Académique Documents
Professionnel Documents
Culture Documents
Features:
Current display in percentage
User settable trip level and timer delay
Panel mount
CBCT open circuit detection
CBCT available in various sizes
Compliance with IEC 947-1
Advantages: Applications:
Door mount Generator Control Panel
Protects human life Distribution Control Panel
Constant leakage current detection Protection Control Panel
Fewer nuisance trips
Output Specifications
96 92
Trip Relay Output 80-90% of Range
1 SPDT switch NO (5A and 240V AC)
NC (5A and 240V AC).
55 -2 -2
(Optional) 1 SPDT switch NO (5A and 240V AC) Front View Side View Panel Cutout
NC (5A and 240V AC)
Functional Diagram
Relay Contacts 1 potential free contact (NO,C & NC)
Supply
Functional Specifications Interrupted
Fault
Set Point 0.03, 0.10, 0.30, 0.50, 1.0, 3.0, 5.0, Current
Trip Level (I?n)
10.0,20.0 & 30.0 A Reset Level
Power ON Delay Approx. 1 sec Failure of connection
to toroid
request
1 2 3 4 5 6 7 8 9 10
Weight 228 g NC C NO NC C NO
N
Dimensions 96X96X48mm (WxHxD)
P
Mounting Door Mount
Enclosure ABS Thermoplastic
Ordering Information
User Settable Parameters
Range Set 0.03, 0.10, 0.30, 0.50, 1.0, 3.0, 5.0, Ordering Code Description
10.0, 20.0 & 30.0 A
Flush mounted digital ELR, current rating
Delay Set 0.04, 0.06, 0.15, 0.25, 0.5, 0.8, 1, 2.5, VIPS 98PF 30 mA- 30 A, SMPS based
5, 10 Sec