Vous êtes sur la page 1sur 101

Electrical Installation Handout

CHAPTER 1
INTRODUCTION TO ILLUMINATION
1.1. LIGHTING
Light is defined as the radiant energy from a hot body, which produces the visual sensation
upon the human eye. The sensation of color is due to the difference in wavelength of the light
radiations. White light, such as given by the sun, is composed of different color each having
different wavelengths. These are:
0.300 – 0.436 micrometer----------Violet
0.436 - 0.495 >> ---------------------Blue
0.495 - 0.566 >> ---------------------Green
0.566 - 0.589 >> --------------------Yellow
0.589 - 0.627 >> --------------------Orange
0.627 - 0.780 >> --------------------Red
In general, light is an electromagnetic radiation such as radio waves, x-rays e.t.c. We can
classify electromagnetic waves as visible and invisible waves.
* Visible waves: daylight, radiations from candles and lamps.
* Invisible waves: x-rays, gamma rays, radio waves.
v = fλ (v is speed of light, f is frequency and, λ is wave length)
-8 -10
Angstrom unit (Ǻ): 1Ǻ=10 cm=10 m
λ of red light = 7500 Ǻ
λ of violet light = 4000 Ǻ
λ of blue light =5000 Ǻ
λ of yellow light =6500 Ǻ

Those colours of white light having wave lengths of less than 0.3 micro meter belongs to the
ultra violet range and those with wave lengths greater than 0.8 micro meter belong to the
infrared range. The visible spectrum ranges is from 0.4 to 0.7 micrometers.
Human eye is most sensitive to light having wavelengths of about 0.555 micrometer in the
green portion of the spectrum.
Maximum power of light is radiated when the wavelength is about 0.5 micrometer, which is
approximately the wavelength at which the human eye is most sensitive.

Adama Science & Technology University Page 1


Electrical Installation Handout

Illumination refers to the provision of sufficient lighting either by natural means (e.g.
sun light) or artificial light sources (e.g. electric lamps).
Terms used in Illumination
Luminous Flux: It is the total quantity of light energy radiated/ produced per second from a
luminous body in the form of light waves. It is measured in lumens. It is represented by symbol
φ. Approximate relation b/n lumen & electric unit of power i.e. watt is given as 1
lumen=0.0016 watt (approx.)
2. Luminous Intensity (I): It is the amount of luminous flux emitted by a source per unit solid
angle. It is measured in candela or lumens per steradian. i.e. I =φ / ω,

1 Candela = 1 Lumen / steradian

Where the solid angle is measured in Steradians (ω). It is the angle generated by the surface
passing through the light point in space and periphery of the area. It was denoted by ω. Solid
angle was given by the ratio of the area of the surface to the square of the distance between the
2 2
area and the point. i.e. A / r . Since the surface of a sphere has an area equal to 4πr ;
2 2
∴ Total angle, ω=4πr / r = 4π steradians

3. Illumination (intensity of illumination) (E) - it is the luminous flux received by a surface


per unit area of surface. Its unit depends upon the units in which area is measured. It is
measured in lumens per square meter or lux or meter candle. Mathematically, E=φ/A
4. Luminous efficiency (k): a measure of unit lumens per watt (lm/W). It can be thought of as
the ‘efficiency’ of the light source.
5. Luminance, L: The luminous intensity (I) per unit of the apparent area of the source of light
(or illuminated areas).
2
L = I/A [cd/m ]
6. Coefficient of utilization:
This is a factor showing the ratio of the lumens reaching on the working plane to the total
lumens generated by the source. It depends on the dimension of the room to be illuminated,
the reflectance of the walls, ceilings, and floors, the lamp out put of reflectors and diffusers
used and the position of the lamp.
7. Maintenance Factor: The light obtained from a light source may be affected by variables
due to dire, ageing of the lamp, e.t.c. The MF takes in to account such effects.
Adama Science & Technology University Page 2
Electrical Installation Handout

Illumination Laws
▪ Inverse square law:
The illumination of a surface is inversely proportional to the distance between source &
surface, provided that the distance between the surface & the source is sufficiently large so that
source can be regarded as a point source. This is known as Inverse square Law.
Let, E1 be the illumination on surface A1,
E2 be the illumination on surface A2,
Since exactly the same luminous flux falls on A1 & A2 we can have the relation,
ф= E1A1= E2A2
E2 = E1A1/A2
2
= E1 (d1/d2)
2
i.e. E ~ 1/d Where d is the perpendicular distance from the light source.

2
E = IcosӨ/h Or cosӨ = d/h, h = d/cosӨ
Q
3 2
E =Icos Ө/d this is known as Lambert Cosine Law
Q

Thus the illumination depends not only on the perpendicular distance from the light source but
also on the angle that the light falls on the area to be illuminated.
Examples:

Adama Science & Technology University Page 3


Electrical Installation Handout

1. A 250W sodium-vapour street lamp emits a light of 22,500 cd and is situated 5m above the
road. Calculate the luminance
a) directly below the lamp and
b) at a horizontal distance along the road of 6m
2. Two light sources each having a uniform intensity of 64,000 cd is mounted 8m high. If the
illumination midway between the lamps on ground level is same as the illumination level
produced by one of the lamp vertically below it, calculate the distance between the poles.

1.2. LIGHT SOURCE AND APPLICATION


Light is a form of energy, which is radiated or sent out from a source in a waveform. It is part
of a whole family of electromagnetic wave. Light sources can either be natural (sun) or
artificial (e.g. electric lamps).
Generally, electric lamps can be classified in to:
a) Incandescent lamps
b) Discharge lamps.
When an electric current passes through a fine metallic wire, heat is produced and the
temperature of the wire increases. At low temperature the wire radiates heat energy. As the
temperature of the wire increases due to heating, it radiates heat as well as light energy.
Incandescent lamps
The incandescent lamp consists of a glass globe completely evacuated or gas filled and a fine
wire known as filament, which is heated to white heat by the passage of electric current. The
filament of modern lamps are normally made of tungsten since this material has a very high
0
melting point (3400 c) and can be manufactured in the form of a suitably thin wire. The bulbs
of smaller lamps are evacuated to prevent oxidization of the filament. But, in many lamps, an
inert gas such as argon is introduced. This enables the filament to operate at a higher
temperature without undue deterioration due to the evaporation, which tends to take place in a
vacuum.
The materials, which can be used for the filament, are: carbon, osmium, tantalum and tungsten.
These metals are selected due to their high melting points.
The main advantages of incandescent lamp are:
a) The filament has a more compact formation.

Adama Science & Technology University Page 4


Electrical Installation Handout

b) Heat losses due to conviction currents in the gas are reduced, thus giving a higher
efficiency.
There are two types of incandescent lamps:
1. Vacuum lamps
- air is evacuated from the glass bulb.
0
- operates only up to around 2000 c.
2. Gas-filled
- the glass bulb is filled with inert gases(Ne or Ar)
0
- operates up to around 2500 c.
- in gas-filled lamps, the bulb is so bright that it is given an opaque coating
internally.
The light out put of incandescent lamps is about 10 to 15 lm/W. Thus:
- a 25W IL produces about 250 to 375 lm.
- a 40W IL produces about 400 to 600 lm.
- a 60W IL produces about 600 to 900 lm.
The average lifetime of incandescent lamps is about 2000 hours when operating at rated
voltage.
An incandescent lamp gives out light at all frequencies including DC.
Incandescent lamps suffer from two disadvantages
- low efficiency and
- coloured light.
To overcome these drawbacks, the gaseous discharge lamp has been developed.
Discharge Lamps
When an electric current is passed through certain gases visible light is produced. Gases are
normally pure conductors especially at atmospheric pressure, but applications of suitable
voltage called, ignition voltage, across the two electrodes can result in a discharge through the
gas, which is accompanied by electromagnetic radiation. The wavelength of the radiation
depends up on the gas, its pressure, and the metal vapour used in the lamp. Although the
current is small, a fairly high voltage is required to maintain the discharge. For most discharge
lamps the striking voltage required is higher than the running voltage. So some means of

Adama Science & Technology University Page 5


Electrical Installation Handout

limiting the running current is required. Argon gas and sodium vapour are commonly
employed in the manufacture of gaseous discharge lamps.

● Colours of Discharge Lamps

The colour of the light emitted depends upon the type of gas used. The colour obtained from
some of the gases and vapours commonly employed are listed in the table below

Electric discharge lamps can in general be classified as cold-cathode and hot-cathode

Gas or vapour Colour of Light


Neon Red
Hydrogen Pink
Nitrogen Ivory
Mercury (low pressure) Buff
Mercury (high pressure) Blue together with strong ultra-violet emission
Sodium Bluish white with less ultra-violet emission Yellow

 Cold-cathode:

In some type of discharge lamp the electrodes are not heated. These types are therefore known
as cold cathode lamps, an example of this being the ordinary neon tube.
Uses a high voltage (3.5KV) for its operation.
They are familiar as fluorescent tubes with 25mm in diameter, either straight, curved, or bent
to take a certain form for general lighting purpose.
The electrodes of these lamps are not preheated. e.g. Neon lamps.

● Hot-cathode:

In other type of discharge lamp the electrodes are heated, as this reduces the voltage required to
strike and maintain the discharge. Lamps using heated electrodes are known as hot cathode
lamps. A typical example is the ordinary fluorescent lamp. The hot cathodes are usually in the
form of short filament which may be heated either by passing a heating current through it or by
the discharge current itself.
Are commonly called fluorescent lamps.
Are more commonly used type of discharge lamps.
Available in tube lengths of 2.5m, 1.7m 1.3m or 30cm.

Adama Science & Technology University Page 6


Electrical Installation Handout

Electrodes are heated and operating voltage is low or medium.


To assist starting the mercury vapour is mixed with argon gas.
Hot cathode lamps are produced as sodium vapour lamps, high-pressure mercury vapour lamps,
and fluorescent lamps.

● High pressure mercury vapour lamps:

It consists of a quartz tube containing mercury at high pressure and a little argon gas to assist
starting. There are two main electrodes and auxiliary electrode connected through a high
resistance. The auxiliary electrode is used to start the discharge. A choke is provided to limit a
current to a safe value.

Adama Science & Technology University Page 7


Electrical Installation Handout

Fig.1.1 typical high-pressure mercury vapour lamps: (a) basic circuit (b) modern mercury
vapour lamp.
A capacitor is connected in parallel to the lamp to improve its power factor. The initial
discharge takes place in the argon gas between the auxiliary (starting) electrode and main
electrode close to it. This causes the main electrode to heat up and the main discharge between
the main electrodes takes place.
The high pressure mercury vapour lamp has an efficiency of about 40-50lm/W they are
manufactured in 250 and 400W ratings for use on 220-250v a.c. supply mains. Their
application is mainly for industrial and street lighting, commercial and display lighting.

● Sodium vapour lamps:

Is a double glass container, the inner glass tube filled with Neon and Argon gas and some
sodium drops. When the supply is switched on, the lamp would not start as the supply voltage
is too low to start the discharge. The leak transformer is connected across the mains produces a
starting voltage of about 400v. Then the Neon Argon gas starts the discharge, and afterwards
the sodium vaporizes and the discharge continues.

Adama Science & Technology University Page 8


Electrical Installation Handout

Fig. 1.2 Sodium vapour lamps

● Fluorescent lamp (Low pressure mercury vapour lamps):

Certain materials, such as calcium halo phosphate, emit visible light whenever they absorb
ultra-violet light. This phenomenon is known as fluorescence and may be used to produce a
very efficient type of lamp. If a tube of a discharge lamp containing mercury vapour is coated
internally with an even layer of fluorescent material a considerable proportion of the ultra-
violet light caused by the discharge is converted into useful visible light. Low-pressure mercury
vapour lamps:
- consists of glass tube filled with mercury vapour at low pressure.
- is provided with two electrodes coated with electron emissive material.
- the inner wall of the tube is coated with fluorescent powder which transforms
ultraviolet radiation in to visible radiation or light.
The light out put of fluorescent lamp is 70 lm/w and has an average life of about 7500 hrs.
The application includes lighting of shops, homes, factories, streets, ships, transport (buses
and trains), e.t.c.

Adama Science & Technology University Page 9


Electrical Installation Handout

Using this tubes it is quite possible to achieve high lighting intensity without excessive
temperature rise and, owing to the nature of light sources, the danger of glare is minimized.
The efficiency of fluorescent lamp is about 40 lumens per watt, which is about three times
the efficiency of an equivalent tungsten filament lamp.
Fluorescent tubes are available in the following sizes:

Fluorescent lamp circuits

Fig 1.3 shows the basic switch start circuit, which operates as follows:
When the supply is switched on with the starter switch, s, closed a current flows through the
inductor, L, and through the lamp electrodes. The initial current heat the lamp electrodes in
readiness for striking the lamp. The starting switch is now opened making a sudden interruption
in the current flowing through the inductor and so causing a high voltage to be Lamp Electrode
Starter switch AC supply Inductor L C momentarily induced (Note that breaking an inductive
circuit causes high voltage to appear across the break in contacts, and energy is released in the
form of an arc. in this case, however, there is an easier way for the energy to dissipate- via the
gas, and the high voltage appears across the end of the tube). This voltage starts a discharge
between the two lamp electrodes and the current rapidly rises to value determined mainly by
the inductance of inductor. The starter witch is left open while the lamp is alight, the electrodes
Adama Science & Technology University Page 10
Electrical Installation Handout

maintaining their operating temperature as long as they continue to pass the discharge current.
In practice it is desirable that the starter switch should operate automatically, switching on
when the supply is first on then switching off to strike the lamp and remaining of all the time
that the lamp is alight. Due to the inductor the lamp current loges the supply voltage (at
approximately 0.5 p.f) a capacitor, C, is usually connected between the lamp terminals to
improve the overall power to an acceptable value.

● Starters

Three methods are commonly available for starting the discharge in a fluorescent tube: the
thermal starter, the glow start and the quick start.
▪ Thermal type start
The thermal type starter switch has two contacts mounted on bi-metal strips, a small heating
coil being fitted very close to the bi-metal strips but not electrical contact between them. The
contacts arc normally closed so that the main supply is first switched on full heating current
passes through the lamp electrodes as before. The current also flows through the starter heater
and so warms the bi-metal strips. After a short time the be-metal strips warms sufficiently to
bend and open the contacts thus striking the lamp. As long as the lamp remains alight current
flows through the starter heater keeping the contacts apart. a small capacitor is often connected
in parallel with the starter switch contacts to suppress radio interference.
▪ Glow type start
The glow type starter switch consists of a small bulb filled with helium and containing two
contacts, one of which is mounted on a bi-metal strip. The contacts are normally open so that
when the main supply is firs switched on full main voltage is applied to the starter contacts.
This causes a glow discharge, which warms the bi-metal strip making it bends, so closing the
starter contacts. The closing of the starter contacts allows full heating current to pass through
the lamp electrodes and also extinguish the glow discharge. After a short time the bi-metal strip
cools sufficiently to open the circuit thus striking the lamp. As long as the lamp remains alight
the voltage applied to the starter is insufficient to initiate a glow discharge and so the starter
contacts remain open until the next starting operation. A small capacitor is often connected in
parallel with the starter switch contacts to suppress radio interference.

Adama Science & Technology University Page 11


Electrical Installation Handout

Fig.1.4 Stages in striking of a fluorescent tube, using glow-type starter switch


(a) Contacts snap open, causing arc to strike between electrodes
(b) Glow discharge between bimetal contacts
(c) Bimetal heated; contacts close, bimetal then cools
▪ Quick type start or Instant type start
In the case of the quick start or instant start, starting is achieved by the use of autotransformer
and an earthed metal strip in close proximity to the tube.
When the supply is switched on, mains voltage appears across the end of the tube, and the
small part of the winding at each end of the transformer energizes the filaments, which heat up.
The difference in potential between the electrodes and the earthed strip causes ionisation, which
spreads along the tube.
● Stroboscopic Effect
A disadvantage of fluorescent lamp is that as the alternating discharge current passes through
zero twice every cycle the light produced tend to flicker at twice of main frequency. Although
this effect is not noticeable to the eye, machinery rotating at certain speed may appear to be
stationary or moving more slowly than it really is. This is known as the stroboscopic effect and

Adama Science & Technology University Page 12


Electrical Installation Handout

is obviously a cause of danger in situations such as workshops where rotating machinery is in


use.
a) If a three-phase supply is available the stroboscopic effect can be minimized by connecting
lamps to alternate phases. As the lamps in the circuit attains their maximum and
minimum values, the light output in sequence of overall illumination is kept practically
constant thereby keeping the stroboscopic effect to a minimum.
c) If only a single-phase supply is available then the ‘lead lag’ circuit shown in figure below
may be used. In this circuit lamp A, is supplied via and inductor and so has a lagging
current, both an inductor and a capacitor are connected in series with lamp B. The
inductor is required to supply the initial starting surge. But, when the lamp is a light, the
effect of the capacitor predominates so that the lamp takes a leading current. It follows
that when one lamp is producing its minimum light output the other is producing its
maximum and so, by using this circuit the stroboscopic effect is greatly reduced.

1.3. PRACTICAL LIGHTING SCHEMES

A good lighting system should produce:

 Uniform illumination of not less than the required value.

 It should be free from glare and hard shadows.

In fact and endeavour should be made to have quality of light as close to day light as possible.

The interior lighting schemes may be classified as: -


i. Direct light
ii. Semi- direct lighting
iii. Semi-indirect lighting
iv. Indirect lighting and
v. General lighting
1. Direct light: - the most commonly used type of lighting scheme. In this scheme more than
90% of total light flux is made to fall directly on the working plane with the help of deep
reflectors. Though it is more efficient but causes hard shadows and glare. It is mainly used
for industrial and general out-door lighting.

Adama Science & Technology University Page 13


Electrical Installation Handout

2. Semi-direct lighting: - in this lighting scheme 60-90% of the total light flux is made to fall
down wards directly with the help of semi-direct reflectors. The remaining light is used to
illuminate the ceiling and walls. Such a lighting scheme is best suited to rooms with high
ceiling where there is a high level of uniformity of illumination is desired.
Besides this scheme avoids glare, it also improves the efficiency of the system with
reference to the working plane.
3. Semi indirect lighting: -in this scheme 60-90% of total light flux is thrown up wards to the
ceiling for reflection and the rest reaches the working plane directly except for some
absorption by the bowl. This lighting scheme has soft shadows and is glare free. It is mainly
used for indoor decoration purpose.

Adama Science & Technology University Page 14


Electrical Installation Handout

Fig 1 a) Type of reflectors b) Lighting fittings, types and performance

Adama Science & Technology University Page 15


Electrical Installation Handout

4. Indirect lighting scheme: - in this scheme more than 90% of total light flux is thrown
upwards the ceiling for diffuse reflection by using inverted or bowl reflector. In this scheme
the glare is reduce to minimum. The resulting illumination is soft and more diffused. The
shadows are less prominent and the appearance of the room is much improved. It is used for
decoration purpose in cinemas, theatres and hotels etc. and in areas where troublesome
shadows are produced if direct light in lighting is employed.
5. General lighting: - in this scheme lamps made of diffusing glass are used, which gives
nearly equal illumination in all directions.
All fittings may be reduced to five basic types according to their light distribution as shown
in fig.1
Design of lighting schemes
The lighting scheme should be such that it may,
I. provide adequate illumination
II. Provide light distribution all over the working plane as uniform as possible
III. Provide light of suitable colour.
IV. Avoid glare and hard shadows as far as possible

1. Illumination level: - In order to see the details of the things that surround us the source has
to illuminate them very well in order the objects take the necessary brightness. For each
type of work there is a range of brightness most favourable to output in terms of quality and
quantity.
Degree of illumination, to give necessary brightness to objects, depends upon:
I. the size of the object and distance of the observer.
II. Contrast between the object and background. Greater the contrast greater will be the
illumination required to distinguish the object properly.
III. speed of object - Speedy object require more illumination.
IV. duration of gazing - Object seen for long duration of time require more illumination.
2. Uniformity of Illumination: - It has been found that visual performance is best if the range
of brightness within the field of vision is not greater than 3:1, which can be achieved by
employing general lighting in addition to localised lighting. Otherwise due to the frequent

Adama Science & Technology University Page 16


Electrical Installation Handout

accommodation of pupil or iris of the eye, fatigue is caused and it creates psychological
felling of loneliness, gloom and unfriendliness.
3. Colour of light: - The appearance of the body colour entirely depends upon the colour of the
incident light. In general the composition of the light should be such that the colour appears
natural.
4. Shadows: - In lighting installation, formation of long and hard shadows causes fatigue and
are undesirable. However a certain amount of shadow is desired as it helps to give shapes to
solid objects and make them easily recognized. But there is one exception to this i.e. in
drawing offices, where we are to see flat surfaces. Hard and long shadow can be avoided
by: a) Rising a large number of luminaries mounted at a height not less than 2.5m.
b) By using wide surface of light - using globes or indirect lighting system.
5. Glare: - Glare is generally produced by very bright sources of light, which emit light directly
or at very low angle towards the viewer. This causes the person to neglect the other
surrounding objects, as they appear darker and is a major cause of road accidents. The glare
is also caused by highly polished surfaces when the angles are incorrect. This also tends to
damage retina of the eye. Glare may be direct or indirect. Motorcar headlights produces
direct glare.

In other words glare may be defined as the brightness within the field of vision of such a
character as to cause annoyance, discomfort interference with the vision or eye fatigue.
Therefore, glare is to be avoided at any cost. For this purpose very bright point sources of light
should be avoided. Highly reflective surfaces should be replaced by Mat surfaces, which cause
diffusion. The angle of light should be such that it does not dazzle the person. A surface, which
is almost free from mirror reflection, is called a mat surface. The factories act discusses the
matter and lays down regulations to prevent it. If a glare is produced by a lighting point, such as
incandescent lamp, it can be avoided by the use of globes or making the light source at such a
height that to place them above the ordinary range of vision.

In fulfilling the above requirements, in designing a good lighting scheme, we have to consider

i. The intensity of illumination required

ii. The selection of the required lamps and fittings

iii. The size of the room

Adama Science & Technology University Page 17


Electrical Installation Handout

iv. The conditions under which the illumination is used etc

The recommended illumination level for various occupancies is shown in Tables given on page
40 and subsequent.

The choice of lamps for different type of occupancies differs. Tubular fluorescent and tungsten
filament lamps can be used when lighting is to be done in small premises. But in large
premises, the lighting can be carried out by using high intensity sources such as mercury or
sodium discharge lamps.

The following are some of the conditions that should be considered when the illuminations are
used:

► Utilization Factor (η whole light radiated by the lamps doesn’t reach the working plane.
B) the

the ratio of lumens reaching the working plane to the total light given out by the lamp or lamps,
when the installation is new, is known as utilization factor or coefficient of utilization. the
value of utilization factor depends upon:
i) the mounting height of lamps
ii) area to be illuminated
iii) type of lighting scheme
iv) colour of the surrounding, etc.
► Spacing Luminaries: - correct spacing is of great importance to provide uniform
illumination over the whole area. The ratio of the horizontal spacing between rows to the height
of the luminaries above the working plane, called space to height ratio, depends quite on
luminous output, type of lighting scheme and on the extent of candlepower distribution curve
of the luminare. Mounting height is largely governed by the type of the building and type of
lighting scheme employed.
The term “general lighting” implies that the illumination at the working level
should not vary substantially throughout the room. Therefore it is apparent that the
fitting for general lighting should not be so placed that the illumination received
from each fitting overlaps and builds up that of its neighbours. That means the
distance lights source from the wall should be equal to one half of the distance
between two adjacent light sources. Also distance between lighting fittings should
not exceed 1.5 times the mounting height.

Adama Science & Technology University Page 18


Electrical Installation Handout

In the case of direct and semi-direct luminaries, it is generally advisable to mount them high
considering a normal ceiling height and average size floor area. With fluorescent luminaries it
3
is good practice to aim at a value of unity for this ratio and to set on upper limit of / . In the
4

case of indirect and semi-indirect luminaries, it is a good practice to aim at a horizontal spacing
between rows approximately equal to the height of the ceiling above the working plane, and in
1
no case should the horizontal spacing exceed 1 / times this height. In case of direct and semi-
3

direct lighting scheme.

► Colour of Surrounding Walls: - the illumination in a room depends upon the light reflected
from walls and ceilings. White walls and ceilings reflect more light as compared to collared
ones.

► Maintenance Factor - as we are to continue to use the installation, the illumination


produced considerably decreases due to ageing of the lamps and accumulation of dusts on the
lamps, reflectors, ceiling and walls. Its value is more if there is much as the ageing problem
increases, etc. The value is mostly ranges between 0.8 and 1. The other term used is
depreciation factor, which is merely the inverse of the maintenance factor. Its value is more
than unity.
Methods of lightning calculation
In order to estimate the number and the type of light fittings required to suit a particular
environment, it is necessary to know what level of luminance is required, the area to be
illuminated, the maintenance factor and the coefficient of utilization, and the efficiency of the
lamps to be used. A number of methods have been employed for lighting calculations among
which may be mentioned:

A. Watts per square metre method


B. Lumen or Light flux method
► Watts per Square Meter method: - applicable for rough calculations. It consists in making
an allowance of watts per square meter of area to be illuminated accordingly to the illumination
desired on the assumption of the average figure of an overall efficiency of the system.
2
According to NEC 220-3(d) this figure is about 3 watt per ft .

Adama Science & Technology University Page 19


Electrical Installation Handout

Example: - A house has an external dimension of 30ft by 50ft. If an 80w fluorescent lamps,
and 220V supply is used, determine the size of the service wire and the number of lamps
required.
Solution:
A = 30ft X 50ft = 1500ft
Total wattage required = 1500 X 3w = 4500w ⇒ 4.5Kw
No of lamps required = 4.5Kw/80w = 56.1 ⇒ 56 lamps - each 80w
Current carrying capacity = 4.5Kw/220V = 20.5A
Therefore, the size of the cable will be conductor if there is no any correction factor.
► Lumen or Light flux or efficiency method: - it is the most advisable method to be used. Lumens' r
calculated as:

Adama Science & Technology University Page 20


Electrical Installation Handout

1. A road 300 m long is required to be illuminated by providing 40W fluorescent lamps. The width of th
lighting scheme for obtaining minimum level of illumination of 0.6 lux assuming a mounting height
utilization. (In designing you have to determine the distance between the poles and find out the num
given distance.)
2. A light assembly shop, 15m long, 9m wide and 3m up to trusses, is to be illuminated to a level of
maintenance factors are respectively 0.9 and 0.8. Make a scale drawing of the plan of the shop and
points, assuming the use of tungsten lamps and dispersive metallic reflectors. You may assume a lam
spacing height ratio of unity.
2
2. A hall 30m X 15m height is to be provided with a general illumination of 120 lm/m taking a co
depreciation factor 1.4 and appropriate space-height ratio, determine the no. of fluorescent tubes req
height and total wattage. Take luminous efficiency of fluorescent tubes as 40lm/W for 80-watt tube.
 Inverse square law method
This method is applicable where the illumination at a point due to one or more sources of light is required, th
in the particular direction under consideration being known. If we were to illuminate a surface by means o
above it, measure the illumination at the surface, and then move the lamp twice as far away, the illumination
times less. If it were moved away three times the original distance the illumination would be nine times less

Adama Science & Technology University Page 21


Electrical Installation Handout

Fig. 1.6
Hence it will be seen that the illuminance on a surface is governed by the square of the vertical distance of the
1.6).
Example
A light source of 900 candelas is situated 3 m above a working surface. (a)
Calculate the illuminance directly below the source. (b) What would be the
Illuminance if the lamp were moved to a position 4 m from the surface?
Cosine rule
From Fig. 10.16 it will be seen that point X is further from the source than is
Point Y. The illuminance at this point is therefore less. In fact the illuminance
at X depends on the cosine of the angle . Hence,

Adama Science & Technology University Page 22


Electrical Installation Handout

Fig. 1.7.
Example
A 250 W sodium vapor street lamp emits a light of 22 500 cd and is situated 5 m above the road. Calcula
below the lamp and (b) At a horizontal distance along the road of 6 m. (Fig. 1.8).

Fig. 1.8
From Fig. 1.8, it can be seen that the illuminance at A is given by
1 22,500
EA    900lx
d2 25
The illuminance at B is calculated as follows. Since the angle _ is not known, it can be found most simply by
AB 6
tan     1.2
d 5
From tangent tables, ϴ=50.20 and from cosine tables,
Cos 50.20=0.64
I cos3  22,500 x 0.642
Therefore, EB    236lx
d2 25

Adama Science & Technology University Page 23


Electrical Installation Handout

Allowable Illumination Levels To Various Locations & Rooms Of (Roads, Offices, Schools And Factories)

ROADS
Classification of Type of Road Average level of
Lighting Installation illumination on road
surface
Group A Important traffic route carrying 30
1
fast traffic
Group A Other main roads carrying a 15
2
mixed traffic
Group B Secondary roads with 8
1
considerable traffic
Group B Secondary road with light 4
2
traffic
Note- Excellent illumination is considered when the distance apart is not more than 8 times the height
of the luminaries. Normal spacing for standard lamps is 50 metres with a mounting height of 8 metres.
Offices
Level of Illumination Place
(lux)
1500 - 750 Offices, design and drawing rooms
750 - 300 Offices, conference rooms, computer rooms
300 - 100 Kitchens, ordinary work rooms, corridors,
stairways and toilets
Schools
1500 - 300 Precision drawing or drafting, laboratory rooms
750 - 200 Class rooms, library reading rooms, experiment
demonstration rooms, staff rooms and gymnasium
300 - 75 Lecture halls, assembly rooms, locker rooms,
corridors, stairways and toilets

Factories

Adama Science & Technology University Page 24


Electrical Installation Handout

Level of Illumination Place


(lux)
3000 - 1500 Where such work as inspecting, testing, selecting
and specially as machine tool operation is carried
out
1500 - 750 Inspecting, testing, selecting, welding and machine
shops
750 - 300 Inspecting, testing, selecting, welding and
machining and wrapping.
300 - 150 Wrapping and crating, welding and machining.

Data On Commonly Used Light Sources


Wattage Nominal Nominal Luminous Flux
Without With A.C. Current Without With Base
Ballast Voltage Luminescent material
in watt in watt In voltage in amp in lumen in lumen
With yttrium vanadate luminescent material
50 59 220 0.6 --- 2000 E 27
80 89 220 0.8 --- 3800 E 27
125 137 220 1.15 --- 6300 E 27
250 266 220 2.15 --- 13500 E 40
400 425 220 3.25 --- 23000 E 40
700 735 220 5.4 --- 40000 E 40
1000 1045 220 7.5 --- 55000 E 40
Metal halide lamps (with dysprosium iodide)
250 275 220 3.0 21000 17000 E 40
360 385 220 3.5 28000 26000 E 40
1000 1040 220 9.5 80000 80000 E 40
2000 2070 380 8.8 190000 80000 E 40
3500 3650 380 18.0 300000 --- E 40

Adama Science & Technology University Page 25


Electrical Installation Handout

High Pressure Mercury Vapour Lamps


Wattage Nominal Luminous Flux
Without With a.c. Nominal Without With Base
Ballast Voltage Current Diffusing glass
in watt in watt in voltage in amp in lumen in lumen in watt
70 83 220 1.0 --- 5800 E 27
150 170 220 1.8 14500 14000 E 40
210 232 220 2.25 --- 18000 E 40
250 275 220 3.0 25500 25000 E 40
350 385 220 3.45 --- 34000 E 40
400 450 220 4.4 48000 47000 E 40
1000 1090 220 10.3 130000 120000 E 40

General-purpose lamps (220V-230V)


Wattage Luminous Flux Base Wattage Luminous Base
at 225V Voltage Flux at 225V
W lm W
40 430 E 27 300 5000 E 40
60 730 E 27 500 8400 E 40
100 1380 E 27 1000 18800 E 40
200 3150 E 27 75 1190 E 40
15 125 E 27 150 2880 E 40
25 235 E 27 750 17040 E 40
Fluorescent lamps

wattage Nominal Length Luminous flux,


Current of lamp acc. to type of lamp
and light colour
Without With out With mm
Ballast

Adama Science & Technology University Page 26


Electrical Installation Handout

W W A lm
Standard Construction
15-2 19.5 0.33 438 500 to 720
18 23 0.37 590 1300 to 1450
20 25 0.37 590 700 to 1250
30-2 39 0.365 895 1150 to 1800
36 45 0.43 1200 3100 to 3450
38 48 0.43 1047 3200 to 3400
40 49 0.43 1200 1600 to 3200
42 52 0.535 1047 2000 to 2500
58 69 0.67 1500 5050 to 5400
65 76 0.67 1500 2600 to 5200
Indium amalgam type, for higher ambient temperature
40 49 0.44 1200 2000 to 2500
65 76 0.7 1500 3300 to 4000

Utilisation Factors

Types of Lighting η Types of Lighting η


B B

Direct 0.6 to 0.45 Semi-indirect 0.45 to 0.3


Semi-direct 0.55 to 0.45 Indirect 0.35 to 0.25
General diffuse 0.5 to 0.35 Indirect ceiling lighting
RECOMMENDED ILLUMINATION LEVELS
SERVICE ILLUMINATION LEVEL (Lux )
Building Areas

Adama Science & Technology University Page 27


Electrical Installation Handout

- Circulation areas, corridors 100


- Stairways, Escalators 150
- Cloak rooms, Toilets 150
Assembly Shops
- Rough work: Heavy machinery assembly 300
- Medium work: Engine, Vehicle body assembly 500
- Fine work: Electronic and Office machinery 750
assembly
Offices
- General offices, Typing, Computer rooms 500
- Deep-Plan general offices 750
- Drawing offices 750
Schools
- Class rooms, Lecture theatres 300
- Laboratories, Libraries, Reading rooms and Art 300
rooms
Shops, Stores and Exhibition Areas
- Conventional Shops 300
- Self-service Shops 500
- Supermarkets 750
Museums and Art galleries
- Light - Sensitive exhibit 150
- Exhibits insensitive to light 300
Public Buildings
- Cinemas 50
- Auditoriums 150
Theatres and Concert Halls
- Auditorium 100
- Foyer 200
Dwelling Houses

Adama Science & Technology University Page 28


Electrical Installation Handout

- Bed rooms: -
- General 50
- Bed-Head 200
Nursery 150

Adama Science & Technology University Page 29


Electrical Installation Handout

Chapter 2
Electrical installation in consumer premises
2.1. Electrical regulations and Standards

General information on wiring regulations


Regulations and standards are two different things: regulations are the law and must be
complied with; standards on the other hand are advisory. They are closely linked together.
A standard is a document specifying nationally or internationally agreed properties for
manufactured goods and equipment. As part of this process the manufacturer must show how
the risks and hazards that the equipment will present have been overcome or protected against.
This information is placed in the Technical Document of the equipment so that it can be
inspected should there be a query by the authorities regarding the equipment’s safety or
performance. The best way to show compliance with a regulation is to use recognized standards
in the design and construction of the product, thereby fulfilling the requirements of the
regulation. The British Standards Institute (BSI), as well as other European and international
bodies, publish standards which give recommendations and guidance on – amongst other things
– the selection and use of various electrical components and cables.
Electrical safety and wiring regulations are here to help to make the electrical systems and
installations safe. They give the basic safety needs, define which kind of circuits to use,
material to use and generally specify wiring colors. This standardization makes is easier for
electrical installers to make wiring right, make them safe and for somebody else to fix them
later safely if that is needed.
Electrical code is a compromise between safety and cost. Much of the world considers 220 V
(220-240V) to be safe enough for standard residential outlets and lighting, and they can wire a
house with about one-half the copper compared to countries that use 120 V. Those countries
which use 120V considered that 220V to be too dangerous for most residential uses.
Some other wiring practices have their good and bad sides. Using a common neutral, saves
copper (or aluminum), but carries some risk, that if done improperly, an overloaded or open
neutral situation may occur. Using aluminum in wiring saves costs in wiring material, but if
connections done to aluminum wiring are not done carefully they can become loose and cause

Adama Science & Technology University Page 30


Electrical Installation Handout

fire danger (nowadays aluminum is not generally used in residential installations, usually only
on large power feed cables going to distribution board power input).

USA/Canada wiring regulations


The National Electrical Code (NEC) is a set of regulations which specify the wiring and safety
practices in use in USA.
The NEC speaks to a nominal line voltage of 120 volts with a +/- 5% tolerance for a low of 114
volts and a high of 126 volts. Most appliances and electronic equipment, etc. is designed to
work within that voltage range without problems. At higher and lower voltages, risk of damage
increases although most modern appliances are remarkably tolerant.
The mains power frequency used nowadays in USA is 60 Hz. Many frequencies were used in
the 19th Century for various applications, with the most prevalent being the 60 Hz supplied by
Westinghouse-designed central stations for incandescent lamps. The development of a
synchronous converter which operated best at 60 cycles encouraged convergence toward that
standard. Around 1900, the introduction of the high-speed turbine led to settlement on two
standards: 25 cycles for transmission and for large motors (this had been a compromise
decision at Niagara Falls), and 60 cycles for general purpose systems.
In USA homes get two-phase 120v. In a typical home in the states you have 3 cables coming
into your panel from the service. Basically, there's a center-tapped step-down (few kV
distribution voltage to 120V+120V AC) transformer on the electrical line pole, with the tap
earthed (at least in theory) and each socket connected across one side of the transformer. Larger
devices (electric stoves, central air conditioning units, electric dryers, etc.) are wired across the
entire transformer, receiving 240v.
The power distribution in typical residential house in USA is implemented so that locally (near
the house) a single phase transformer provides a 240 volts center tapped output. This center tap
is grounded at the transformer and called the neutral wire, and then the three wires are run into
each house along the street. The two live (hot) wires each separately provide 120 volts relative
to the neutral wire and go to wall outlets to run low power devices (lights, TVs etc.). Power
hungry devices like electric stoves and water heaters which require 240 volts are connected
across the two live or hot wires. These two 120V hot lines with 240V between them wiring
system is sometimes called "two phase power".

Adama Science & Technology University Page 31


Electrical Installation Handout

Each house also has a good local ground which is connected to input mains power neutral wire.
For example typical small house could use system such as an 8 ft ground rod or a cold water
pipe which also goes to each power outlet as the ground pin.
The typical wall outlet in home in USA outputs 120 volts AC. The maximum current that
should be allowed to be drawn from a normal outlet is 15 amps. That means that nothing over
1800 watts should be plugged into that circuit. The 1800 watts is the total for all devices on that
same circuit fed by one breaker in the supply panel. There are grounded and ungrounded power
outlets. In grounded outlets the National Electric Code (NEC) requires the ground pin to be
first-make, last-break. That's why they're longer in mains connectors than the other contacts,
and I doubt you'd disconnect a ground pin without disconnecting the blades. This connector in
the wall is wired in the following way: The ground pin should be at the bottom, the "hot" blade
should be on the right and the neutral blade (the wider one) should be on the left. The
ungrounded outlet is wired in the same way, just without the ground pin.
For special uses there are sometimes higher current outlets available. Sometimes you can see a
20A 120V AC outlet (a little different AC connector than normal 15A). Some very high power
loads like air conditioners usually use 240V two phase outlets (15A or 20A). 3-phase power is
not typically available in homes in the US. 3-phase power is it is common in commercial and
industrial installations.
Most household circuits are 15 amp (15 amp receptacles, 14 gauge wire, 15 amp breaker or
fuse) Today's code requires 20 amp (12 gauge wire and 20 amp receptacles) in kitchens and
dining rooms, and 12 gauge wire to bathroom outlets, although these are usually 15 amp outlets
so one should not exceed 15 amps. Breakers are designed to trip not so much at eh amperage
rating (15, 20 etc) but when they get hot - pulling too much current through a wire heat it up,
too hot and the breaker will trip. It the wire is over 100 feet from the panel to the point of use,
the amperage rating is dropped down one, or else the wire is upped to next thicker wire
thickness. It is typical that electrical panel manufacturers also make the circuit breakers that go
into their panels. Circuit breakers are not interchangeable in other manufacturers' electrical
panels.
Circuits are designed so that under normal conditions (whatever those are) that the load will not
be more than 80% of the rating - so a 15 amp circuit (120volts x 15 amps = 1800 watts x 80% =
1440 watts) should not regularly exceed 1440 watts. That is why today each bathroom outlet

Adama Science & Technology University Page 32


Electrical Installation Handout

gets its own 20 amp circuit; a kitchen should have at least 2 small appliance circuits (for
outlets) the disposal, dishwasher, fridge and microwave should each be on their own individual
20 amp circuit.
Electrical work must be done so that it meets the local and national codes. For most works it
means that you must be a licensed persons and the work may need to be inspected before it is
taken to use.
The National Electrical Code says that electrical equipment be "suitable" for use, and says that
"suitability of equipment MAY be evidenced by listing or labeling". However many localities
by local authorities DO require appropriate listing. Most all local and national building codes
require that eligible equipment be "safe", and that one of the ways demonstrate safety is for the
product to have earned a safety certification from a Nationally Recognized Testing Lab ( like
UL ). In practice this usually requires that all equipment must be listed, if listed equipment is
available. Listing is done by 3rd party safety testing agencies, two of which are Underwriters
Laboratories (UL) and Electrical Testing Laboratories (ETL). These agencies list a product if it
has successfully passed the required testing. Standards for testing and listing are established by
the agencies. Standards are not available for all products. UL listing on electrical equipment is
required for code compliance in most areas. UR listing is usually acceptable if the component is
being used in a UL approved panel or piece of equipment.

General

 Aluminum Wiring: Do I Have It And What Should I Do? - Certain properties of aluminum
can cause deterioration of connections, possibly presenting a fire hazard after years of
service. The problem is most marked in homes built in USA during the mid- to late-1960's.
Usage of aluminiun in wiring varies between countries.
 Ampacity Ratings for Feeder Cable - as used in USA
 Cable Amperage Guide - ratings used in USA
 Common Electrical Wiring Problems Found in Older Homes
 Construction Electrician
 Construction Electrician Basic - This is a full book on-line.
 Electrical Symbols
 Energy Star Programs - ment to reduce the standaby power used by equipments

Adama Science & Technology University Page 33


Electrical Installation Handout

 Do-it-yourselfer shocked by city's electrical code - Generally a permit is needed to "install,


change or repair any hard-wired electrical system.". But there are local exceptions to those
rules, so you need to be careful what you are allowed to do and what you are not allowed
to do.
 In home electrical safety check - applies to households in USA
 Ground-Fault Protection on Construction Sites - With the wide use of portable tools on
construction sites, the use of flexible cords often becomes necessary. Hazards are created
when cords, cord connectors, receptacles and cord- and plug-connected equipment are
improperly used and maintained. Generally, flexible cords are more vulnerable to damage
than is fixed wiring. GFCIs can be used successfully to reduce electrical hazards on
construction sites.
 Incandescent Dimmer Installation - example manual how to install light dimmer to wall
wiring (instructions for USA).
 National Electrical Code Internet Connection Free Stuff - lots of information
 Ten Tips on becoming familiar with the National Electrical Code
 The National Electrical Code - slide set tells what is it all about
 Underwriters Laboratories Changes Color Coding of Conductor Requirements for Power
Cords in UL 1950 and UL 2601 - For years, the colors of individual conductors in non-
detachable power cords for use in North America have traditionally been black for line,
white for neutral, and green for earth (ground). Now, two major equipment standards, UL
1950, Information Technology Equipment, and UL 2601, Medical and Dental Equipment,
are beginning to require the more traditional European conductor color coding: brown for
line, light blue for neutral, and a combination of green and yellow for ground. Now, UL
and CSA have harmonized with these IEC standards to ensure standardization of these
products around the world.
 Why is that some appliances have a 3-prong outlet while others have only 2 prongs?

Safety
Safety is of utmost importance when working with electricity. Develop safe work habits and
stick to them. Be very careful with electricity. It may be invisible, but it can be dangerous if not

Adama Science & Technology University Page 34


Electrical Installation Handout

understood and respected. The electrical installations should be properly designed, properly
installed and use the necessary safety devices needed on this type of application.
Fuses and circuit breaker are devices which protect wiring and devices agains short circuits and
overloads. Circuit breaker is a protective device for each circuit, which automatically cuts off
power from the main breaker in the event of an overload or short. Only a regulated amount of
current can pass through the breaker before it will "trip." The fuses and circuit breakers
generally connect to the live wires (the ungrounded phase conductor). Where circuit breakers
are used to protect sub-fused circuits, the circuit breakers will almost always trip before the
fuses blow. Circuit breakers also make accidental short circuits less violent.
Ground fault circuit breakers offer protection against more than just overloads, Ground fault
protection devices (RCD, GFI, GFCI) are good protection devices to give extra protection
agains accidents. GFCI's are most often used for protection from hazards associated with
"portable" appliances in wet damp areas. This kind of devices are generally used in dangerous
environments like places near water (electrical outlets outside, bathroom outlets, kitchen
outlets), in construction sites and in work shops for example. As far as the RCD's / GFI's
(Residual Current Device) / (Ground Fault Interrupter) go, they are not infallible. It is still
possible to pass enough current to kill without reaching the tripping current, and it's also still
possible to get a live to neutral shock which will look like a normal load to the breaker. These
things should also be tested quite regularly since they can fail. For personal protection 30 mA
offers a high degree of protection and will operate by cutting off the earth fault current well
within the time specified in the IEC Publication 1008/1009. IEC Standard 1008/1009 of 30 mA
sensitivity for domestic and personal protection with the tolerance of 30 mA plus zero and
minus 50%, that is, a range from 15 mA to 30 mA.

 Aluminum Wiring in Residential Properties: Hazards & Remedies


 Electrical OSHA training material - Examination, Installation, and Use of Equipment,
Identification of Disconnecting Means and Circuits, Working Space About Electrical
Equipment, Guarding of Live Parts, Identification of Conductors, Polarity of Connections,
Grounding, Grounding Path, Grounding of Equipment Connected by Cord and Plug,
Ground Fault Circuit Interrupters (GFCI's), Cabinets, Boxes, and Fittings, Flexible Cords
and Cables

Adama Science & Technology University Page 35


Electrical Installation Handout

 Electrical Safety and Health - article collection


 Electrical Wiring: Updating for the 21st. Century! - Information on common problems
found in older homes and how to solve them.
 Enclosure Classifications - Industry Standards Enclosure Types for All Locations, National
Electrical Manufacturers Association (NEMA Standard 250), NEMA/EEC to IEC
 GFCIs
 G.F.C.I. by Sam Goldwasser - good description of GFCI operation
 GFCI Testing
 Ground-Fault Protection on Construction Sites - Insulation and grounding are two
recognized means of preventing injury during electrical equipment operation.
 Hazardous (Classified) Locations - The National Electrical Code (NEC) defines hazardous
locations as those areas "where fire or explosion hazards may exist due to flammable gases
or vapors, flammable liquids, combustible dust, or ignitable fibers or flyings."
 Hazardous Location Classifications - according NEC
 Lightning Protection
 Making Electrical Connections - Making electrical connections is a fairly common
procedure but needs to be done correctly and carefully. If you don't make tight connections,
heat can build up between the conductors and cause a fire.
 Multiwire Branch Circuit Wiring Precautions when using Stand-Alone 120 VAC Inverters
or Generators - document describes conventional home wiring and multiwire brach circuit
wiring
 NFPA's Home Page - latest information about the National Fire Protection Association
(NFPA) and it's standards like National Electric Code
 Understanding Industrial Wiring: 3-Phase Electric

There are three types of standards that are important to us:


British Standards (BS),
European Harmonized Standards (EN or BS EN),
International Standards (IEC)

Adama Science & Technology University Page 36


Electrical Installation Handout

These are of course mainly the concern of the designer but it is as well to be aware that they
exist, as it may explain why one component is used instead of another and why only those
components designated in the parts list must be used.
Standards of most importance to us includes the BS EN 60204 (Safety of Machinery Electrical
Equipment of Machines) and BS EN 60947 (IEC947) (Low Voltage Switchgear and Control
gear).
 BS EN 60204 covers the way in which the electrical equipment should be constructed and
includes everything from the selection of components, through the sizes, types and colour of
the wiring, to the electrical tests that should be done on the finished equipment. Within BS EN
60204 there are references to other standards, including BS EN 60947 that will give more detail
on individual parts or components.
 BS EN 60947 and the international standard IEC 947 are in seven parts, giving the specification
and other requirements of the individual components we will use in the equipment.
Part 1: General Requirements-defines the rules of a general nature to obtain uniformity in
requirements and tests. Each of the following parts deals mainly with the characteristics,
conditions for operation, methods for testing and marking requirements of the various electrical
components.
Part 2: Circuit-breakers.
Part 3: Switches, disconnectors, switch-disconnectors and fuse combination units.
Part 4: Contactors and motor starters including short circuit and overload protection devices.
Part 5: Control circuit devices and switching elements.
Part 6: Multiple functions equipment such as that used for automatic emergency power
switching.
Part 7: Ancillary equipment such as terminal blocks used to connect copper conductors.
Basically our control equipment panels should be built to conform to the requirements of BS
EN 60204 using components manufactured to conform to the requirements of BS EN 60947
and other related component standards and approvals. An approved component is one whose
manufacture and performance has been checked and proven to meet the specifications set by
the standards authority of an individual country. For example, a part approved in the UK would
be ‘BS approved’. These approvals may be important if the equipment is to be exported.
Some other standards authorities are:

Adama Science & Technology University Page 37


Electrical Installation Handout

 USA ANSI – approvals are made by the Underwriters Laboratory and marked UL.
 Canada, CSA.
 Denmark, DEMKO.
 Italy, CEI.
 Norway, NEMKO.
 Germany, DIN/VDE.
 France, NF/UTE.
 Europe, CENELEC.
Some other BSI documents
 PD 2754: Parts 1 and 2.
Part 1 deals with the classification of electrical and electronic equipment with regard to
protection against electric shock, for example whether it is earthed, double insulated or uses a
safe, low voltage supply.
Part 2 is a more detailed guide to the requirements of the various classes as defined in Part 1.
 BS 7452: Specification for transformers of the type used in control panels. Equivalent to IEC
989: Control transformer specification.
 BS 3939: Graphical symbols. Provides comprehensive details of the symbols to be used in
electrical, electronic and telecommunication diagrams. It is published in 12 parts and is broadly
the same as EN 617 – Parts 2 to 12.
 BS EN 60073: Colors for indicator lamps, push buttons, etc. Provides a general set of rules for
the use of certain colours, shapes, positioning requirements of indicators and actuators to
increase the safety and operational efficiency of equipment.
 BS EN 60204 also provides guidelines specific to the electrical controls for machinery.
 BS EN 60529: Specification for classification of degrees of protection provided by electrical
enclosures. Also known as ‘IP Codes’, it uses a two or three digit number to define to what
degree the enclosure is sealed to protect the contents against dust, moisture and similar
damaging substances.
 BS 6231: Specification for PVC-insulated cable for switchgear and control gear wiring. This
deals with the requirements for the wires and cables used in the wiring of control panels up to
600 V/1000V.

Adama Science & Technology University Page 38


Electrical Installation Handout

The IEE regulations (BS 7671)


The Institute of Electrical Engineers publishes its Regulations for Electrical Installations, which
cover the design, selection and construction of electrical installations in buildings generally,
and provide guidance for safety in the design and construction of electrical equipment.
Although mainly concerned with electrical systems in buildings, the information is applicable
to machine control panels because they will be connected to the building’s electrical system.
These are now published as BS 7671. In addition there are guidance notes from the Health and
Safety Executive, and Specifications and Regulations from the Department of Trade and
Industry, BSI and the Institute of Electrical Engineers. You may be interested to know that all
the standards referred to concern ‘low voltage’ equipment. Low voltages as defined by the IEE
are those up to and including 1000 volts AC or 1500 volts DC.
2.2. Electrical Installation materials, components and accessories

There are various kinds of electrical insulation materials, components and accessories use for
electrical installation. Some of them are explained in tables below

An important consideration in selecting symbols is that they should be, as far as possible, self
explanatory and easy to draw.

Table 2.1. Wires and connections

Component Circuit Symbol Function of Component

To pass current very easily from one part of a circuit to


Wire
another.

A 'blob' should be drawn where wires are connected (joined),


Wires joined ‘crossroads’ should be staggered slightly to form two T-
junctions, as shown on the right.

In complex diagrams it is often necessary to draw wires


Wires not joined crossing even though they are not connected. The 'bridge'
symbol shown on the right is preferable

Table 2.2. Symbol of wires

Adama Science & Technology University Page 39


Electrical Installation Handout

1. Power Supplies

Component Circuit Symbol Function of Component

Supplies electrical energy. The larger terminal (on the left) is


Cell positive (+). A single cell is often called a battery, but strictly a
battery is two or more cells joined together.

Battery Supplies electrical energy. A battery is more than one cell.

DC supply Supplies electrical energy. DC, always flowing in one direction.

AC supply Supplies electrical energy. AC, continually changing direction.

A safety device which will 'blow' (melt) if the current flowing


Fuse
through it exceeds a specified value.

Two coils of wire linked by an iron core. Transformers are used to


Transformer
step up (increase) and step down (decrease) AC voltages.

A connection to earth. For many electronic circuits this is the 0V


Earth
(zero volts) of the power supply, but for mains electricity and some
(Ground)
radio circuits it really means the earth. It is also known as ground.

Chassis Ground Connected to the chassis of the circuit

Digital, Ground Serves as a zero reference or ground to digital circuits

Motor Electric motor

Electrical voltage is generated by mechanical rotation of the


Generator
generator

Current Source Generates constant current.

Adama Science & Technology University Page 40


Electrical Installation Handout

AC Voltage
AC voltage source
source

Voltage Source Generates constant voltage

Table 2.3. Symbols of Power supplies

2. Output Devices: Lamps, Heater, Motor, etc.

Component Circuit Symbol Function of Component

A transducer which converts electrical energy to light.


Lamp (lighting)
This symbol is used for a lamp providing illumination

A transducer which converts electrical energy to light.


Lamp (indicator)
This symbol is used for a lamp which is an indicator.

Heater A transducer which converts electrical energy to heat.

A transducer which converts electrical energy to


Motor
kinetic energy (motion).

A transducer which converts electrical energy to


Bell
sound.

A transducer which converts electrical energy to


Buzzer
sound.

Inductor A coil of wire which creates a magnetic field when


(Coil, Solenoid) current passes through it.

Table 2.4 Symbols of output devices, lamps and heater

Adama Science & Technology University Page 41


Electrical Installation Handout

3. Switches

Component Circuit Symbol Function of Component

Push Switch A push switch allows current to flow only when the
(push-to-make) button is pressed. Used to operate a doorbell.

Push-to-Break This type of push switch is normally closed (on); it


Switch is open (off) only when the button is pressed.

SPST = Single Pole, Single Throw.


On-Off Switch
An on-off switch allows current to flow only when it
(SPST)
is in the closed (on) position.

SPDT = Single Pole, Double Throw.


A 2-way changeover switch directs the flow of
2-way Switch
current to one of two routes according to its
(SPDT)
position. Some SPDT switches have a central off
position and are described as 'on-off-on'.

DPST = Double Pole, Single Throw.


Dual On-Off Switch A dual on-off switch which is often used to switch
(DPST) mains electricity because it can isolate both the live
and neutral connections.

DPDT = Double Pole, Double Throw.


Reversing Switch This switch can be wired up as a reversing switch
(DPDT) for a motor. Some DPDT switches have a central off
position.

An electrically operated switch


Relay NO = Normally Open, COM = Common,
NC = Normally Closed.

Jumper Close connection by jumper insertion on pins.

Adama Science & Technology University Page 42


Electrical Installation Handout

Solder Bridge Solder to close connection

SPST Toggle
Disconnects current when open
Switch

SPDT Toggle
Selects between two connections
Switch

Table 2.5 symbols of different types of switches

4. Resistors

Component Circuit Symbol Function of Component

A resistor restricts the flow of current,


Resistor Some publications still use the old resistor symbol:

Variable Resistor This type of variable resistor with 2 contacts


(Rheostat) (A rheostat) is usually used to control current.

Variable Resistor This type of variable resistor with 3 contacts (a


(Potentiometer) potentiometer) is usually used to control voltage.

Variable Resistor This type of variable resistor (a preset) is operated


(Preset) with a small screwdriver or similar tool.

Table 2.6 Symbols of Resistors

5. Capacitors

Component Circuit Symbol Function of Component

A capacitor stores electric charge. A capacitor is


Capacitor
used with a resistor in a timing circuit. AC signals.

A capacitor stores electric charge. This type must be


Capacitor, polarized
connected the correct way round.

Adama Science & Technology University Page 43


Electrical Installation Handout

Variable Capacitor A variable capacitor is used in a radio tuner.

This type of variable capacitor (a trimmer) is


Trimmer Capacitor
operated with a small screwdriver or similar tool.

Table 2.7: Symbols of Capacitors

6. Diodes

Component Circuit Symbol Function of Component

A device which only allows current to flow in one


Diode
direction.

LED
A transducer which converts electrical energy to light.
Light Emitting Diode

A special diode which is used to maintain a fixed


Zener Diode
voltage across its terminals.

Photodiode A light-sensitive diode.

Table 2.8: Symbols of Diodes

7. Audio and Radio Devices

Component Circuit Symbol Function of Component

Microphone A transducer which converts sound to electrical energy.

Earphone A transducer which converts electrical energy to sound.

Loudspeaker A transducer which converts electrical energy to sound.

Adama Science & Technology University Page 44


Electrical Installation Handout

Piezo Transducer A transducer which converts electrical energy to sound.

An amplifier circuit with one input. Really it is a block


Amplifier
diagram symbol because it represents a circuit rather than just
(general symbol)
one component.

Aerial A device which is designed to receive or transmit radio


(Antenna) OR signals.

Dipole Antenna Two wires simple antenna

Table 2.9: Symbols of Audio and Radio devices

8. Meters

Component Circuit Symbol Function of Component

A voltmeter is used to measure voltage.


Voltmeter The proper name for voltage is 'potential difference', but
most people prefer to say voltage!

Ammeter An ammeter is used to measure current.

A galvanometer is a very sensitive meter which is used


Galvanometer
to measure tiny currents, usually 1mA or less.

An ohmmeter is used to measure resistance. Most


Ohmmeter
multimeters have an ohmmeter setting.

An oscilloscope is used to display the shape of electrical


Oscilloscope signals and it can be used to measure their voltage and
time period.

Table 2.10: Symbols of Meters

Adama Science & Technology University Page 45


Electrical Installation Handout

9. Sensors (input devices)

Component Circuit Symbol Function of Component

A transducer which converts brightness (light) to


LDR resistance (an electrical property).
LDR = Light Dependent Resistor

A transducer which converts temperature (heat) to


Thermistor
resistance (an electrical property).

Table 1.11: Symbols of Sensors

2.3. Design of Residential, Commercial and industrial consumer’s Installation


► Terminology and definitions:
Ampacity: current carrying capacity of electric conductors expressed in amperes.
Appliance: utilization equipment.
Branch circuit: the circuit conductor between the final over current device protecting the
circuit and the outlet(s).
Demand factor: the ratio of the maximum demand of a system, or part of a system, to the total
connected load of a system or the part of the system under consideration.
Feeder: all circuit conductors between the service equipment, or the generator switchboard of
an isolated plant, and the final branch circuit over current device.
Ground: a conductor connection, whether intentional or accidental, between an electric circuit
or equipment and the earth, or to some conducting body that serves in place of the earth.
Lighting outlet: an outlet intended for direct connection of a lamp holder, a light fixture, or a
pendant cord terminating in a lamp holder.
Outlet: a point on the wiring system at which current is taken to the utilization equipment
Receptacle: a contact device installed at the outlet for the connection of a single attachment
plug.
Service: the conductor and equipment for delivering energy from electric supply system to the
wiring system of the premises served.
Switch board: a large panel, frame or assembly of panels on which are mounted, on the face or
back or both, switches, over current and other protective devices, buses, any usual instruments.

Adama Science & Technology University Page 46


Electrical Installation Handout

► Wiring Design Criteria


Flexibility: every wiring system should incorporate sufficient flexibility of design in branch
circuitry, feeders, and panels to accommodate all portable, patterns, arrangements and locations
of electric loads. The degree of flexibility to be incorporated depends in large measure on the
type of facility. As part of the design for flexibility, provision for expansion must be provided.
It must, however, be emphasized that over design is as bad as under design.
Reliability: the reliability of electrical power within a facility is determined by two factors:
-The utility’s service and the building’s electrical system.
Safety: the designer must be constantly alert to an initial safe electrical installation and such
factors as electrical hazards caused by misuse of equipment or by equipment failure after
installation.
Energy consideration: includes limiting voltage drops, power factor correction, use of
switches for control, etc
Economic cost: includes initial cost and operating cost
Space allocation: concerned with maintenance ease, ventilation, expandability, centrality,
limitation of access, and noise, in addition to the basic item of space adequacy.

► Design procedure
The steps involved in the electrical wiring design of any facility are outlined below.
These may in some instances be performed in different order, or two or more steps may be
combined, but the procedure normally used is that listed below.
a) Determine with the client the usage of all areas, and type and rating of all client furnished
equipments including their specific electric ratings.
b) If the designer could not get the exact electrical rating of all the equipment that are going to
be installed in the building such as plumbing, elevators, kitchen, motors etc, determine their
ratings from other consultants.
c) Make an electrical load estimate based on the above collected data, areas involved,
previously installed similar installation data and any other pertinent data.
Load Estimation: when initiating the wiring design of a building, it is important to be able to
estimate the total building load in order to plan such spaces as transformer rooms, chases, and
closet. This information is also required by the local power company well in advance of the

Adama Science & Technology University Page 47


Electrical Installation Handout

start of construction. Of course, an exact load total can be made after completing the design.
But such estimation can be made from the knowledge of the loads the building uses.
The electrical loads in any facility can be categorized as:
(i) Lighting.
(ii) Miscellaneous power, which includes convenience outlets and small motors.
(iii) Heating, ventilating, and air conditioning.
(iv) Plumbing or sanitary equipment: house water pump, air compressors, and vacuum pumps
etc.
(v) Vertical transportation equipment: elevators, moving stairs, and dumbwaiters.
(vi) Kitchen equipments.
(vii) Special equipments.
d) In cooperation with the local electric utility, decide upon the point of service entrance, type
of service run, service voltage, metering location, and building utilization voltage.
The above considerations and general rules affecting service equipment are listed below:
i. A building may be supplied at one point by either a single set or parallel sets of service
conductors.
ii. All equipment used for service including cable, switches, meters, and so on, shall be
approved for that purpose.
iii. It is recommended that a minimum of 100-amp, 3-wire, 220/380V service be provided for
all individual residences.
iv. No service switch smaller than 60 amp or circuit breaker frame smaller than 50 amp shall be
used.
v. In multiple occupancy buildings tenants must have access to their own disconnect means.
vi. All building equipment shall be connected on the load side of the service equipment except
that service fuses, metering, fire alarm, and signal equipment and equipment serving
emergency systems may be connected ahead of the main disconnect.
In computing the size of the service equipment bus, a total is taken of the various feeder loads.
Although application of a Diversity Factor to this total is permissible, good practice dictates the
use of a unity Diversity Factor in order to provide a measure of spare capacity in the service
equipment.

Adama Science & Technology University Page 48


Electrical Installation Handout

(e) Determine the location and estimate the size of all required electric equipment spaces
including switchboard rooms, emergency equipment spaces, electric closets, and so forth.
NOTE: - Panel boards are normally located in closets but may be located in corridor walls or
elsewhere. This work is necessary at this point to enable the architect to reserve these spaces
for the electrical equipment. Once the design is accomplished in detail, the estimated space
requirements can be checked and necessary adjustments made.
(f) Design the lighting for the facility. This step is complex and involves a continued interaction
between the architect and the lighting designer.
(g) On the same plan, or on a separate plan, as decided, locate all electrical apparatus including
receptacles, switches, motors, and other power consuming apparatus. Under floor duct and
ceiling track systems would be shown at this stage. If extensive, a separate plan is made.
(h) On the plan, locate signal apparatus such as phone outlets, speakers, microphones, TV
outlets, fire and smoke detectors, and so on.
(i) Make drawing showing all lightings, devices, and power equipments circuit connection to
the appropriate panel board.
(j) Prepare the panel schedule (table). This table shows the load distribution over the three
phases and the type of load which is connected on each circuit. At this step, include the
separate circuitry for emergency equipments and for spare circuit.
(k) From the panel schedule (table) compute panel loads, and make connection rearrangement
so that you will be able to an optimum power balance over the three phases R, S and T.
(l) Prepare the riser diagram. This includes design of distribution panels, switchboards, and
service equipment.
(m) Compute feeder sizes and all protective equipment ratings.
(n) Cheek the preceding work.

► Branch Circuit Design


● Guidelines for Residential
(a) The NEC requires for residences sufficient circuitry to supply a load of 3W/sq ft in the
building, excluding unfinished spaces such as porches, garages, and basements.
(b) The NEC requires a minimum of two 20-amp appliance branch circuits to feed all the small
appliance outlets in the kitchen, pantry, dining room, family room etc.

Adama Science & Technology University Page 49


Electrical Installation Handout

Furthermore, all kitchen outlets must be fed from at least two of these circuits (Avoid placing
all the lighting in a building on a single circuit). Also receptacles should be circuited with
preferably two, but not more than four on a 20-amp circuit.
(c) The NEC requires that at least one 20-amp circuit supply to be set for laundry outlets.
This requirement satisfies good practice. If electric clothes dryer is anticipated an individual
branch circuit should be supplied to serve this load, via a heavy-duty receptacle.
(d) Do not combine receptacles and switches into a single outlet except where convenience of
use dictates high mounting of receptacles.
(e) Circuit the lighting and receptacles so that each room has parts of at least two circuits.
This includes basements and garages.
(f) Supply at least one receptacle in the bathroom and one outside the house
(g) Provide switch control for closet lights.
(o) In bedrooms supply two duplex outlets at each side of the bed location to accommodate
electric blanket, clocks, radios, lamps, and other such appliances.
(i) Since receptacles are counted as part of general lighting and no additional load is included
for them, no limit is placed on the number of receptacle outlets that may be wired to a circuit.
But for good practice they should be limited to 6 on a 15-amp circuit and 8 on a 20-amp circuit.
(l) Kitchens should have a duplex appliance outlet every 36 in. of counter space, but no less
than two in addition to the normal wall outlets.
(m) A disconnecting means, readily accessible, must be provided for electric ranges, cook tops,
and ovens. It is better practice to utilize a small kitchen panel recessed into a corner wall to
control the large kitchen appliances and to provide completely safe, accessible disconnecting
means. Such an arrangement can also be cheaper if the length of run between the main panel
and the kitchen is appreciable.

● Guidelines for Non-residential


(a) Schools. Since schools comprise an assembly of varied use spaces, including lecture hall,
laboratory, shop, assembly, office, gymnasium, plus special areas such as swimming pools,
photographic labs, and so on, it is not possible to generalize on branch circuit design
considerations except for the following:
i. To accommodate the opaque and film projectors frequently used in the classroom,

Adama Science & Technology University Page 50


Electrical Installation Handout

20-amp outlets wired two receptacles on a circuit are placed at the front and back of each such
room. A similar receptacle, wired 6 or 8 to a circuit is placed on each remaining wall.
ii. Light switching should provide:
1) High-low levels for energy conservation and to permit low-level lighting for film viewing.
With fluorescent lighting this can be accomplished by alternate ballast wiring and switching,
thus avoiding the high cost of dimming equipment.
2) Separate switching of the lights on the window side of the room, which is often lighted
sufficiently by daylight.
iii) Provide appropriate outlets for all special equipment in labs, shops, cooking rooms, and the
like.
iv) Use heavy-duty devices and key operated switches for public area lighting (corridors, etc.),
plastic instead of glass in fixtures, and vandal-proof equipment wherever possible. All panels
must be locked and should be in locked closets.
v) The NEC requires sufficient branch circuitry to provide a minimum of 3 W/sq ft for general
lighting in schools. Refer to the NEC Article No. 220. Unlike residential occupancy this figure
does not include receptacles. Receptacles are calculated separately at 180 W each for ordinary
convenience outlets.
vi) Keep lighting and receptacles completely separate when circuiting.
(b) Office Space
i. In small office spaces (less than 400 sq ft) provide either one outlet for every 40 sq ft, or one
outlet for every 10 linear ft of wall space, whichever is greater. In larger office spaces, provide
one outlet every 100 to 125 sq ft beyond the initial 400 sq ft (10 outlets). These should
comprise wall outlets spaced as above plus floor outlets sufficient to make up the required total.
In view of the increasingly heavy loads of office machines, these receptacles should be
circuited at no more than 6 to a 20-amp branch circuit, and less if the equipment to be fed so
dictates.
ii. Corridors should have a 20-amp, 220-V outlet every 50 ft, to supply cleaning and waxing
machines.
iii. As with all non-residential buildings, convenience receptacles are figured at 180W each.

Adama Science & Technology University Page 51


Electrical Installation Handout

(c) Stores. In stores, good practice requires at least one convenience outlet receptacle for every
300 sq ft in addition to outlets required for loads such as lamps, show windows, and
demonstration appliances.

► Load Tabulation
While circuiting the loads, a panel schedule is drawn up which lists:
The circuit numbers
Load description (the type of the load)
Wattage (actually in volt-amperes)
The current ratings
Number of poles of the circuit-protective device feeding each circuit and the like.
Spare circuits are included to the extent that the designer considers them necessary and
consonant with economy, but normally no less than 20% of the number of active circuits.
Finally, spaces are left for future circuit breakers, in approximately the same quantity as the
number of spare circuits, but always to round off the total number of circuits. A typical panel
schedule is shown on the next page as an example.
In calculating panel loads, the following rules apply:
(a) Each specific appliance, device, lighting fixture, or other load is taken at its nameplate
rating, except certain kitchen and laundry appliances for which the NEC allows a demand
factor. (See NEC Article 220.)
(b) Each convenience outlet, in other than residential spaces, is counted as1.5 amp (180 W).
(c) Spare circuits are figured at approximately the same load as the average active circuits.
(d) Free spaces are not added into the load.
(e) Loads for special areas and devices such as show window lighting, heavy-duty lamp
holders, and multi outlet assemblies, are taken at the figures given in NEC Article 220.

Adama Science & Technology University Page 52


Electrical Installation Handout

Schedule for lighting panel


Note: 1) In calculating total panel load, no demand factors may be applied except specifically
stated in the NEC. This is because feeders are calculated for maximum load to be carried, i.e.
100% demand factor is used.
2) The phase loads have to be approximately equally distributed over the three phases (if a
three-phase supply is utilized in an installation). It is the responsibility of the designer (or
contractor) to circuit the loads so that the phases are as closely balanced in load as possible. If

Adama Science & Technology University Page 53


Electrical Installation Handout

this is not done, one phase will carry considerably more current than the others. Since the panel
feeder must be sized for the maximum phase current, this may lead to an over sized feeder and
therefore a waste of money.
Having tabulated and balanced the loads and totaled them by phase, the maximum current is
calculated. A portion of the spare capacity available in branch circuit is added to the above
total, as the basis for the calculation of the feeder load.

► Feeder Capacity
The electric line (cable) that is running from the main distribution line to each sub distribution
board is known as Feeder. To achieve economy, the panel feeder must accommodate the initial
load plus some portion of the future load. One or more of the following procedures provides
spare capacity in feeders:
(a) Provide feeder for initial plus spare, with properly sized conduit. This method is generally
most economical.
(b) Provide feeder for initial plus spare, with conduit oversized by one size. Some additional
cost is entailed here. This is only used where large load expansion is anticipated.
(c) Provide for initial load plus spare, with an empty conduit for future. This method is
expensive because of high conduit cost, and it is infrequently advisable.

EXAMPLE Assume a single floor of an office building 100 ft X 200 ft. Assume also 15% of
the area is corridor and storage. Calculate the required number of panels, circuits, and feeder
size.
Solution
Office space = 85% of 20,000 sq ft = 17,000 sq ft
Corridor and storage=15% of 20,000 sq ft=3000 sq ft
With respect to minimum loads, NEC specifies that the power supply can be increased by 25%
if loads are continuous (3 or more hours). This requirement allows for breakers to heat up in
panels while carrying continuous load, and is waived for circuit breaker which are ambient
compensated, that is, are rated to carry 100% load. Since we have established 80% of the
breaker rating as maximum load, we have already accounted for this factor in circuitry, but
must keep it in mind in feeder calculation.

Adama Science & Technology University Page 54


Electrical Installation Handout

Office load
17,000 sq ft @ 5 w/sq ft = 85kw
Storage
3000 sq ft @ 0.5 w/sq ft = 1.5kw
TOTAL LOAD = 86.5kw
Minimum feeder capacity 1.25 X 86.5 = 108kw. The 25% additional capacity is for continuous
load. Since this building is of good grade office construction, let us anticipate 40 to 80%
expansion, and utilize an initial branch circuit loading of 1300 W per ckt, Assuming that each
lightening branch circuit is 1300 W rated.
86.5 *1000
Number of branch circuit for lightening will be = = 66.54 ~ 67 ckt.
1300
Because of the size of the building, three panels are required to keep branch circuits below 100
ft in length. Also we need to have additional circuits that are provided for receptacles and
spares.
Receptacles:
For the first 400 sq ft 10 receptacles, and for the next 16,600ft2, taking 1 receptacle per
110sqft, there will be 151 receptacles. This will give a total of 161 receptacles in the building.
If each branch circuit carries 20A, supplying for 6 receptacles,
161
No. of receptacle circuits will be = = 27 ckts
6
The total no of circuits for lighting plus receptacles is 67 + 27 = 94 ckts
Spares is = 20% of total circuits
94*20% = 94*0.2 = 18.8 ~ 19
Total 0f 113 ckts.
Each panel would then have 113/3 or 38 circuits plus 4 free spaces, for a maximum of 42 poles.
Thus, with initially three panel locations we proceed to circuit the lighting and receptacles
according to the actual tenant requirements.
NOTE. In calculating the panel load for feeder sizing, the actual load as determined by adding
the lighting and other loads on the panel. This load is compared to the load by square foot
calculation. And the larger figure is used in determining the required panel feeder size.

Adama Science & Technology University Page 55


Electrical Installation Handout

Thus in the above case, the actual load would be compared to 108 kW and the larger used. If
the actual number of circuits is less than 67, then 67 ckt must be provided; but if greater, the
actual number required must be used. In either case, 20% spare should be used.
Assuming even distribution of load, and actual load greater than the minimum 67 ckt, panel
load would be 38 ckts each rated @ 1300 W = 49.5 KW, and if 25% future expansion is
anticipated that is 12.5 KW (note: it is for this power that the four free spaces are left).
So feeder load would become 62 KW
The feeder current is calculated in terms of the panel 3-phase kVA thus:
Kilo Volt
I Or
Power Factor * Mains Voltage * Efficiency
Kilo Watt
I
3 * Mains Voltage * Efficiency
If mains voltage is 380, PF 0.8, 100% efficiency
62Kw
I  94.2 Amp
3 * 380 * 1
Thus, the above feeder current is 94.2 amp.
► Riser Diagrams
When all devices are circuited and panels are located and scheduled, we are ready to prepare a
riser diagram. A typical diagram, shown in figure below, represents a block version of a single-
line diagram, as the name implies, vertical relationships are shown. All panels, feeders,
switches, switchboards, and major components are shown up to, but not including, branch
circuiting. This diagram is an electrical version of a vertical section taken through the building.

Adama Science & Technology University Page 56


Electrical Installation Handout

Fig.2.1. Typical power riser diagram.


Ordinarily the main switchboard would be shown as a large rectangle with the feeder
emanating from it, and a switch board schedule would detail the contents. Here, because of the
unusual bus arrangement, we have shown the main switch board as it would appear on a single-
line diagram.
The main switchboard shown in the above figure constitutes a combination of service
equipment and feeder switchboard. The service equipment portion of the board comprises the
metering and the 4 main switches feeding risers, motor control center (MCC), roof, machine
room, and elevators
*NEC: - National Electrification Code.
*EBCS: - Ethiopian Building Code Standard.

Adama Science & Technology University Page 57


Electrical Installation Handout

► Choosing Cable Size


● Cable Size Design procedure
The correct choice of cable size for any installation is dependent upon fundamental aspects of
(a) Environmental conditions and characteristics of protection,
(b) Current-carrying capacity of the cable and
(c) Voltage drops of the cable.
When current flows through a conductor, the resistance offered by the conductor produces heat.
The increase in heat is proportional to the cable resistance, which in turn depends upon the
cross-sectional area of the cable. Since overheating damages the insulation, the conductor size
must be of adequate size to prevent this from occurring.
The requirements of IEE Regulations make it clear that circuits must be designed and the
design data made readily available. How then can we begin to design? Clearly, plunging into
calculations of cable size is of little value unless the type of cable and its method of installation
is known. This in turn will depend on the installation’s environment. At the same time, we
would need to know whether the supply was single or three phases, the type of earthing
arrangements, and so on. Here then is our starring point.
Having ascertained all the necessary details, we can decide on an installation method, the type
of cable, and how we will protect against electric shock and over currents. We would now be
ready to begin the calculation part of the design procedure.
Basically, there are eight stages in such a procedure. These are the same whatever the type of
installation, be it a lightening circuit, cooker circuit or a sub main cable feeding a distribution
board in a factory. Here then are the eight basic steps in a simplified form:
1. Determine the design current Ib.
2. Select the rating of the protection In
3. Select the relevant correction factors (CFs).
4. Divide In by the relevant CFs to give cable current-carrying capacity
5. Choose a cable size to suit Iz
6. Check the voltage drop
7. Cheek for shock risk constraints
8. Cheek for thermal constraints.
Let us now examine each stage in detail.

Adama Science & Technology University Page 58


Electrical Installation Handout

Design current
In many instances the design current Ib is quoted by the manufacturer, but there are times when
it has been calculated. In this case there are two formulae involved, one for single phase and
one for three phase:
Single phase:

Three phase:
Ib=P/ (√3 V)
If an item of equipment has a power factor and/or has efficiency (eff) will have been taken into
account. Hence: Single phase:
Ib = (Px1000)/ (V*PF*eff)
Three phase:
Ib = (Px1000)/ (√3*VL*PF*eff)
Nominal setting of protection
Having determined Ib we must now select the nominal setting of the protection In such that
In>Ib. this value may be taken from IEE regulations.
Correction factors
When a cable carries its full load current, it can become warm. This is not problem unless its
temperature rises further due to other influences, in which case the insulation could be damaged
by over heating. These other influences are:
High ambient temperature
Cable grouped together closely
Uncleared over currents and
Contact with thermal insulation.
For each of these conditions there is a correction factor (CF) which will respectively called Ca,
Cg, Cf and Ci, & w/c derates cable current carrying capacity or conversely increases cable size.
Ambient temperature Ca
The cable rating in the IEE regulations are on an ambient temperature of 300C, and hence it is
only above this temperature that an adverse correction improvement is needed.
Grouping Cg

Adama Science & Technology University Page 59


Electrical Installation Handout

When cables are grouped together they impart heat to each other. Therefore the more cables
there are the more heat they will generate, thus increasing the temperature of each cable.
IEE regulation also gives factors for such groupings of the same cable sizes.
Protection by BS 3036 fuse Cf
Because of the high fusing factor of BS 3036 fuses, the rating of the fuse In, should be less than
or equal to 0.725 Iz Hence 0.725 is the correction factor to be used when BS 3036 fuses are
used.
Thermal Insulation Ci
With the modern trend, towards energy saving and the installation of thermal insulation, there
may be a need to derate cables to account for heat retention. IEE Regulation gives these factors
for situations when thermal insulation touches one side of a cable. However, if a cable is totally
surrounded by thermal insulation for more than 0.5 m, a factor of 0.5 must be applied to the
tabulated clipped direct ratings. For less than 0.5 m, derating factors Table __ should be
applied. Refer to the table on pages __.
Application of correction factors
Some or all of the onerous conditions just outlined may affect a cable along its whole length or
parts of it, but not all may affect it at the same time. If all conditions are to appear at the same
time consider all correction factors, otherwise take the worst.
Having chosen the relevant correction factors, we now apply them to the nominal rating of the
protection. In as divisors in order to calculate the current carrying capacity Iz of the cable.
Current carrying capacity
The required formula for current carrying capacity Iz is
Iz= In/ (relevant CFs)
Choice of cable size
Having established the current carrying capacity Iz of the cable to be used, it now remains to
choose a cable to suit that value. The IEE regulation also lists all the cable sizes, current
carrying capacity and voltage drops of varies types of cables.(These data is given from page _to
page __ ).
Voltage drop
The resistance of a conductor increases as the length increases and/or the cross-sectional area
decreases. Associated with an increased resistance is a drop in voltage, which means that a load

Adama Science & Technology University Page 60


Electrical Installation Handout

at the end of a long thin cable will not have the full supply voltage available. The IEE
regulation requires that the voltage drop Vd should not be so excessive that equipment does not
function safely. They further indicate that a drop of no more than 4% of the nominal voltage at
the origin of the circuit will satisfy. The voltage drop will be calculated using a formula
(adopted by IEE regulation):
Vd = mV * Ib * L where mV- voltage drop in mV obtained from IEE table
L- Total length of the cable in consideration.
● Fundamental 3-phase Voltage-drop Calculations
These are all based on the basic formula
R =ρ l/A where ρ (rho) stands for resistivity.
ρ = 1.72x10-8 – for copper conductor
ρ = 2.83x10-8 – for Aluminum conductor
If resistance of a conductor at any temperature different from room temperature is required it
can be calculated using
RT= RO (1+ αΔT). Where RT- resistance at the required temperature
RO =ρ l/A resistance at room temperature
α-Expansion coefficient= 0.00393 - for copper
= 0.0039 - for Aluminum
ΔT- Change in temperature
Resistivity is defined as the resistance between two opposite faces of a unit cube of the
conductor material. Many voltage-drop problems involve the determination of resistance by
this means and then multiplying by the current to obtain the IR drop. The weakness of this
method, as against that adopted by use of the I.E.E. Tables, is that the Tables are much more
realistic since they take into account the actual type of cable and conditions of service.
● Diversity Factor
The diversity factor has an important place in the design of an installation and its final costing.
IEE regulation 311-01 deals with this subject. Diversity factor is a factor which is applied to
sub main and main cables and their associated gears to reduce:
a) The cross sectional area if the cable conductor, and
b) The capacity of the switch gears.

Adama Science & Technology University Page 61


Electrical Installation Handout

The factor is based on the assumption that the whole of the connected load will not be turned
on at the same time. For example, the total lighting load in a dwelling house is rarely switched
on at a time. Thus, it can be taken that if the total lighting load is 1000W during the life of the
installation, only 66% of the load (660W) will be switched on at any one time. The factor in
this instance is 0.66. A factor for diversity shall not be allowed for calculating the size of circuit
conductor and switchgears of final sub circuits, other than specified circuits such as cooker
circuits. It is noted that the provision of an allowance for diversity is a matter of calling for a
special knowledge and experience. Indeed, the application of the diversity should be decided by
the engineer responsible for designing each particular installation. The amount by which they
are increased or decreased for each installation is a matter for the installation engineer to
decide.
There are ten types of final circuit fed from wiring to which diversity applies:
Lighting
Heating
Cooking appliances which are permanently connected
Motors (other than lifting motors)
instantaneous-type water heater
thermostatically controlled water heater
floor-warming installation
thermal-storage space-heating installation
13A fused socket outlets and appliance fed there from and
other socket outlets such as 15A sockets.
The general groups of installation premises are also recognized:
1) Individual domestic installation, including individual flats of a block.
2) Hotels, boarding house, lodging houses etc.
3) Shops, stores, offices and business premises
In the case of lighting for each type of installation, it will be noticed that the more the total
lighting load is likely to switched on over definite periods, the smaller is the allowance made
for diversity. In a domestic installation, it is estimated that some two- thirds (0.66) of the
lighting load will be on at any one time. In a hotel, the figure is 75% (0.75), and in a shop,
where virtually all the lights are on for most of the time when the shop is open, the figure is

Adama Science & Technology University Page 62


Electrical Installation Handout

90% (0.90). It should be noted that no diversity is allowable in the relevant wiring supplying
certain types of load.
Example 1
From EBCS-10. Table B.1, select cables of suitable current-carrying capacity for the following
loads and conditions (p.v.c. cables to BS 6004 into screwed conduit).
(a) 240 V single-phase sub-mains of lighting load totaling 10.5 kW.
Length of run 10 m. Average ambient temperature 25'C, diversity 66%
(b) 400 V balanced 3-phase power circuit. Load 18.65 kW, efficiency, 80%, power factor 0.69.
Average temperature 30'C. Length of runs 100 m.
Solution of (a)
Power 10.5*1000
Current taken by load, I    43.75 A
Voltage 240
66
43.75 A *  28.88 A
100
Allowing for diversity, maximum current through cables
If BS 88 32-A circuit breaker is chosen for protection, 32 A rated circuit breaker can be
selected from table 9.1.
→ In = 32 Amp
The correction factor for ambient temperature from Table A.4 for250C is 1.06.
Therefore the required cable rating:


From Table B.1, choose a 4 mm2 conductor which carries 32A.
Testing for Voltage drop = (mV/Am) * I * l
→ From table B.2 voltage drop for 4mm2 conductor size = 11mv/Am
→ Voltage drop on cable = 11 mv/Am * 28.8 A * 10 m = 3.168 V
→ Maximum allowable voltage drop = 2.5% of 240 V = 6V.
Since the actual voltage drop is less than from the allowable maximum voltage drop, selected
size is 4 mm2
If BS 3036 fuse is chosen for protection, this fuse type requires a correction factor of 0.725.
→ In = 32 Amp

Adama Science & Technology University Page 63


Electrical Installation Handout

Therefore the load current will be :


→ Iz = In/CF CF- Correction Factors.
Ca= 1.06, Cf = 0.725
Required cable rating

From Table B.1, a 6mm2 conductor carries 41 A. And a 10mm2 conductor carries 57 A.
Take 10mm2 diameter conductor.
Testing for Voltage drop = (mV/Am) * I * l
→ From table B.2 voltage drop for 6mm2 conductor size = 7.3mv/Am
→ Voltage drop on cable = 4.4 mv/Am * 28.8 A * 10 m = 1.27 V
→ Maximum allowable voltage drop = 2.5% of 240 V = 6V.
Since the actual voltage drop is less than from the allowable maximum voltage drop, selected
size is 10 mm2.
Comment: you can easily observe that the conductor size deference in using Circuit breaker and
fuses.
Solution of (b)
Output KW *1000 80 18.65*1000
Efficiency=     48.77 A
Input 3 *VI cos  100 3 * 400* I *0.69
From table 9.1, 50 A circuit-breaker of type BS 3871 can used for protection.
→ In = 50 Amp
Load current will be :
→ Iz = In/CF CF- Correction Factors.
CF = 1 because Ca = 1.
→ Iz = 50 A
Choose 16 mm2 cable which is capable of carrying 52 A.
Testing for Voltage drop:
Maximum voltage drop = 2.5% of 400 V = 10V.
Voltage drop on the cable = (mV/Am) * I * l = 2.3 * 48.77 * 100 = 11.22 V this is beyond the
allowable voltage drop. So, choose the next cable size, which is 25mm2.
Voltage drop for 25 mm2 = 1.7 * 43.77 * 100 = 8.29 V

Adama Science & Technology University Page 64


Electrical Installation Handout

Therefore selected size is 25 mm2.


Comment. This is one of the situations where the voltage drop becomes the main determining
factor of the conductor size.
From table 9.1, 50 A BS 3036 fuse can used for protection.
→ In = 50 A
→ Correction factor for the fuse is Cf = 0.725
→ Load current Iz = In / CF = In / Cf
→ Iz = 50 A / 0.725 = 68.966 A
From table B.3 select 25mm2 cable which carries 97 A
Testing for Voltage drop:
Voltage drop on the cable = (mV/Am) * I * l = 2.3 * 48.77 * 100= 13.17 V this is beyond the
allowable voltage drop. So, choose the next cable size, which is 25mm2.
Voltage drop for 25 mm2 = 1.7 x 48.77 x 100 = 8.29 V
Therefore selected size is 25 mm2.
Example 2
A 30 m run of twin and earth p.v.c. non-armored four touching copper cables are situated in an
ambient temperature of 350C. Determine the minimum size of cable to supply a 220-V 10-kW
load. Protection given by:
(a) Miniature circuit-breaker (m.c.b.)
(b) Rewirable fuse.
Solution of (a)

From table A.1,Correction factor for cables group together is 0.75


→ Cg = 0.75
Required cable current rating Iz = 50 = 70.9 A
0.94 x 0.75

Adama Science & Technology University Page 65


Electrical Installation Handout

→ Iz = 70.9 A
From Table B.3 (for multi core cable) 16mm2 cable carries 69A.
Testing for Voltage drop:
Maximum voltage drop = 2.5% of 220 V = 5.5V
Voltage drop on the cable = (mV/Am) * I * l = (2.8 mV/A m) * 41.67 A * 30m = 3.50 V this is
with in the allowable voltage drop.
So, choose cable size of 16mm2.
Solution of (b)
Ib = 41.67 A.
Assume that a rewirable fuse type that requires a correction factor of 0.725 is
used. So Cf = 0.725
→ In = 50 A.
Required cable rating

From Table B.3 (for multi core cable) 35 mm2 cable carries 111 Amp.
Testing for Voltage drop:
Voltage drop on the cable = (mV/Am) * I * l = ( mV/A m) * 41.67 A * 30m = V < 5.5V
So, choose cable size of 35mm2.
Comment. The example exhibits once again the considerable economic savings which can be
gained by fitting an m.c.b. or correct cartridge fuse in place of the rewirable type.
Example 3
A load of 300 kW at 0.78 power-factor is to be supplied at 415 V, 3-phase, through a 3-core
copper cable 260 m long. The cross-sectional area of each cable core is 400 mm2. Calculate
the voltage drop in the cable. Ignore voltage drop due to reactance. (Resistivity of copper may
be taken as 0.017 μΩ-m).
Three-phase power, p= 3 VICOS 
P 300W *1000
By transposition I    535.2 A
3 *VI cos  3 * 415*0.78

0.017m * 260m *106


Resistance per core, R =ρ l/A=  0.01105m
106 * 400m 2

Adama Science & Technology University Page 66


Electrical Installation Handout

Therefore Voltage drop in the cable= 3 *I*R= *535.2*0.01105=10.24V


Comments. The important point to note is the voltage drop in a 3-core cable, when carrying the
current in to a balanced 3-phase load, is given by √3*I* R. The cable conductors are presumed
to act as a pure resistance without any reactive effects.
Problems
An apartment having 15 individual rooms each 3.5mX2.5m (see figure below) is to be installed
with the following loads: Ventilator (500W), Fridge (1kW), Stove (2kW), six 60W lamps, and
five socket outlets.
a) Locate the approximate area of location of each lamps and sockets.
b) Calculate the sub-feeder cable size for this room if the average ambient temperature of the
local area is taken as 35oC and five groups of circuits are running together in a conduit with it.
The length of run is 15m and protection is by MCB.
c) Choose the rating of the MCB and the branch circuits breakers.

Fig.2.2 Floor Plan for problem no. 6


Data for Electrical Installation

Adama Science & Technology University Page 67


Electrical Installation Handout

Adama Science & Technology University Page 68


Electrical Installation Handout

Adama Science & Technology University Page 69


Electrical Installation Handout

Adama Science & Technology University Page 70


Electrical Installation Handout

Adama Science & Technology University Page 71


Electrical Installation Handout

2.4. Grounding/Earthing System


Earthing means connection of the neutral point of a supply system or the non-current carrying
parts of electrical apparatus such as metallic frame work, metallic covering of cables, metal
covers of switches, metal casing of portable apparatus, frame of every generator and motor etc.
to the general mass of earth in such a manner that at all times an immediate discharge of
electrical energy takes place without danger.

Earth Electrodes Resistance


If we were to place an electrode in the earth and then measure the resistance between the
electrode and points at increasing larger distance from it, we would notice that the resistance
increased with distance until a point was reached (usually around 2.5m) beyond which no
increase in resistance was seen.

Adama Science & Technology University Page 72


Electrical Installation Handout

Fig.2.3
The value of this electrode resistance will depend on the length and cross-sectional area of the
electrode and the type of the soil.
Typical Value of Soil Resistivity in Ohms

Earth-fault-loop path
Fig. 2 shows the path taken by an earth-fault current. This system has a direct connection of the
supply transformer to earth and a direct connection of the installation metalwork to earth.

The total sum impedance of the individual parts of the path is known as the loop impedance,
Zs. This is made up of:

Adama Science & Technology University Page 73


Electrical Installation Handout

Ze which is the impedance external to the consumer’s intake terminals and include the
supply transformer secondary winding, the phase conductor and the metallic return path
(general mass of earth) back to the supply transformer earthing arrangement.

The value of Zb depends on the type of supply system.


R1. Which is the resistance of the phase conductor from the supply intake position to the final
circuit load.
R2. Which is the resistance of the circuit protective conductor (CPC).
The total earth-loop impedance is thus:
Zs = Ze + (R1 + R2) Ohms and
If = Vs / ZS
Where If is the fault current and VS is the nominal voltage to earth (usually 220 V).
The loop impedance Ze external to the installation may be measured in existing installations
using a phase-to-earth loop impedance tester. However, when a building is only at the drawing
board stage, we have three methods available to assess the value of Ze:
(I) determine it from details (if available) of the supply transformer, the main distribution cable
and the proposed service cable: or
(II) Measure it from the supply intake position of an adjacent building having service cable of
similar size and length to that proposed; or
(III) Use maximum likely values issued by the supply authority. Having established ZS, the
resistance of the phase conductor (R1) plus the resistance of the CPC (R2), i.e. R1+R2
calculated for the type of conductor used (normally copper or aluminum).
Earth-leakage protection may be afforded by means of fuses or excess-current circuit breakers
provided that the earth fault current available to operate the protective device and to make the
faulty circuit dead exceeds;
(I) 3 times the current rating of any semi-enclosed fuse or cartridge fuse used to protect the
circuit or
(II) 1.5 times the tripping current of any excess current circuit breaker used to protect the
circuit.
Testing of Installation

Adama Science & Technology University Page 74


Electrical Installation Handout

The tests to be performed before a new installation or an addition to an existing installation is


connected to the supply mains are as follows:
1. Insulation Resistance
The insulation resistance between the wiring and earth with all fuses (breakers) and lamps in
and all switches ‘ON’
The insulation resistance between the conductors with all lamps out and all switches ‘ON’
2. Testing of polarity of non-linked single pole switches.
3. Testing of earth continuity path.
4. Testing of earth-electrode resistance.
1. Insulation Resistance
The aim of this test is to know whether the wires or cables used in the wiring are sufficiently
insulated to avoid leakage current. Test is performed by a DC source not less than twice of
working voltage but not exceeding 500 V. A 500 V tester, known as ‘Megger’ is used for this
purpose.
Since installation circuits are wired in parallel, one can see that for a very large
Installations an insulation resistance test at the intake position may show a low value, which
isn’t actually due to bad insulation. In order to overcome this problem, EELPA regulation
(SECTION E-2) permits such installation to be broken down into smaller units of not less than
50 outlets.
• Testing of Insulation Resistance between the Wiring and the Earth.
The resistance offered to leakage from conductors to earth is known as insulation resistance test
between the wiring and earth. Before making an insulation test ensure that:
a) Supply is isolated, i.e. the main switch, breaker or fuse is in OFF position.
b) All protective devices are in place.
c) All the switches are in ON position.
d) All the lamps are in their positions or the holders are short-circuited.
e) Link all the poles of the supply together i.e. line and neutral terminals are shorted on the
installation side.

Adama Science & Technology University Page 75


Electrical Installation Handout

Fig.2.4. Insulation Resistance to Earth


The line terminal of the megger (marked as L) is connected to the point where the conductors
have been shorted at the main switch and the E terminal is connected to the earth. Now the
handle of the tester is turned so that it begins to slip and the reading on the dial gives the
insulation resistance between the wiring and earth.
The insulation resistance to earth measured should not be less than 1 Mega ohm. Very small
leakage current IL=220/1MΩ
•Testing of Insulation Resistance between Conductors
The objective of this test is to ensure that the insulation is sound between the conductors so that
there may not be an appreciable leakage between them.
In this test the circuit diagram remains the same as in Fig.1 except that all the lamps and all
metallic connections between the two wires of the installation are removed from the holders.
With the supply isolated, all protective devices in place, and all single pole switches in ‘ON’
position; the terminals of the megger are connected between poles (i.e. R to S, R to T, S to T,
and each pole in turn to N). The reading should not be less than 1 Mega ohm.

Fig. 2 Between Poles Test.

2 Testing of polarity of Single Pole Switches

Adama Science & Technology University Page 76


Electrical Installation Handout

Section E-2 of EELPA’s regulation states that “A verification of polarity shall be made and it
shall be ensured that all fuses and all single pole control devices are connected in the live
conductor only, that the outer contacts of center-contact bayonet and Edison-type lamp holders
are connected to the neutral or earthed conductor, and that wiring has been correctly connected
to plugs and socket outlets”.
A convenient and quicker method of performing this test is by means of a small neon tube
tester.
1 See EELPA’s regulation SECTION E-2

An alternative method is by means of a test lamp. In this method one end of the test lamp is
connected to earth and the other end is tapped to each contact of the switch in turn. If the test
lamp is in the live wire i.e. gives light, otherwise the installation is wrong (see fig 3)
3 Testing of Earth Continuity Path
For safely all metal pieces or covering such as conduits, metal covers of switches, metal casing
of portable apparatus, frame of every generator and motor, etc, must be solidly connected to
earth otherwise on the damage of insulation, the leakage current will start giving severe shock
to the person touching it. In case of conduit wiring there is a possibility of the conduit joints to
become loose to be separated resulting in high resistance in the earth path.
The test shall be made when the normal supply is disconnected from the final sub-circuit under
test. One end of the earth-continuity conductor shall be connected to a cable of known
resistance. An AC voltage not exceeding 40 V at approximately the frequency of supply shall
then be applied between the other end of the earth conductor and the other end of the cable.
Subject to the requirement for the total earth loop impedance, it is satisfactory if, after
allowance has been made for the return conductor, value not exceeding 0.5 ohm for the ratio
voltage/current is obtained where steel conduit or pipe form part or whole of the earth-

Adama Science & Technology University Page 77


Electrical Installation Handout

continuity conductor, or a value of 1 ohm where the earth-continuity conductor is composed


entirely of copper, copper alloy or aluminum.
2.5. Lightning Arrestors
Surge arresters are devices to protect equipment from surge line voltages. They absorb some of
the surges, but are also capable of stopping the flow of the surge current by absorbing it, and
they maintain their capability of repeating such functions.
These surge arresters break down at voltages higher than the supply voltage, allowing the
higher voltage and accompanying currents to flow to ground, thus protecting the equipment on
the system.
After the surge passes to ground, the arrester heals itself, shutting off flow current from the
supply system.
A case in point: There was a 71⁄2-horsepower irrigation-pump motor out in a field under a large
tree. Because of lightning, motor rewinds were required on an average of once every two years.
Special permission was granted to install surge arresters and surge capacitors to the service.
Approximately 30 years later, there has not been a motor burnout due to lightning.
Number Required
When using surge arresters, they shall be connected to each ungrounded circuit conductor.
Surge arresters are available in single units to connect to only one ungrounded circuit
conductor; here one would be required for each ungrounded conductor. They also are available
with three units in one enclosure, which would thus take care of a three-phase supply. If there
are other supply conductors, such as supplied from a farm service pole, as illustrated in Figure
225-1, one set of surge arresters would be sufficient. But in Figure 225-1 there are a number of
service drops, and so surge arresters should be installed at the load-end of each service drop.
Surge Arrester Selection
(A) On Circuits of Less Than 1000 Volts. On circuits of less than 1000 volts, it is required
that the voltage rating of the surge arresters be equal to or greater than the maximum voltage of
the phase-to-ground voltage available. Thus a service of 480 volts to ground (RMS) would be
0.707 of the maximum voltage to ground; so maximum voltage would be 480 divided by 0.707,
or 679 volts. By the same token, a service of 20 volts to ground (RMS) would be 170 volts
maximum.

Adama Science & Technology University Page 78


Electrical Installation Handout

(B) On Circuits of 1 kV and Over. This requires that the surge arrester have a rating of not
less than 125 percent of the maximum phase-to-ground voltage. Again, don’t confuse RMS
voltage and maximum voltage. Use the examples in (A) above.
Note
See ANSI Standard C62.2for further information. Arresters are usually metal oxide. See the
NEC for this fine-print note.
II. Installation
Location
Surge protection of surge arresters may be located in the system either indoors or outdoors, but
shouldn’t be accessible to unqualified persons. In deciding whether to place surge arresters
indoors or outdoors, take into consideration that some have exploded. Although this is not a
Code requirement, I would suggest that if they are placed indoors, they should be kept away
from combustible items.
Exception
There are some surge arresters that are listed to be located in accessible places
Routing of Surge Arrester Connections
The connections from the supply system to the surge arresters should be as short as possible.
Also, there should be as few bends in the leads and grounding as possible. Lightning takes a
direct path to the ground.
III. Connecting Surge Arresters
Installed at Services of Less Than 1000 Volts
Conductors used to connect surge arrestors can’t be smaller than No. 14 copper or No. 12
aluminum. The conductor that is used to ground the arrestor must be connected to the grounded
service conductor, the grounding electrode conductor, the grounding electrode, or the
equipment-grounding terminal of the service panel.
Installation on the Load Side of Services of Less Than 1000 Volts
This section tells us that line and grounding conductors shouldn’t be smaller than No. 14
copper or No. 12 aluminum. Some judgment must be used here, and, if possible, check with the
authority that has jurisdiction as to the size of conductors to use.

Adama Science & Technology University Page 79


Electrical Installation Handout

Surge arresters may be connected to any two ungrounded conductors, grounded conductors, or
grounding conductors. The grounded conductors and the grounding conductors should be
interconnected only during normal operation of the surge arrester when a surge occurs.
The shortest method of getting the surge to ground is always the best method. Avoid bends as
much as possible.
Circuits of 1 kV and Over—Surge Arrester Conductors
Here we are limited to No. 6 copper or aluminum for conductors connecting the surge arrester
to both the ungrounded conductors and the ground.
Circuits of 1 kV and Over—Interconnection
Where circuits are supplied by 1 kV and over, the grounding conductor from surge arresters
that protect a transformer supplying a secondary distribution system must be interconnected as
follows.
(A) Metallic Interconnection. An interconnection to the secondary neutral may be made if the
direct grounding is made to the surge arrester, provided that both of the following conditions
are met:
(1) If the secondary has the grounded conductor connected elsewhere to a continuous metal
underground water-piping system. If in urban areas there is a minimum of four water pipe
grounding connections in a distance of one mile, the direct ground from the surge arrester may
be eliminated and the secondary neutral used as the grounding for the surge arrester.
(2) In many instances the primary is four-wire wye, with the neutral grounded periodically. In
these cases the secondary neutral is usually interconnected with the primary neutral.
If the primary neutral is grounded in a minimum of four places in each mile, plus the secondary
service ground, the surge arrester ground may be interconnected with the primary and
secondary grounds in addition to the surge arrester grounding electrode.
(B) Through Spark Gap. If the surge arrestor is not connected in accordance with part (A) of
this section, or if it is not grounded as in part (A), but is grounded according to Section 250.83,
a connection may be made through a spark-gap device, but only according to the following
rules:
(1) In ungrounded or ungrounded systems, the spark-gap arrestor must have a breakdown
voltage of more than two times the circuit’s normal operating voltage, but not necessarily more
than 10,000 volts. There must also be at least

Adama Science & Technology University Page 80


Electrical Installation Handout

two grounding electrodes, placed no more than 20 feet (6.1 m) apart.


(2) In multi-grounded neutral primary systems, the spark-gap arrestor must have a breakdown
voltage of no more than 3000 volts, and there must be at least two grounding electrodes, placed
no more than 20 feet (6.01 m) apart.
(C) By Special Permission. The authority that has jurisdiction may grant special permission
for an interconnection of the surge arrester ground and the secondary neutral other than
permitted in (A) and (B) of this section.

Lightning is not attracted to radio antennas unless the antenna is one of the highest points
around. Unfortunately, that's where antennas work best: up high. Because of this problem, it is
necessary to provide some protection against lightning strikes.
Get one thing straight right away: a direct hit on your antenna will destroy the antenna and the
radio equipment connected to it. It might also set fire to your house. No amount of protection
will guarantee that no damage will occur, but you can mitigate the damage by taking certain
steps. Also, a lightning bolt need not strike the antenna to damage radio equipment. A lightning
bolt that strikes the ground nearby, or strikes between two clouds overhead, will produce a high
enough electrical field to put very high voltage spikes into the receiver front-end. Older
vacuum tube equipment was relatively immune to such transient voltages, but modern solid-
state equipment is sensitive.
All antenna installations should have a lightning arrestor either in the feedline or at the base of
the antenna in the case of verticals. Your radio dealer can sell you approved types. The
lightning arrestor should be installed outside of the house, and be well grounded.
Note: In many cases your homeowners insurance may not pay off in the case of lightning
damage if you failed to use an approved lightning arrestor properly installed. Some companies
also require that the installation be inspected by the local government electrical inspector.
If you follow the principles discussed in this paper, you should achieve a good ground, with the
expected improvement in the performance of receivers, transmitters and antennas.

2.5. Installation Design and Design Drawing


A typical electrical drawing consists of solid or dashed lines representing wiring or cables and
symbols for luminaires, receptacles, switches, auxiliary systems, and other electrical devices

Adama Science & Technology University Page 81


Electrical Installation Handout

and their locations on a scaled architectural floor plan of a home or building. The drawings also
include title blocks to identify the project, the designers or engineers, and the owner, and
change blocks to record any changes that have been made since the drawing was first issued.
Drawing for an electrical project serves three distinct functions.
1. Describes the electrical project in sufficient detail to allow electrical contractors to use the
drawings in estimating the cost of materials, labor, and services when preparing a contract
bid.

2 Instructs and guides electricians in performing the required wiring and equipment installation
while also warning them of potential hazards such as existing wiring, gas pipes, or plumbing
systems.

3 Provides the owner with an “as-built” record of the installed electrical wiring and equipment
for the purposes or maintenance or planning future expansion. The owner then becomes
responsible for recording all wiring and equipment changes. In any given set of electrical
drawing there are also specialized drawings such as one-line, elevation or riser, and electrical
equipment installation drawings. There might be no drawing requirements for relatively simple
electrical projects such as updating the amperage capacity of a home or extending branch
wiring into a basement, lattice, or extension. In these situations, all information needed can be
included in a written proposal or other contractual agreement.

For commercial projects or new home construction, formal drawings are required to gain
approvals from building inspectors and the local electric utility. A typical set will include
several 24 x 36 in. architectural floor plans marked with the appropriate electrical graphic
symbols. The set might also include drawings for telephone and multi media structured wiring,
outdoor wiring, or a security system.

By contrast, major large-scale construction projects such as shopping centers, higher rise office
buildings, factories, hospitals, and scientific laboratories might require dozens of 24 x 36 in. (or
larger) sheets. depending on the size and complexity of the project. These might include one-
line drawings and manufacturer-furnished wiring diagrams for installing equipment. For
complex projects, special instructions and installation schedules will also be included.

Adama Science & Technology University Page 82


Electrical Installation Handout

ELECTRICAL PLAN
The electrical information and layouts in construction drawings, just as the mechanical plan,
are generally superimposed on the building plan and the plot plan.
As an EA3, the electrical layout for both light and power is your main concern. You will be
required to draw electrical drawings and layouts from notes, sketches, and specifications
provided by the designing engineer. Although you are not required to design the electrical
wiring system, you must be familiar with the methods, the symbols, and the nomenclature, as
well as the basic functions of the components associated with the electrical systems, its
transmission and distribution, and the circuits hookup. In addition, you must also be familiar
with the codes (both NEC ® and local) and standards and specifications, and be able to apply
that knowledge in
Codes
Code requirements and installation procedures offer protection for the consumer against un-
skilled electrical labor. Among other functions, the NEC ® serves as a basis for limiting the
type and wiring to be used, the circuit size, the outlet spacing, the conduit requirements, and the
like. In addition, local codes are also used when separate electrical sections are applicable to
the locale in which the building will be built. Be certain that you always have a copy of the
latest edition of the NEC ® available for your use.
Similarly, all of the types of electrical devices and fixtures included in the materials list
prepared for electrical plans are to meet certain specifications and minimum requirements. An
independent organization called Underwriters

Adama Science & Technology University Page 83


Electrical Installation Handout

Figure 9-23.-Common types of electrical symbols.


Laboratories (UL) tests various electrical fixtures and devices to determine if they meet
minimum specification and safety requirements as set up by UL. Those fixtures and devices
that are approved may then bear UL labels.
Permit

Adama Science & Technology University Page 84


Electrical Installation Handout

In the SEABEEs, utility drawings (both mechanical and electrical) are thoroughly reviewed
before an excavation (or digging) permit is granted and issued to the project subcontractor.
Such action minimizes the hazards to personnel and underground structures during the
construction process. All of the minor design changes and field adjustments must be noted and
reflected on as-built and working drawings. Therefore, close coordination and cooperation must
develop within and among all of the parties involved in the project to maintain periodic checks
on red-lined prints so that information can be compared and verified as up to date.
ELECTRICAL SYMBOLS
The conventions used on the electrical plan are SYMBOLS that indicate the general layout,
units, related equipment, fixtures and fittings, and routing and interconnection of various
electrical wiring. The most common types of symbols used in electrical drawings are shown in
figure 9-23. To see additional or special symbols, refer to the appendix section of this book
and/or to ANSI Y32.9.
To draw in electrical symbols in an electrical drawing, as in drawing a mechanical plan, it is
best to use templates. For example, a wiring symbol is generally drawn as a single line but with
slanting "tick marks" to indicate the number of wires in an electrical circuit.
EXTERIOR ELECTRICAL LAYOUT (PLAN)
Exterior distribution lines (or network) deliver electrical power from the source (generating
station or transmission substation) to various points of use. Figure 9-24 shows a typical layout,
extracted from NAVFAC P-437, area with facilities and the location of the electrical
component system. Included in the electrical plan is a list of facilities (upper right-hand corner
of fig. 9-24) that describes the corresponding item symbol, facility number, and quantity. An
electrical load data table is also included in the drawing.
As an EA, you will be called upon to trace, modify, revise, and even review the workability of
the drawing. It is therefore to your advantage not only to study and become familiar with the
electrical plans, but also to gain a working knowledge of how the system works. NAVFAC P-
437 offers a wide variety of plans, drawings, and applications for the Advanced Base
Functional Component (ABFC) System for use in SEABEE construction.
INTERIOR ELECTRICAL LAYOUT (PLAN)
As we mentioned earlier, the electrical information on exterior electrical distribution is
generally shown in the regular site or plot plan. The INTERIOR ELECTRICAL LAYOUT,

Adama Science & Technology University Page 85


Electrical Installation Handout

however, is, for small buildings, drawn into a print made from the floor plan. On larger
projects, additional separate drawing sheets are necessary to accommodate detailed information
needed to meet construction requirements.
Figure 9-25 shows an electrical layout of a typical public works shop. Once again, note that the
electrical information is superimposed on an outline taken from an architectural floor plan. In
addition to the list of assemblies and electrical load table, a wiring diagram and panel schedule
of a 225-A, three-phase circuit breaker is drawn. The underground service entrance (item 10 on
the list of assemblies) delivers a four-wire, 120/208-V power into the building. Lighting
circuits use a three-wire, No. 12 AWG (TW).
The following basic steps are suggested to guide you in the development of an interior
electrical plan:
1. Show the location of the service panel and its rating in amps.
2. Show all of the wall and ceiling outlets.
3. Show all of the special-purpose outlets, such as telephones, communications, doorbells, and
so forth.
4. Show all of the switches and their outlet connections.
5. Show convenience outlets.
6. If required, complete a schedule of electrical fixtures, symbols, legends, and notes necessary
to clarify any special requirements in the drawing that are not stipulated in the specifications.
The steps suggested above can be put to practice in the next chapter following mastery of civil
and architectural drawings.

Adama Science & Technology University Page 86


Electrical Installation Handout

3. Contracting Electrical Construction


3.1. Electrical installation contracting

The law relating to contracts is extremely complicated and involved, and hence only the most
basic concepts will be considered. In simple terms, for any job there is a main contractor,
which can be an electrical installation firm, building firm or a decorating firm, etc., depending
on the work to be done. This main contractor is responsible to the client (i.e. the person
ordering the work to be done), either directly or via an agent such as an architect.

Should the main contractor employ the services of another firm, this firm is called the
subcontractor and is responsible to the main contractor. A typical sequence of events is as
follows:

1. The client approaches an architect with a view to having, say, a hotel designed and built.

2. The architect designs the building and the design is approved by the client.

3. A specification and a bill of quantities are prepared.

4. The work is put out to tender, and eventually one is selected – not necessarily the lowest
priced.

5. The architect may nominate the sub contractors that is, painters, electricians, plumbers, etc.,
or leave it to the main contractor. In any event the subcontracts will go to tender. This is where
the ability to read and interpret drawings, bills of quantities and specifications is so important..

3.2. Cost Estimation


Introduction
Estimating is an art by which we can get an approximation of the material, investment
involved, and the time to be taken for the completion of Electrification project we are planning
to do.
By estimating the material coast and the time required for completion of the project we can set
help in making right and firm decision while making a contract with any firm but in itself the
report prepared on estimating and costing does not establish any tender or contract. The job of
an estimator is interconnected with different aspects of estimating a program in such away that

Adama Science & Technology University Page 87


Electrical Installation Handout

it can not be demarcated separately very easily. Normally ,it can be analyzed under the
following headings.
Estimating the quantity of material and the cost involved.
1-Analysis of cost or selling price.
2-Maintaining proper accounts.
3-Provision of selling aids.
Purpose of Estimating and Costing
It is necessary to know the necessary material and the cost to be incurred on it before starting
anew program. Hence it is necessary to make a complete project report for the program be
cause this project acts as a guide in the successful implementation of our program.

Estimating is also necessary because it gives us certainty about the amount of money required,
availability of material etc.
In the absence of pre-project and the work started without estimating and costing, the work
cannot be completed in uninterruptedly because; it becomes difficult to continue the work due
to instantaneous shortage of money or unavailability of material.
For purchasing the material according to estimating and costing, market survey is necessary.
The estimating and costing have the following aims.
-To ensure that the list of material is completed before starting the job so that there are very
sleek chances of shortage of any necessary material after staring the work.
-To ensure that the money is not misused in the projects under implementation.
-The time is saved i.e. the work is completed well in time as planned.
The following problems may come on the work started with out estimating and costing.
-It becomes very difficult to purchase necessary material in the absence of list of material.
-The money is misused by purchasing seller, or excess quantities of material from market and
the shortage of money cause the work interrupted.
-Due to above mentioned difficulties, the work may take more time for completion and it can
affect the other project which is related to the existing project in hand.

Hence, for completion of project work with in time limit uninterruptedly and with out misuse of
money, it is necessary to do estimating and costing prior to starting any work on the project.

Adama Science & Technology University Page 88


Electrical Installation Handout

For instance, for electrification of any building, estimating and costing is necessary. The
estimator will make complete planning of electrification including designing of wiring, location
of points and finally prepare a complete estimating and costing report.
After purchase of material according to the estimating and costing report, the work should be
completed under the supervision of some qualified or permit-holder engineer (from chief-
electrical inspector), supervisor or contractor.

Essential Elements of Estimating and Costing.


The estimator should also know the following aspects, which are essential elements of
estimating: -
-Specification of material
-Latest market cost of material
-Prince list and net princes
-Calculation of material and labour cost
-Knowledge of purchase system
-Labour cost.
Specification of material
The specification and cost of all necessary material should be known at the time of preparing a
report on estimating and pricing of the project. It will be very difficult to purchase the material
from market without knowledge of specifications.
For example, it will be very difficult to choose a specific holder out of different holders to be
installed in an electrical installation, because there are many holders, batten holders or screw
type holders, pendant holders available in market.
In the absence of detailed specifications, the shopkeeper feels difficulty in providing the correct
material.
Market Survey: - The market cost of material is that cost of the material at which it can be
purchased or brought to the store at any time. The mistakes or carelessness show purchasing the
material with out any market survey will add the cost of electrical installation along with
addition of time in completion of the project. Market survey is an art in which only experienced
persons succeed.

Adama Science & Technology University Page 89


Electrical Installation Handout

Price List: - By market surrey, the estimator gets the price list of the material from
shopkeepers in which the shop keepers give the retail and wholesale prices according to local
market rates. This list is updated according market rate from time to time.
Hence, at the time of estimating and costing, the price list available at that time of the market
should be taken in to consideration.
Net Price: - is that price, in which all the imposed taxes such as sale tax,
Central sales tax, excise duty and other local taxes are included.
Electrical Schedule: - is that list or plan of the building by which we come to known the
number of points provided in each room of the building under estimation. We need to know the
ceiling outlet, different switches, wall plugs and any other special plus etc. in any room of a
building under estimation.
Preparation of List of Material :- preparing estimation of the total material required for a
project and the total cost involved in the project is an important task of the estimator.
Table List of Material

Sr.n Name of Item with Required Rate


full Specification Qty Total Remar
Cost ks
Birr

Qty Unit Birr Per


Double, pole, iron
1 clad, main switch, 1 Num
30A rating, 250v ber
grading

Determination of Labor Cost: The total cost involved on the project is completed in two
steps: -
1. Quantity of material and cost determination
2. Determining of labor charges

Adama Science & Technology University Page 90


Electrical Installation Handout

To arrive at a final conclusion for determination of labor charges for wiring a particular
building is very difficult. It is because of the effect that labor charges are different at different
places. It is therefore necessary to arrive at a common conclusion on the aspects of labor
charges. The labor charges can be as under:
-As per duration and work amount
-As per unit work basis
-As per percentage of material cost
Guide Lines for Conducting Estimates
The engineer who has been assigned for estimating for internal house /commercial/ building
wiring, he /she should be fully conversant for the general rules followed for internal wiring.
The general rules, which are to be kept in mind in executing the internal wiring, are as under.
-The pace where the service connections from nearest pole are to be received should be selected
carefully. The pace should be covered to provide protection to energy meter against rain sun
and mechanical damage.
-No additional road is to be connected to an existing installation unless it has been ascertained
that the installation can carry the additional lead safely.
-The height of main board, and meter beard are to be installed so that its center is 1.6 Meters
above the floor.
-The socket outlets in house wiring in office buildings can be installed 0.3m above floor but
those to residential buildings can amount to electrical accidents by small children in the house.
-Sufficient number of socket out lets is to be provided at suitable places.
-3 pins, 5Amp socket outlets are to be used for light and fan sub. Circuits, 3 pin, 15A sockets
are to be used in power circuits.
-In both rooms, the height of socket outlet should not be less than 1.5 meters in any case.

-For small and medium sized rooms, all light points are to be placed on walls about 2.75 to 3.0
meters above floor on horizontal run below ceiling.
-All ceiling fans are to be hung 2.75 meters above the floor, unless otherwise specified.
-Each sub-circuit, is better it not more than ten lighting, fan and fire (5Amper) socket outlets. If
a separate sub- circuit is installed for fans only, the number of fans in that sub-circuit is not to
exceed ten.

Adama Science & Technology University Page 91


Electrical Installation Handout

-The fuse and switch are not to be provided on earthed conductor or earth wire.
-The metal sheaths or conduits for all wiring and metal covering of all current consuming
apparatus or appliances is to be properly earthed in order to avoid danger from electric shock
due to leakage or failure of insulation.
-In large buildings where 3 phase 4 wire supply is to be given, the load is to be distributed
equally on all the phases.
-All apparatus requiring attention are to be provided with means of access to it.
-The height of ceiling for a normal residential building may be taken as 3.5 meters for
estimation purpose. The height of ceiling for large halls may be assumed to be 4-meters.

-While calculating the cost of wiring a house or commercial building, the rates from the local
market of standard quality goods preferably of the some company should be taken into
account as there is a variety of rates from company to company.
-The estimator must take into account each and every item i.e. from minor items to major items
required in the wiring calculations.

Sequences to carry out estimate


While calculating the material and cost of wiring a house the following sequence should be
adopted in case of conduit system of wiring.
a) Drawing Installation plan drawn in suitable scale and electrical points, switch board, location
of main board, energy meter, distribution board etc. are marked on the plan through specified
symbols.
b) Assumptions:- for instance location of main board in verandah can be assumed to be half or
one meter inside. The height of the building may also be assumed it not specified.
c) Calculations: - For length of conduit pipe. It may be calculated in three stages:-
-The conduit installed from switchboards up to horizontal run including from main switch.
-The conduit on walls running parallel to floor (Horizontal run) running below ceiling.
-The conduit installed between HR and ceiling to last point on HR.
 Them finally add the three stages and add 10% wastage.
d ) Calculations for phase & Neutral wire :- the phase wire and Neutral wire is calculated sub-
circuit wises for instance.

Adama Science & Technology University Page 92


Electrical Installation Handout

Sub ckt No 1 :- phase & Neutral wire


Sub ckt No 2 :- '' ''
 Then finally totalize the phase and neutral wire and add 15% wastage on each.
E) Calculate for length of Earth wire: - the earth wire for casing Capping and batten wiring is
laid on the batten along with other wires. If the conduit is metal pipe no additional earth wire
will be in the conduit, as the conduit can act as earth wire.
f) Prepare material Table: - It should be prepared with complete Specification of each item.

Adama Science & Technology University Page 93


Electrical Installation Handout

Adama Science & Technology University Page 94


Electrical Installation Handout

3.3. Contract Document Preparation


The preparation of an accurate and complete electrical specification is the responsibility of the
architect/engineer and is an integral part of the project contract documentation. The
specification must be coordinated with the project electrical drawings and failure to do so can
result in significant costs and lost time for making corrections.
The electrical specification for a project might refer to hundreds of products, parts, and
components as well as numerous items or equipment and systems. By agreement between the
owner and the architect/engineer, these items can be specified in different ways. They can be
approved only if they are the products of a single manufacturer and are identified by a part or
model number. Alternatively, the citation of one manufacturer and model numb ber can
become the standard for quality and specification grade hospita1. industrial, commercial, or
residential) if the phrase “or equivalent” is added. Yet another option is simply the statement in
the specification that a material or product shall conform to a specific commercial, federal, or
military standard or comply with certain codes and tests.
In some specifications, especially those calling for the procurement of equipment or systems, a
summary of critical performance characteristics and perhaps outline dimensions is included to
define the desired products. This information can be obtained from the catalog data obtained
from a number of manufacturers whose products have been approved as meeting the
specification requirements. By using this approach, procurement is opened to competitive
bidding from a wider base of qualified suppliers. This can lead to more favorable prices and
delivery schedules.

Adama Science & Technology University Page 95


Electrical Installation Handout

Adama Science & Technology University Page 96


Electrical Installation Handout

TYPE ‘B’ 3 BED LINKED (Continued)

DINING ROOM

1 Ceiling light point

2 Twin socket outlet

1 Radiator

KITCHEN

1 Fluorescent ceiling light

3 – Twin 13 A socket outlets

Adama Science & Technology University Page 97


Electrical Installation Handout

1 Cooker control with 1 additional socket incorporated

1 Immersion heater switch

1 – 13 A point for gas boiler

Wall-fitted gas boiler for central heating

3 Gas points

Double drainer, stainless steel sink unit, mixer taps and cupboard under

1 Large base unit

1 Broom cupboard

1 High level cupboard

HALL

1 Ceiling light point

1 – Twin 13 A socket outlets

CLOAKROOM: 1 Ceiling light point

1 Low-level W.C. suite

1 Corner hand basin

GARAGE: Metal up and over door

1 Ceiling light point

1 – Twin 13 A socket outlets

Electric and gas meters

LANDING: 1 Ceiling light point

1 – Twin 13 A socket outlets

Adama Science & Technology University Page 98


Electrical Installation Handout

1 Full height airing cupboard with slatted shelves

BEDROOM 1: 1 Ceiling light point

2 – Twin 13 A socket outlets

1 Radiator

BEDROOM 2: 1 Ceiling light point

2 – Twin 13 A socket outlets

1 Radiator

BEDROOM 3: 1 Ceiling light point

2 – Twin 13 A socket outlets

1 Radiator

Adama Science & Technology University Page 99


Electrical Installation Handout

Adama Science & Technology University Page 100


Electrical Installation Handout

Adama Science & Technology University Page 101

Vous aimerez peut-être aussi