51. Plumbing fixtures are often referred to as “sanitary ware”.

52. The total number of water closets for females shall be at least equal to the number of
water closets and urinals required for males.

53. Temporary workingmen facilities, one (1) water closet and one (1) urinal for each thirty-
(30) workmen.

54. Identify the type of water closet shown below. Siphon Vortex

55. Close Coupled Water Closet - A water closet wherein the flush tank is separate but is
attached to the bowl. It is a two-piece model.

56. A Flush Valve requires a flow pressure of - 69 to 138 kPa ( 10 to 20 psi).

57. Round Front - A type of water closet intended for installation on a limited space.

58. Supports for Wall-Hung Fixtures shall comply with ASME A 1126.1

59. Minimum size of overflow (wash basin) with a cross-sectional area must be 18 in².

60. The bathtub shall be fitted with overflow of nominal diameter not less than 32mm.

61. Flushing style for urinals will be similar to the water closet. (True or False)

62. Urinals shall not be installed where wall and floor surfaces are not waterproof and do not
have a smooth, readily cleanable, non-absorbent surface extending not less than 4ft above the
floor and 1 ft to each side of the urinal, and 1 ft of the lip of the urinal.

63. An emergency shower is also called a “drench shower” because of the large volume of
water discharged through the emergency shower.

64. Slop Sink – A deep sink, set low & used for janitors for emptying pails of dirty water &
mop cleaning.

65. Centrifugal pumps generally makes more pressure than Positive Displacement Pump's.
(True or False)
66. Positive Displacement Pumps are better suited for higher viscosity applications.
(True or False)

67. Drawdown – difference between Pumping Water Level and the Static (non-pumping)
Water Level.

68. Hydraulic Ram – It is a pump in which the power generated from flowing in an enclosed
pipe is used to raise part of the water to a height above that from which the flow began.

69. Pump Selection “ Rule of Thumb” - if a well water depth is 20 meter, use Submersible
Pump or Vertical Line Shaft Turbine Pumps.

70. Effluent pumps are design to pump solid and liquid human waste only. (True or False)

71. Sewage tanks, unlike storm tanks, must be completely water and air tight.

72. Where equipment does not operate automatically, the capacity of the sump shall be
sufficient to hold at least a 24 hours accumulation of liquid.

73. An appurtenance demands no additional water supply nor does it add any discharge load
to a fixture or the drainage system.

74. Bowl height for juvenile (children’s) use_______________ to rim. 10 ½” to 13 ½”.

75. Toilet compartments must have a minimum area of 1.70 m x 1.80 m intended for PWD as per
BP344.

76. The height of toilet seat shall be 450 mm intended for PWD as per BP344.

77. For Intermittent Flow, 4 FU is equivalent to 1 L/s to 1.89 L/s .

78. For Continuous Flow, 4 FU is equivalent to 0.126 L/s .

79. What is the Engagement Length for 75mm Cat Iron Pipe? 68mm or 2 ¾”

80 to 82. (3 Points)

From the figure below, find the number and length of cast iron pipe required using 75mm
(3”) diameter. (Use 150cm pipe standard)
From the figure below, find the number and length of cast iron pipe required using 75mm
(3”) diameter. (Use 150cm pipe standard)

a. The length of face distance is 360cm + (6.8cm+6.8cm) for 2 end engagement length =
(360+13.6) = 373.6cm

b. To get the no. of pipes. Divide total length by the effective L


373.6/(150-6.8) = 373.6/143.2 = 2.61 Pipes

c. Therefore, the pipes required base on 2.61 pipes

2 pieces (75mm dia.) x 150cm = 300cm


I piece (75mm dia.) x (0.61x150) = 91.5

Total length base on 150cm standard is 391.5cm

83 to 86. (4 Points)

Determined the quantity of oakum and lead in kilograms required for a drainage installation
with the following joint.

8 joint of 100mm pipe


14 joints of 50mm pipe having 20mm lead packing

a. Refer to table

Oakum: 8 joints (100mm) x 0.15 = 1.20 kg


14 joints (50mm) x 0.05 = 0.70 kg

b. Refer to table

Lead: 8 joints (100mm) x 1.0 = 8.0 kg


14 joints (50mm) x 0.5 = 7.0 kg
87 to 88. (2 Points)

Determine the length of galvanized steel pipe required to connect the installation using 38mm
pipe as per below
a. Say length of face distance is 430cm refer to table under 38mm pipe size (screwed pipe
length is 1.6cm)

Total pipe length is 430cm+1.6cm+1.6cm = 433.2cm

89 to 91. (3 Points)

Determine the amount of Teflon tape required for the following number of pipes and fittings
connection specifying 5 rounds per joint

For 12mm dia. pipes = 32 joints


For 20mm dia. pipes = 24 joints
For 25mm dia. pipes = 20 joints

For 12mm dia. pipes = 32 joints x 0.335m= 10.72m


For 20mm dia. pipes = 24 joints x 0.415m= 9.96m
For 25mm dia. pipes = 20 joints x 0.565m= 11.30m
Total teflon tape = 31.98 meters

92. Commercial length for uPVC Pipe is 6.0m.

93. PTFE means Polytetrafluoroethylene also known as Plumber’s tape.


94. WFSU – is numerical weighing factor to account for the water demand of various
plumbing fixtures.

95. Minimum number of Urinals in Office or Public Buildings (for employee use) having 135
males? Ans. 2 (page 7)

96. Minimum number of Water Closets in School (Secondary) having 60 males? Ans. 2

97. Minimum number of Lavatories in Office or Public Buildings (for public use) having
1200 males? Ans. 4 (page 7)

98 to 100. (3 points) Common plumbing materials:


(Vitreous China, Non-vitreous China, Enameled Cast Iron, Porcelain enameled Steel,
Stainless Steel, Plastic.)