CF150MAx
XF80MAx
XF150MAx
CF80MAx
CF80MAx or
CF150MAx XF80MAx or
Counterflow XF150MAx
Tower
Crossflow
Tower
CF80MAx Counterflow Cellular Drift Eliminators CF150MAx Counterflow Cellular Drift Eliminators,
are specifically-designed for applications requiring are cost-effective, high-efficiency cellular drift elimina-
very low drift levels in counterflow Cooling Towers, tors designed specifically for counterflow Cooling
Evaporative Cooling systems, Turbine Intake Hoods, and Towers and Evaporative Cooling systems. With over 10
Scrubbers, providing the best drift removal efficiency. million square feet installed worldwide, the 150-series
With field-verified drift test results of .0005% per CTI has been our most popular drift eliminator.
Standard 140 (the industry standard for testing of cooling
tower drift), there is no need to use double layers of drift FEATURES & BENEFITS “MA” Technology
eliminators to achieve high drift-reduction efficiency. • Engineered flute design
PAT. NOS. 6,544,628 and 6,640,427
provides high performance at U.S. AND INT’L PATENTS
FEATURES & BENEFITS a cost-effective price.
• Beveled Drainage Tip
• Patented “MA” (Mechanical
design (right) reduces
Assembly) Technology for
pressure drop by up to 25%
environmentally-friendly
(based on air velocity of
glue-free packs
800 fpm [4.1 m/s]) over
non-beveled designs. • Heavy duty CF150MAx
Beveled Drainage Tips Male/Female attachment
modules are strong enough tabs align with and nest into
• Patented “MA”
to span 6 ft (1.8m), requiring the adjoining sheet’s tabs.
(Mechanical Assembly) Technology for environmentally-
fewer support beams and
friendly glue-free packs
less air blockage.
• Heavy duty CF80MAx modules are strong enough
• Can be field cut for a tight
to span 6 ft (1.8m), requiring fewer support beams and
fit around columns and other
less air blockage.
structures without sacrificing
• Can be field cut for a tight fit around columns and structural integrity.
other structures without sacrificing structural integrity. Attachment tabs are
• All Brentwood Cellular Drift
Dri-Seals are recommended for maximum performance. pressure-sealed ...
Eliminator modules "nest" with
• All Brentwood Cellular Drift Eliminator modules the adjoining modules (below
"nest" with the adjoining modules (below) to provide left) to provide "seamless" panel
"seamless" panel installations. installations.
• Raw material meets CTI Standard 136 and has a flame • Raw material meets CTI
spread rating of 25 or less per ASTM E84. Standard 136 and has a flame
spread rating of 25 or less per ... creating a strong,
ASTM E84. permanent bond
without glue, solvents,
or adhesives!
XF80MAx Crossflow Cellular Drift Eliminators XF150MAx Crossflow Cellular Drift Eliminators
provide the best available drift removal efficiency on are specifically-designed to achieve maximum drift
the market today. The upward flow path, steep water removal efficiency in Crossflow Cooling Towers by
drainage angle, and “tuned venturi section” make this providing an upward flow path and discharge angle of
the ideal product for factory-built crossflow towers. 40-55° from horizontal (depending on installation angle)
and molded-in drainage channels that direct the collected
FEATURES & BENEFITS drift back to the wet section of the tower even when
• The upward flow path and impacted by water spray.
steep water drainage angle
maximizes the drift removal for FEATURES & BENEFITS
crossflow applications, making • The upward flow path and discharge angle of 40-55°
it fully-effective even when increases fan efficiency by reducing pressure drop.
installed vertically.
• Installed at the standard 10° from vertical (as shown at
• The engineered venturi design left on Brentwood XF-600 Supports), XF150MAx modules
(right) increases the velocity of Tuned Venturi Section are strong enough to span 10 ft. (3.0 m), requiring fewer
the exit airflow to “scrub out” support beams and less air blockage.
smaller droplets.
• Patented “MA” (Mechanical Assembly)
• The .86” (21.8 mm) flute spacing effec- Technology for environmentally-friendly,
tively removes drift (at the lowest pressure glue-free packs
drop) in crossflow towers with high air
• Can be field cut for a tight fit around
velocities up to 800 fpm (4.0 m/s).
columns and other structures without
• Patented “MA” (Mechanical Assembly) sacrificing structural integrity.
Technology for environmentally-friendly,
• High surface area (flute height of 1.50"
glue-free packs
[38mm]) provides high performance at a
• Can be field cut for a tight fit around cost-effective price.
columns and other structures without
• All Brentwood Cellular Drift Eliminator
sacrificing structural integrity.
modules "nest" with the adjoining modules
• All Brentwood Cellular Drift Eliminator (far left) to provide "seamless" panel
modules "nest" with the adjoining modules installations.
(far left) to provide "seamless" panel • Raw material meets CTI Standard 136
installations. XF150Max shown on
and has a flame spread rating of 25 or less
Brentwood XF600 Supports
• Raw material meets CTI Standard 136 per ASTM E84.
and has a flame spread rating of 25 or
less per ASTM E84.
C E L L U L A R D R I F T E L I M I N AT O R S
PRODUCT CELL MODULE DIMENSIONS inches (mm) SHEET DRY MAX. DRIFT
NUMBER SIZE DEPTH (D) WIDTH (W) STANDARD LENGTHS (L) THICKNESS* WEIGHT SPAN** LOSS
COUNTERFLOW
.013 in
12 in 2 to 12 ft. (610 to 3658 mm) 1.6 lbs/ft2 4 ft
(.33 mm)
(305 mm) in 1 ft. (305 mm) increments (7.8 kg/m2) (1.2 m)
.86 in 5.25 in Standard
CF80MAx or up to 6 ft. (1829 mm) and in .0005%
(21.8 mm) (133 mm) 2 ft. (610 mm) increments .020 in
18 in 2.2 lbs/ft2 6 ft
(457 mm) over 6 ft. (1829 mm) (.51 mm)
(10.7 kg/m2) (1.8 m)
Heavy Duty
D L
2 to 12 ft. (610 to 3658 mm) .015 in
12 in 1.0 lbs/ft2 4 ft
W
in 1 ft. (305 mm) increments (.38 mm)
(305 mm) (4.9 kg/m2) (1.2 m)
1.500 in 5.25 in up to 6 ft. (1829 mm) and in Standard
CF150MAx or .001%
(38.1 mm) (133 mm) 2 ft. (610 mm) increments .020 in
18 in 1.4 lbs/ft 2
6 ft
(457 mm) over 6 ft. (1829 mm) (.51 mm)
(6.8 kg/m2) (1.8 m)
Heavy Duty
CROSSFLOW
.013 in
2 to 12 ft. (610 to 3658 mm) 1.1 lbs/ft2 8 ft
(.33 mm)
D in 1 ft. (305 mm) increments (5.4 kg/m2) (2.4 m)
.86 in 5.25 in 24 in Standard
XF80MAx up to 6 ft. (1829 mm) and in TBD†
(21.8 mm) (133 mm) (610 mm) 2 ft. (610 mm) increments .020 in
1.5 lbs/ft2 10 ft
over 6 ft. (1829 mm) (.51 mm)
(7.3 kg/m2) (3.0 m)
Heavy Duty
L
.015 in
12 in 2 to 12 ft. (610 to 3658 mm) 1.0 lbs/ft2 8 ft
(.38 mm)
(305 mm) in 1 ft. (305 mm) increments (4.9 kg/m2) (2.4 m)
1.500 in 5.25 in Standard
W XF150MAx or up to 6 ft. (1829 mm) and in .001%
(38.1 mm) (133 mm) 2 ft. (610 mm) increments .020 in
18 in 1.4 lbs/ft2 10 ft
(457 mm) over 6 ft. (1829 mm) (.51 mm)
(6.8 kg/m2) (3.0 m)
Heavy Duty
.140
(35)
MATERIALS .120
INCHES WG (Pa)
(30)
VELOCITY
FEET/MINUTE (METERS/SECOND)