Vous êtes sur la page 1sur 10

Project:

R.R. Rojo and Associates


Prepared by: Checked by: Location:

ANCHOR BOLT DESIGN


RESULT The Anchor Rod Design Is A
Loadings:
Mu = 163 kN-m.
Pu = 667.2 kN
Vu = 71.2 kN

Properties:
Concrete Strength fc' = 21 MPa
Strength of Anchor futa = 400.2 MPa
Base Plate Yield Strength fy = 248 MPa
Base Plate Cantilever m= 100 mm.
Eff. Embedment Depth hef = 400 mm.
Anchor Diameter d= 25 mm.
Type of Anchor Head Square
Apply Seismic Load Factor? Yes
Ω= 2.5
Ase,N = 390.967 mm^2
Ab = 945.159 mm^2
distance between Fastener an ca1 = 300 mm
distance between Fastener an ca2 = 230 mm
Anchor Bolt Location to Work Point

Bolt Number X Y
1 -203.2 203.2
2 -203.2 0
3 -203.2 -203.2
4 203.2 203.2
5 203.2 0
6 203.2 -203.2
Analysis:
Anchor Forcces Without Concrete Compression Forces Being Considered
cg of bolt from work point
XCG of bolt YCG of bolt
0 0

Bolt Number X Y XCG2


1 -203.2 203.2 41290.24
2 -203.2 0 41290.24
3 -203.2 -203.2 41290.24
4 203.2 203.2 41290.24
5 203.2 0 41290.24
6 203.2 -203.2 41290.24
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
247741.4
Tensile Anchor Strength
Nua,1 = 56.236 kN

φNsa = φAse,N(futa) = 117.349 kN >

Concrete Breakout Strength of Governing Anchor


φNcb = φ(ANC/ANCo)Ψec,NΨed,NΨc,NNb = φ(AN/9h2ef)Ψec,N1.0Ψc,N(24√(fc')hef1.5)
φ 0.5625
ANCo = 1440000 mm^2
AN = 1080000 mm^2
AN = 0 1/4 of ANCo **Conservative Value
Used AN = 1080000 mm^2
Ψec,N = 1.0, for no eccentricity in the connection.
Ψc,N = 1.0, for location where concrete cracking is likely t
φNcb = 371.189 kN >

Concrete Breakout Strength of All Anchor


φNcbg = φ(ANC/ANCo)Ψec,NΨed,NΨc,NNb = φ(AN/9h2ef)Ψec,N1.0Ψc,N(24√(fc')hef1.5)
φ= 0.5625
ANCo = 1440000 mm^2
AN = 1615232.96 mm^2
Used AN = 1615232.96 mm^2
Ψec,N = 1 1.0, for no eccentricity in the connection.
Ψc,N = 1 1.0, for location where concrete cracking is likely t
φNcbg = 555.145 kN >

Pull out Strength of Governing Anchor


φNpn = φΨcp,N(Ab8fc')
φ= 0.5625
Ab = 945.159
Ψcp,N = 1 for concrete cracking likely to occur
φNpn = 89.318 kN >

Side-face Blowout Strength


φNpn =φ13ca1√(Abrg)λa√(fc')
φ= 0.5625
Ab = 945.1594 mm^2
ca1 = 300 mm.
ca2 = 230 mm.
ca2 < 3ca1
ca2/ca1 = 0.766667 0.7666666667
factor = 1
φNpn = 309.0646327042 kN >

Design Tensile Strength of Governing Anchor


φNn = min(φNsa,φNcb,φNpn,φNpn)
φNn = 89.318 kN

Shear Strength of Governing Anchor


φVsa = φ0.60*Ase,Vfuta
φ= 0.65
Ase,V = 390.96696 mm^2
φVsa = 61.021 kN >
**first factor shall be multiplied by 0.8, for built-up grout pads

Breakout Strength of Governing Anchor For Shear

φVcb = φ(AVC/AVCo)Ψec,VΨed,VΨc,VVb = φ1.0Ψec,V1.0Ψc,V(0.6(le/d)0.2√(d)√(fc')(hef)1.5


φ= 0.75
Ψec,V = 1 for no eccentricity in the connection.
Ψc,v = 1 for location where concrete cracking is likely to oc
le/d = 8 should not exceed 8
φVcb = 125.026 kN >

Breakout Strength of All Anchor For Shear


φVcbg = φ(AVC/AVCo)Ψec,VΨed,VΨc,VVb = φ(Av/4.5(1.5hef)^2)Ψec,V1.0Ψc,V(0.6(le/d)0.2√(d)√(fc')(hef)1.5
φ= 0.75
Ψec,V = 1 for no eccentricity in the connection.
Ψc,v = 1 for location where concrete cracking is likely to oc
le/d = 8 should not exceed 8
ca1 = 300 mm.
ca2 = 230 mm.
Av = 488880 mm^2
φVcbg = 84.8926 mm^2 >

Pryout Strength for Shear Load on Governing Fastener


φVcp = φkcp(ANC/ANCo)Ψed,NΨc,NNb = φkcp(AN/9h2ef)1.0Ψc,N(24√(fc')hef1.5)
φ= 0.75
Ψc,N = 1 for location where concrete cracking is likely to oc
kcp = 2 for hef ≥ 2.5mm
φVcp = 742.38 kN >

Pryout Strength for Shear Load on All Fastener


φVcpg = φkcp(ANC/ANCo)Ψed,NΨc,NNb = φkcp(AN/9h2ef)1.0Ψc,N(24√(fc')hef1.5)
φ= 0.75
Ψc,N = 1 for location where concrete cracking is likely to oc
kcp = 2 for hef ≥ 2.5mm
φVcpg = 1110.29 kN >

Design Shear Strength on Governing Anchor


φVn = min(φVsa, φVcb, φVpn)
φVn = 61.02 kN

Splitting Failure Check


ca1 > 0.4hef OK!
Note: No Splitting Failure Will Occur Since The Anchor Is Far From the Edge

Shear and Tension Interaction


Nua,2 > 0.2φNn Full Strength in Shear Shall Be
Vua,2 < 0.2φVn Full Strength in Tension Shall

Therefore, the Interaction, Equation may Be Used

Nua,2 Vua,2
+ =
φNn φVn
Description:

Date:

BOLT DESIGN
Anchor Rod Design Is Adequate.

BOLT GROUP
250
200
150
100
50
0
-250 -200 -150 -100 -50 0 50 100 150 200 250
-50
-100
-150
-200
-250
YCG2 Nua,1 Vua
41290.24 22.494 11.867
0 22.494 11.867
41290.24 22.494 11.867
41290.24 -244.894 11.867
0 -244.894 11.867
41290.24 -244.894 11.867
0
0
0
0
0
0
0
0
0
0
0
0
0
0
165161 -667.2 71.2
Nua = max(Nua,1) = 56.2356 kN OK!

**Conservative Value

city in the connection.


here concrete cracking is likely to occur.
Nua = 56.2356 kN OK!

city in the connection.


here concrete cracking is likely to occur.
-Pu = -667.2 kN OK!

ng likely to occur
Nua = 56.2356 kN OK!

Nua = 56.2356 kN OK!


Vua = 29.667 kN OK!

√(d)√(fc')(hef)1.5

n the connection.
concrete cracking is likely to occur.

Vua = 29.667 kN OK!

0Ψc,V(0.6(le/d)0.2√(d)√(fc')(hef)1.5

n the connection.
concrete cracking is likely to occur.

Vua = 61.021 kN OK!

concrete cracking is likely to occur.

Vua = 29.667 kN OK!

concrete cracking is likely to occur.

Vua = 61.021 kN OK!


Full Strength in Shear Shall Be Permitted
Full Strength in Tension Shall Be Permitted

0.82 < 1.2 OK!