS LVL100 is a compact level switch designed for indus-
trial use in all areas of process technology and can be used with
liquids and slurries. With an insertion length of only 40 mm
(1.57“), SITRANS LVL100 can be mounted in small pipes and
confined space applications. It is also virtually unaffected by the
chemical and physical properties of the liquid. The LVL100 can
also be used in difficult conditions including turbulence, air bub-
bles, foam generation, buildup, or strong external vibration.
The tuning fork is piezoelectrically energized and vibrates at its
mechanical resonance frequency of approximately 1200 Hz.
The vibration frequency changes when the tuning fork is cov-
ered by the medium. This change is detected by the integrated
oscillator and converted into a switching command. The inte-
grated electronics evaluate the level signal and output a switch-
ing signal, directly operating connected devices.
• Key Applications: For use in liquids and slurries, for level mea-
surement, overfill, and dry run protection

SITRANS LVL100 Installation

Siemens FI 01 · 2008 5/3


SITRANS L Level instruments
Point level measurement - Electro-mechanical switches
SITRANS LVL100

■ Technical specifications Selection and Ordering data Order No.


SITRANS LVL100 7ML 5 7 4 5 -
Mode of operation Compact vibrating level switch for use in liquid
7 7 7 7 77 - 7 A 0
Measuring principle Vibrating point level switch applications such as overflow, high, low and
demand applications, as well as pump protection.
Input Ideal for use in confined spaces.
Measured variable High and low and demand Approvals
Output Without approvals 1
Shipping approvals 2
Output options • Contactless electronic switch Overfill protection (WHG)1) 3
• Transistor output PNP Process temperature
Measuring Accuracy Standard -40 to 100 °C (-40 to 212 °F)2) A
Extended -40 to 150 °C (-40 to 302 °F)2) B
• Hysteresis approx. 2 mm (0.08”) with vertical
installation Hygienic applications -40 to 150 °C (-40 to 302 °F)3) C
Process connection
• Switching delay approx. 500 ms (on/off)
Thread G¾" A PN64/316L A0
• Frequency approx. 1200 Hz Thread G¾" A PN64/316L Ra<0.8µm A1
Rated operating conditions Thread ¾" NPT PN64/316L A2
Installation conditions Thread ¾" NPT PN64/316L Ra<0.8µm A3
Thread G1" A PN64/316L A4
• Location Indoor/outdoor
Thread G1" A PN64/316L Ra<0.8µm A5
Ambient conditions Thread 1" NPT PN64/316L A6
• Ambient temperature -40 to +70 °C (-40 to +158 °F) Thread 1" NPT PN64/316L Ra<0.8µm A7

5 • Installation category III Tri-Clamp 1" PN16/316L Ra<0.8µm


Tri-Clamp 1½" PN16/316L Ra<0.8µm
A8
B0
• Pollution degree 2
Tri-Clamp 2" PN16/316L Ra<0.8µm B1
Medium conditions
Bolting DN25 PN40 DIN11851/316L Ra<0.8µm B2
• Temperature Bolting DN40 PN40 DIN11851/316L Ra<0.8µm B3
- Standard -40 to +100 °C (-40 to +212 °F) Bolting DN50 PN25 DIN11851/316L Ra<0.8µm B4
- High temperature option -40 to +150 °C (-40 to +302 °F) SMS DN38 PN6/316L Ra<0.8µm B5
Hygienic fitting with compression nut F40 B6
• Pressure (vessel) -1 to 64 bar g (-14.5 to 928 psi g) PN25/316L Ra<0.8µm
• Density 0.7 to 2.5 g/cm³ (0.025 to Electronics
0.09 lbs/in³) Contactless electronic switch 20 to 250 V AC/DC4) 1
Design Transistor output PNP 10 to 55 V DC 2
• Material Housing
- Enclosure 316L and Plastic PEI 316L 1
Electrical connection/Protection
- Tuning fork 316L (1.4404 or 1.4435)
M12x1/IP67 A
- Process connection (threaded) 316L (1.4404 or 1.4435) According to DIN 43650 including plug/IP65 B
- Process seal Klingersil C-4400 Acc. to DIN43650 incl. plug with QuickOn connec- C
tion/IP65
• Process connection
M12x1 incl. 5 m cable/IP68 (0.2 bar) D
- Pipe thread, cylindrical G ¾” A or G 1” A
(ISO 228 T1) Further designs Order code

- Pipe thread, tapered ¾” NPT or 1” NPT Please add "-Z" to Order No. and specify Order
code(s).
- Hygienic fittings Bolting DN40 PN40
Cleaning including Certificate (oil, grease and sili- W01
Tri-clamp 1”, 1½”, 2” PN 10, cone free)
conus DN25 PN 40, Tuchenhagen Y18
Varivent DN50 PN 10, SMS Identification Label, foil laser marking
• Degree of protection IP65/Type 4/NEMA 4 (with DIN Additional instruction manual Order No.
43650 valve plug), IP66/67 or LVL100 (Contactless electronic switch), English 7ML1998-5KN01
IP68 (with M12 connector) LVL100 (Contactless electronic switch), French 7ML1998-5KN11
• Conduit entry 1 x M12 [IP66/IP67 or IP68 LVL100 (Contactless electronic switch), Spanish 7ML1998-5KN21
(0.2 bar)] LVL100 (Contactless electronic switch), German 7ML19985-KN31
• Weight (housing) 250 g (9 oz) LVL100 (Transistor PNP), English 7ML1998-5KP01
LVL100 (Transistor PNP), French 7ML1998-5KP11
Power supply LVL100 (Transistor PNP), Spanish 7ML1998-5KP21
• Supply voltage 20 to 253 V AC, 50/60 Hz LVL100 (Transistor PNP), German 7ML1998-5KP31
20 to 253 V DC This device is shipped with the Siemens Milltronics
• Power consumption 1 to 8 VA (AC), approx. 1.3 W manual CD containing the complete instruction
(DC) manual library.
1)
Certificates and approvals • Overfill protection (WHG) Available with Electronics option 2 only
2) Available with process connection A0, A2, A4, and A6 only
• Shipping approvals 3)
Available with process connection A1, A3, A5, and A7 to B6 only
4)
Available with Electrical connection/Protection option B and C only

5/4 Siemens FI 01 · 2008


SITRANS L Level instruments
Point level measurement - Electro-mechanical switches
SITRANS LVL100

■ Characteristic curves

SITRANS LVL100 Ambient Temperature/Process Temperature derating curves

Siemens FI 01 · 2008 5/5


SITRANS L Level instruments
Point level measurement - Electro-mechanical switches
SITRANS LVL100

■ Dimensional drawings

SITRANS LVL100 dimensions

5/6 Siemens FI 01 · 2008


SITRANS L Level instruments
Point level measurement - Electro-mechanical switches
SITRANS LVL100

■ Schematics

SITRANS LVL100 connections

Siemens FI 01 · 2008 5/7