Data Sheet Wöhr Parklift 440-2,0

Single unit = 2 cars Suitable for condominium and office buildings.


Double unit = 4 cars For permanent use only!*
25 25
40 80
* In case of short time user
– only possible on upper platform
and only if technically adjusted, free space
40 for door free space 40
ask WÖHR!
Or with attendant or valet parking both
levels are possible for short time user.

door lintel
Special reinforced units
for higher parking platform load
are available (see 440-2.6).
X
Both platforms are in a
horizontal position to drive in.

Load per platform max. 2000 kg 15


(load per wheel max. 500 kg) 15
clear height
for
for a lintel ning
h ope and es
wallctrical servic
X = only applicaple if garage ele raulic
hyd
doors are to be fitted. 120
For roller doors x = 10/15 cm
max. + 3% slope
max. -10% slope
X = to be clarified with
door supplier
min.18 e
ac
Dimensions in cm sp

0
0 ss
le on

x2
b

x 5 ce
i i

p s ge
ss ct

m plu na
50 re
po r su

pu 2 ai
fo

p 0 x d dr
um l 1 de
r s e en
fo ann mm
ch co
re

1–2% slope1–2% min.18

50
390
530 – 540

Standard type 440-185/180 · 2000 kg Comfort type 440-200/195 · 2000 kg Compact type 440-170/165 · 2000 kg

385 +30
355 +30 (370) *
(340) * (355) ** 325 +30

185 +30 200+30 170


+3
180+30 195
+3
0
0
165
+3
0

car height distance (h) car height distance (h) car height distance (h)
UL cars/station wagons up to 165 cm UL cars/vans up to 180 cm UL cars/station wagons up to 150 cm
LL cars/station wagons up to 165 cm 170 LL cars/vans up to 180 cm 185 LL cars/station wagons up to 150 cm 155
UL = upper level, LL = lower level cars/vans up to 2000 kg max.
* If cars and station wagons with a height of up * If cars and station wagons with a height of up Please attend to restricted car- and platform
to 150 cm are parked on the upper level, a to 165 cm are parked on the upper level, a distance height!
clear height of 340 cm above the entrance clear height of 370 cm above the entrance
level is sufficient. level is sufficient.
** If cars and station wagons with a height of up
to 150 cm are parked on the upper level, a
clear height of 355 cm above the entrance
level is sufficient.

Clearance profile (car/station wagon)


40 170
50 50 *The total car height
165* includes roof rail
(180*) and antenna fixture
(150*) and must not exceed
275 22 the mentioned max.
60 14 38 height dimension.
120 max. 290 90
500
Parklift 440 | 04.2012 | C027-4303 | © Otto Wöhr GmbH

Notes
1. Clear platform width of 250 cm for car widths of 190 cm (see width dimensions stated on page 2). For large touring sedans we recommend
a clear platform width of at least 260–270 cm for single and 520–540 cm for double systems.
2. Due to recent increases in car length dimensions, and potential future developments, a pit length of 540 cm is advisable. This also offers a greater
safety distance for future car sizes.
3. At the edge of the pit a 10 cm wide, yellow-black marking according to ISO 3864 has to be provided by the purchaser (see “statics and construction
requirements“ on page 3).
4. It is not possible to have channels or undercuts and/or concrete haunches along the pit floor-to-wall joints. In the event that channels or
undercuts are necessary, the system width needs to be reduced or the pit needs to be wider.
5. The manufacturer reserves the right to construction or model modifications and/or alterations. Furthermore, the right to any subsequent part
modification and/or variations and amendments in procedures and standards due to technical and engineering progresses in the art or due to
environmental regulation changes, are also hereby reserved.

Otto Wöhr GmbH Ölgrabenstrasse 14 Fon +49 [0] 7044 46 -0 www.woehr.de


01 Auto-Parksysteme 71292 Friolzheim | Germany Fax +49 [0] 7044 46 -149 info@woehr.de We compact parking space
Width dimensions · Underground garages
All dimensions shown are minimum. Construction tolerances must be taken into consideration.
All dimensions in cm.
The access to the Parklift is possible with max. 3% declination and max.10% inclination.
250, 260 and 270 cm platform widths are also available in special construction options (for both parking levels) with a 2600 kg/3200 kg
parking platform load capacity – please consult the Parklift 440-2.6 and Parklift 440-3.2 datasheets.

Wall to wall
Single unit (2 cars) Double unit (4 cars) Combinated unit (6 cars)
Wall openings required between
partitions for electrical and hydraulic
conduits must be provided where
S D D S applicable. Wall openings may not
be closed after installation.

B B B
The driving aisle width to
Space required gives clear Space required gives clear Space required gives clear be compliant with country
B platform width B platform width B platform width regulations locally in force.
260 230 490 460 750 460+230
270 240 510 480 780 480+240
280 250 530 500 810 500+250
290 260 550 520 840 520+260
300 270 570 540 870 540+270
Other width combinations as well
as smaller widths are possible.

Pillars outside pit


Single unit (2 cars) Double unit (4 cars) Combinated unit (6 cars)

S S D D D S D S
min. 20 min. 20 min. 20

B B1 B B1 B B1
The driving aisle width to
Space required Space required Space required be compliant with country
wall- pillar- gives clear wall- pillar- gives clear wall- pillar- gives clear regulations locally in force.
pillar pillar platform width pillar pillar platform width pillar pillar platform width
B B1 B B1 B B1
250 240 230 480 470 460 740 730 460+230
260 250 240 500 490 480 770 760 480+240
270 260 250 520 510 500 800 790 500+250
280 270 260 540 530 520 830 820 520 + 260
290 280 270 560 550 540 860 850 540+270
Other width combinations as well
as smaller widths are possible.

Pillars inside pit


Single unit (2 cars) Double unit (4 cars) Combinated unit (6 cars)

S S D D D S D S
min.15 min.15 min.15

max.100 max.100 max.100


B B1 B B1 B B1
The driving aisle width to
be compliant with country
Space required Space required Space required
wall- pillar- gives clear wall- pillar- gives clear wall- pillar- gives clear regulations locally in force.
pillar pillar platform width pillar pillar platform width pillar pillar platform width
B B1 B B1 B B1
Parklift 440 | 04.2012 | C027-4303 | © Otto Wöhr GmbH

255 245 230 485 475 460 745 735 460+230


265 255 240 505 495 480 775 765 480+240
275 265 250 525 515 500 805 795 500+250
285 275 260 545 535 520 835 825 520 + 260
295 285 270 565 555 540 865 855 540+270
Other width combinations as well
as smaller widths are possible.

Important notes
If maximum platform widths are not installed, difficulties might For parking slots at edges or between walls, we recommend going
arise when entering or exiting the cars on the parking units. for our maximum platform widths.
This depends on the car type, the access and the individual For cars wider than 190 cm, platform width of 270/540 cm is
driving behaviour. required to enter and exit the car at drivers-side.

02
Width dimensions · Garages with doors
All dimensions shown are minimum. Construction tolerances must be taken into consideration.
All dimensions in cm.
The access to the Parklift is possible with max. 3% declination and max.10% inclination.
250, 260 and 270 cm platform widths are also available in special construction options (for both parking levels) with a 2600 kg/3200 kg
parking platform load capacity – please consult the Parklift 440-2.6 and Parklift 440-3.2 datasheets.

Single garages (2 cars) Double garages (4 cars)


B B x = for doors. See page 1

Wall openings required between


partitions for electrical and hydraulic
conduits must be provided where
S D applicable. Wall openings may not
be closed after installation.

X
B1 B1
15 15 15 15 The driving aisle width to
Space required gives clear Space required gives clear be compliant with country
B B1 platform width B B1 platform width regulations locally in force.
260 230 230 490 460 460
270 240 240 510 480 480
280 250 250 530 500 500
290 260 260 550 520 520
300 270 270 570 540 540

Serial garages with single doors (2 cars) Serial garages with double doors (4 cars)
B B B B B

S S S D D

X
B1 B1 B1 B1 B1
15 30 30 30 15 30 30 The driving aisle width to
Space required gives clear Space required gives clear be compliant with country
B B1 platform width B B1 platform width regulations locally in force.
260 230 230 490 460 460
270 240 240 510 480 480
280 250 250 530 500 500
290 260 260 550 520 520
300 270 270 570 540 540

Statics and construction requirements


Single unit
Bearing loads are transmitted
P1 P2 P3 P4 P1 =+36 kN * to the pit floor by base plates of
– 7 kN
P4 clear approximately 140 cm2, fixed by
platform- P2 = + 2 kN heavy duty anchor bolts to a depth
P4
– 3 kN of approximately 10–12 cm.
width +15
Base plate thickness min. 18 cm.
P1 P2 P3 P4 P3 =+14 kN P4
– 3 kN A Concrete quality according to
5
P4 = + 3 kN P4 the static building requirements,
Marking according to ISO 3864 5° however for the dowel fixing
- 11 - -
concrete quality of min. C20/25
P1 P2 P3
Double unit + + + is required.
P1 P2 P3 P4 P1 =+66 kN ~200 When fixing to waterproof concrete
– 6 kN floors, chemical anchor bolts are
~485
P4 supplied (to be confirmed by Wöhr).
P2 = + 3 kN
Parklift 440 | 04.2012 | C027-4303 | © Otto Wöhr GmbH

– 6 kN ~500
The front wall of the pits must be
clear formed of concrete and must
platform- P3 =+23 kN A be perfectly flat and vertical
width +15 – 3 kN Parklift 440-170/165 72 without any protrusions.
P4 = + 3 kN Parklift 440-185/180 57
P4
The specified lengths to the
Parklift 440-200/195 42
*all static loadings support points are mean values.
P1 P2 P3 P4 include the weight Please contact us for exact
of the car positions for any variations on
the standard units.

Hydraulic power pack


The location of the hydraulic power pack is determined Dimensions in cm 1–5 Parklifts 6–10 Parklifts
according to your plan – space requirements are as following: Length: 100 150
Height: 140 140
Depth: 35 35

03
Electrical datas Installation diagram
Item Performance Quantity Designation Position Frequency 1 Electric meter
1 by customer 1 unit electric meter in the feed cable 2 Fuse or automatic circuit breaker
3 x16A slow blow according to
2 by customer 1 unit fuse or automatic circuit in the feed cable 1 per DIN VDE 0100 part 430
breaker 3x16A slow blow power pack
3 Feed line to the main switch
acc. to DIN VDE 0100 p. 430
3 by customer as locally acc. to local power supply feed cable to 1 per 6 Lockable main switch 7 PVC control cable 5 x 1,52
required regulations main switch power pack from main switch to assembly
3 Ph + N + PE* 13 PVC control cable 8 Hydraulic unit with three-phase
conduit 7 x1,5 2 motor, 230/400V, 50Hz, 1.5/3.0 kW.
4 by customer each equipotential bonding sa- corner pit floor/ Switching cabinet with motor,
10 m fety lead-out connection rear wall 14 Cylinder valve cable protection, wired already for
5 by customer 1 unit equipotential bonding sa- from the lead-out 1 per 120 cm 110 cm PVC control cable installation
fety compliant to the connection to the Parklift 3 x1,5 2 9 PVC control cable 5 x1,52
DIN EN 60204 standard system 10 Branch
6 by customer 1 unit marked main switch, above operating 1 per 4 Equipotential bonding safety
lockable to prevent device power pack lead-out connection
unauthorized switching on 5 Equipotential bonding safety
from the lead-out connection
7 by customer 10 m PVC control cable with from main switch 1 per to the system
marked strands and pro- to hydraulic power power pack 12 Operating device for UP/DOWN with 11 PVC control cable 5 x1,52
tective conductor 5 x 1,5 2 pack EMERGENCY-STOP. If possible on the to the next facility
Items 8–14 are included in Wöhr’s scope of delivery unless otherwise specified in the left, but always outside the platform’s
offer/order. movement range. Cables always feed in
from below. (2 keys per parking place.)
* DIN VDE 0100 part 410 + 430 (not under permanent load) 3PH+N+PE
(three-phase current) Note: Where a door is used to close the garage, the Recesses and conduits for rotary
manufacturer of the door must be consulted before the electric cable is laid.
switches with rolling and sectional gates
The electrical components enable our fitters to complete
supplied by the manufacturer their work satisfactorily and to Above plaster Under plaster
must be connected in accord- check the correct functioning
ance with the appropriate wiring of the units.
diagram and local regulations. In compliance with the DIN EN
German VDE electrical require- 60204 standard provisions, all 15
ments must be adhered to, in systems must be connected
order to validate the TÜV tested directly on site with an earthed
circuit. equipotential bonding. The lead- 115 above access level
The electrical supply to the out connection must be at a
power pack(s) must be provided 10 m distance! = = min.20 = =
prior to or during installation to
B B
A A
Noise protection 7 +0,5
Basis is the German DIN 4109 At differing constructional 8 8
“Noise protection in buildings”. conditions additional sound
With the following conditions absorbing measures are A Plastic or steel armoured conduit M 20
required 30 dB (A) in rooms necessary.
B Flexible plastic insulation pipe M 20
can be provided: The best results are reached
– noise protection package by separated sole plates from
from our accessory the construction. Railings
– insulation figure of the Increased noise protection: The units need to be provided acc. EN ISO 13857 with safety railings
construction of min. R’w = 57dB If increased noise protection if the gap between unit and wall exceeds 20cm. If walkways are arranged
must be provided planning has directly to the side or behind the systems, railings have to be provided
– walls which are bordering
to be confirmed on a project by the customer acc. to local requirements, height min. 200 cm – this is
the parking systems must be
basis by Wöhr (further building applicable during the construction phase too.
done as single wall and
deflection resistant with min. measures are required).
m’= 300 kg/m2 Free spaces
– solid ceiling above the Special drawings for free spaces to accommodate air ducts or other
parking systems with min. pipes can be requested at Wöhr Agent!
m’= 400 kg/m2
Maintenance
Temperature Regular maintenance by qualified personnel can be provided by means
The installation is designed to operate between +5°and +40°C. of an Annual Service Contract.
Atmospheric Humidity: 50% at +40°C. If the local circumstances
differ from the above please contact Wöhr. Protection against corrosion
Independent of a maintenance workings has to be carried out acc. to
Drainage Wöhr Cleaning and Maintenance Instruction regularly.
We recommend the provision accessible for manual drainage, Clean up galvanized parts and platforms of dirt and road salt as well
of a drainage channel at the the client must provide a pump as other pollution (corrosion danger)!
front of the pit which can either on site to empty the pump sump.
incorporate a pump sump To prevent any possibility Pit must always be ventilated and dearated well.
50 x 50 x 20 cm, or a connection of contamination of the ground-
into the storm water sewerage water we recommend that the Parking place width
system via a petrol/oil intercep- pit floor is coated with an oil We recommend a clear platform width of at least 250 cm and/or of
Parklift 440 | 04.2012 | C027-4303 | © Otto Wöhr GmbH

tor. If the pump sump is not proof paint. at least 500 cm for double systems.

Conformity test Dimensions


All our systems are checked according to EC machinery directive All dimensions shown are minimum. Construction tolerances must
2006/42/EC and EN 14010. be taken into consideration. All dimensions in cm.

Illumination Fire safety


Illumination has to be considered acc. to local requirements by the Each and every fire safety requirement and all possible mandatory item(s)
customer. and equipment(s) (fire extinguishing systems and fire alarm systems, etc.)
are to be provided by the customer.