Vous êtes sur la page 1sur 13

HVDC Connected Offshore Wind Farm

DIgSILENT PowerFactory ∗

Abstract the “Detailed Feeder” single line diagram).


The remaining 70 turbines are aggregated
into four DFIG models: three models repre-
This paper discusses the modelling of an senting 20 parallel machines and one rep-
HVDC link for a 400 MW offshore wind farm resenting 10 parallel machines. This ap-
consisting of DFIG wind turbines. Voltage proach offers a compromise where detailed
source converters (VSC) are used for the studies of the explicitly modelled feeder can
HVDC connection. The paper covers load be carried out but where the overall the size
flow calculation and time-domain simulation of the system is reduced. The wind farm
(RMS and EMT). model was built using a Template of a wind
turbine model from PowerFactory’s global li-
brary. The template includes models of the
main elements of the wind turbine (Gener-
1 Content ator and Transformer), as well as the addi-
tional dynamic models which represent the
controllers, PLL etc. during dynamic RMS
This document presents a model of a high and EMT simulations. The asynchronous
voltage direct current (HVDC) system. Simu- generator model used for the DFIG contains
lations are performed and the results are dis- the simulation equations for the frequency
cussed. The simulations show the behaviour converter used on the rotor. Hence only one
of the HVDC system in the case of onshore connection is needed to connect the gener-
and offshore faults. ator to the network (the frequency converter
is connected internally). The HVDC link was
modelled using the VSC element in Power-
Factory . The control structure is of a generic
2 Base Model type. A description of the control structure
used is given in chapter 4. A short descrip-
In the Base Case of the HVDC Offshore tion of the usage of the HVDC system in
Wind Farm example, a model of an off- other projects is given in Section 5. The
shore wind farm is represented. The wind Base Case has been configured for a load
farm consists of 80 wind turbines connected flow calculation. For all other kinds of calcu-
via a voltage source converter high voltage lation or simulation, please refer to the other
direct current system (VSC HVDC, Figure Study Cases (see section 3).
5) to a 380 kV onshore transmission net-
work. Each wind turbine has a nominal
active power of 5 MW. The machines are
equipped with doubly-fed induction genera- 3 Calculations and Simula-
tors (DFIG, wind turbine type 3). Only 10
of the 80 wind turbines are modelled as in-
tions
dividual machines (these are represented in
∗ DIgSILENT GmbH, Heinrich-Hertz-Str. 9, 72810 The following sections will describe the re-
Gomaringen, Germany, www.digsilent.de sults which can be obtained using the dif-

DIgSILENT PowerFactory, r1337 1


HVDC Connected Offshore Wind Farm

ferent study cases of the project “HVDC Off- command dialogue!


shore Wind Farm”.

To run time-domain simulations as described


in Section 3.2, 3.3 and 3.4 the RMS/EMT 3.2 Offshore Fault RMS
Simulation toolbox should be selected as
shown in Figure 1. A simulation has to be ini- In the study case “03 Offshore Fault RMS”
tialised first. The required dialogue is acces- a simulation of a short-circuit in the offshore
sible via the button Calculate Initial Condi- network is presented. The RMS simula-
tions ( ). For the study cases described in tion method is used. The fault location is
the following subsections, all settings in the the node “Term b” located in the detailed
project are already correctly configured. By feeder (first node). The fault is defined via
pressing Execute the simulation initialises. a short-circuit event. The fault starts at 0.0 s
The simulation can then be started by press- and is cleared after 150 ms by opening the
ing the Start Simulation button ( ) and exe- breaker which connects the detailed feeder
cuting the command. The results are visible to the Sub A/A1 terminal. The results are
after the simulation has finished. presented in the two virtual instrument (VI)
panels “Windpark res” and “HVDC res”. The
first VI panel contains results of the wind tur-
bines and the fault current. The second VI
3.1 Short-Circuit Calculation panel shows results of the two HVDC termi-
nals.
In the study case “02 Short Circuit Calcu-
lation” of the HVDC Offshore Wind Farm The results show that the short-circuit can
example the short-circuit calculation is pre- be handled without tripping the HVDC con-
sented. Please press the Calculate Short- nection. This is possible because the fault is
Circuit button ( ) to execute the short- in the 33 kV medium voltage network. The
circuit calculation. voltage drop at the HVDC AC terminal is
not below 0.8 p.u. due to the impedance of
Since the IEC 60909 standard does not re- the three winding transformer. The DFIG
flect the fault behaviour of modern wind tur- wind turbines in the faulted feeder supply a
bines, the DIgSILENT Complete Method is controlled fault current even after the feeder
used to calculate their short-circuit contribu- is disconnected (after 150 ms). Finally the
tions. The quantities Ik00 , Ib , Ith etc. are protection scheme disconnects the wind tur-
calculated, which express the stress on the bines (see Figure 2).
grid elements. In this study case, settings
have been selected for the Complete Method
short-circuit calculation which are similar to 3.3 Onshore Fault RMS
those of IEC 60909 (c = 1.1 for max. short-
circuit currents; loads, capacitances of lines,
In the study case “04 Onshore Fault RMS”
magnetizing currents of transformers, shunt
a simulation of a short-circuit in the onshore
elements and filters are ignored in the pos-
network is presented. The RMS simulation
itive sequence). In addition, settings have
method is used for this example. The fault lo-
been applied which take the short-circuit
cation is the node “Onshore Slack”. The fault
contribution of the wind turbines into account
is defined via a short-circuit event. The fault
accurately. Accuracy is achieved by using
starts at 0.1 s and is cleared after 150 ms
current iteration to calculate the transient
by a second event which removes the fault.
short-circuit current Ik0 . In this current itera-
The results are presented on the two virtual
tion the additional reactive currents provided instruments (VI) panels “Windpark res” and
by the wind turbines are taken into account “HVDC res”. The first VI panel contains re-
precisely, based on the k factor setting and sults of the wind turbines and the fault cur-
the max. current of each turbine/converter. rent. The second VI panel shows results of
Ib and Ith are calculated on the basis of the two HVDC terminals.
Ik00 and Ik0 . Please note that the option
’Current Iteration’ has been activated on the The results show that the offshore wind farm
’Advanced Options’ page of the short-circuit is not affected by the fault. This is possible

DIgSILENT PowerFactory, r1337 2


HVDC Connected Offshore Wind Farm

because the wind farm is decoupled from the simulated with the RMS simulation.
onshore AC network via the DC circuit. The
power which cannot be transmitted to the on-
shore network is consumed by the chopper
resistors (see Figure 3). 4 HVDC Control
The onshore converter switches to a reactive
current priority mode during the fault. This The HVDC control is based on a generic
allows the combined voltage/reactive power structure. It consists of two separate com-
droop control to increase the reactive current posite models: one controls the onshore
to the maximum value. The active current is converter with its chopper resistors, the other
limited during this time via the current limita- one controls the offshore converter.
tion (see Section 4 for further controller de-
scription).
4.1 Onshore Converter Control

3.4 Offshore Fault EMT The composite model of the onshore con-
verter control is based on the frame definition
“Frame onshore VSC” which is displayed in
In the study case “05 Offshore Fault EMT” a Figure 6. Each block represents an element
simulation of a short-circuit in the offshore in PowerFactory . The chopper control with
network is presented. The EMT simulation the two DC valves is marked in red. Besides
method is used for this example. The fault the chopper control, there are two more con-
location is the node “Term b” located in the trollers in the composite model. These are
detailed feeder (first node). The fault is de- the “Main Controller” and the “Current Con-
fined via a short-circuit event. The fault troller”. All controllers will be described in the
starts at 0.0 s and is cleared after 150 ms by following sections.
opening the circuit breaker which connects
the detailed feeder to the Sub A/A1 termi-
nal. The results are presented on the two
4.1.1 Main Controller
virtual instrument (VI) panels “Windpark res”
and “HVDC res”. The first VI panel contains
results of the wind turbines and the fault cur- The onshore converter is a voltage source
rent. The second VI panel shows results of converter. It can control the active current
the two HVDC terminals. as well as the reactive current. The con-
trol objective of the active current is the DC
The results show that the short-circuit can voltage. The control objective of the reactive
be handled without tripping the HVDC con- current can be selected via an input parame-
nection. This is possible because the fault is ter. It can be set to control either the voltage
in the 33 kV medium voltage network. The (with a PI controller), the voltage via a droop
voltage drop at the HVDC AC terminal is or the reactive power (via a PI controller).
not below 0.8 p.u. due to the impedance of This can be changed via the input parameter
the three winding transformer. The DFIG ’MODE’. The block definition of the onshore
wind turbines in the faulted feeder supply a controller is shown in Figure 7. The active
controlled fault current even after the feeder current control path is marked in red, the re-
is disconnected (after 150 ms). Finally the active current control path is marked in green
protection scheme disconnects the wind tur- and the current magnitude limitation block is
bines (see Figure 4). highlighted in blue. During normal operation
the current limiter prioritises the active cur-
The difference between RMS and EMT sim- rent (id) and limits the reactive current (iq).
ulation is that the EMT simulation takes the But during and up to 500 ms after faults (i.e.
inductive and capacitive behaviour of lines u < (u0 − U t)) the reactive current is priori-
and transformers into account via differen- tised and the active current is limited.
tial equations (electro-magnetic transients).
This leads to more precise results. The re- The control uses a first order lag filter (low
sults include the DC component of the short- pass) on the measured AC voltage and on
circuit current. This phenomenon cannot be the measured reactive power. The filter time

DIgSILENT PowerFactory, r1337 3


HVDC Connected Offshore Wind Farm

constant is fixed to 10 ms for the voltage and 4.2 Offshore Control


30 ms for the reactive power. The parame-
ters used in the model are described in Table The offshore controller has to build the off-
1. shore grid voltage. This means the controller
has to keep the frequency and the voltage
On the second page (accessed via the but-
magnitude of the AC offshore network at a
ton below Cancel or via the ’Advanced 1’
constant value. The resulting active and re-
Tap for PowerFactory version 15.1 and later)
active power which flows through the con-
of the common model of the onshore con-
verter cannot be controlled (the converter is
troller there are additional parameters which
the slack in the offshore system).
represent a characteristic for the current lim-
itation. The values of the characteristic are
presented graphically in Figure 8.
4.2.1 Frame of the Offshore Control
Scheme

The definition of the frame used for the com-


4.1.2 Current Controller posite model of the offshore controller is
shown in Figure 11. There are measure-
ment devices used for detecting the offshore
The current controller takes the reference AC voltage, the AC current of the converter
currents from the main controller and calcu- and for the DC voltage (positive and neg-
lates the modulation index which is passed ative). There is also a PLL (phase locked
to the converter. It would also be possi- loop) measurement device, but this element
ble to use the built-in current controller of should only be in service for EMT simula-
the ElmVsc. In this case the option ’Use tions (this is managed in the project via a
integrated current controller’ has to be acti- Variation).
vated on the RMS page of the ElmVsc. The
graphical definition of the current controller
is shown in Figure 9. The control parame- 4.2.2 Common Model of the Offshore
ters are given in Table 2. Controller

The offshore controller has to keep the AC


voltage magnitude and the frequency to a
constant value. This is done via the in-
4.1.3 Chopper Control put signal “Pm” (modulation index) and “f0”
(frequency) of the PWM converter (ElmVsc).
The modulation index is controlled via two
The Chopper Control has the positive and cascaded PI controllers plus a feed forward
negative DC voltage as input signals. It will path using the measured DC voltage. The
ignite the DC valves of the chopper resistors controller structure is shown in Figure 13.
if the voltage exceeds a certain limit and it The controller parameters are given in Table
will block these valves if the voltage drops 4.
again below a defined threshold. The chop-
per resistors are needed in case of a fault in The first PI controller gets the AC voltage de-
the onshore network. In this case, the power viation as input signal, its output is the reac-
which is fed into the DC circuit on the off- tive current reference. This reference signal
shore side cannot be transferred to the on- is compared against the measured reactive
shore AC network by the onshore converter. current. The output of the second PI con-
As a result the DC circuit will be charged. troller is then the reference voltage. In the
This can damage the IGBT valves of the con- block “Udc Feedforward” the reference volt-
verters, therefore the DC chopper has to limit age (AC voltage Uac ) is divided by the mea-
the voltage to an appropriate value. The sured DC voltage Udc and multiplied with
graphical definition of the chopper control is a constant which depends on the modula-
shown Figure 10. The parameters are given tion method (see block: Udc Feedforward).
in Table 3. The ratio Uac /Udc cannot be increased in-

DIgSILENT PowerFactory, r1337 4


HVDC Connected Offshore Wind Farm

definitely as shown in Figure 12. The templates has to stay open while adding the
block “Udc Feedforward” therefore contains template). All type references (line types and
a characteristic which limits the modulation controller definitions) are linked to the library
factor Pm to emulate this effect. For more folder which is located in the template. This
information, please read the technical refer- means the template should not be deleted
ence paper of the PWM converter element after the HVDC-System has been added to
ElmVsc [2]. the project.

The controller has two additional functions:

1. It has a built-in limitation of the reactive


References
current. This limitation becomes active
only in case of a fault in the offshore [1] S. Weigel, B. Weise, M. Poeller:
network. The feedback of the reactive “Control of Offshore Wind Farms with
current (iq) leads to a reduction of the HVDC Grid Connection”, 9th Interna-
voltage magnitude at the converter. tional Workshop on Large-Scale Inte-
2. The control can raise the frequency in gration of Wind Power into Power Sys-
the offshore network in case of high DC tems as well as on Transmission Net-
voltage. This can be used as kind of sig- works for Offshore Wind Power Plants,
nal to the wind turbines in the network 18th -19th Oct. 2010, Québec, Canada
to reduce the active power output. This
function is disabled by default by using [2] DIgSILENT Technical Documentation:
very high DC voltage threshold values PWM Converter, DIgSILENT GmbH,
(the chopper resistor will keep the DC Gomaringen, Germany, 2008
voltage below these values). [3] TransmissionCode - Netz- und
Systemregeln der deutschen
Übertragungsnetzbetreiber (Net-
4.3 DFIG Wind Turbine Model work and System Rules of the German
Transmission System Operators), VDN,
The wind turbine models used in this project Berlin, 2007
are generic DFIG (doubly-fed induction gen-
erator) models which are provided with Pow-
erFactory . These models can be found in
the global templates folder.

5 HVDC Template

The project contains a template of the HVDC


system. This template contains all network
elements, all controllers and all types of the
HVDC system (see Figure 5). To use the
HVDC system in another project the tem-
plate “HVDCSystem” which is located in the
folder \Library\Templates has to be copied
into the target project (to the Templates
folder). Then it can be used via the General
Templates button, as shown in Figure 14.
Pressing the General Templates button will
open a new window which shows all avail-
able templates. The “HVDCSystem” has to
be marked. After this it can be added to
the project by clicking in the single line di-
agram (please note that the window with the

DIgSILENT PowerFactory, r1337 5


HVDC Connected Offshore Wind Farm

Figure 1: Activation of the Simulation Toolbox

Figure 2: Results offshore fault, RMS simulation

DIgSILENT PowerFactory, r1337 6


HVDC Connected Offshore Wind Farm

Figure 3: Results onshore fault, RMS simulation

Figure 4: Results offshore fault, EMT simulation

DIgSILENT PowerFactory, r1337 7


HVDC Connected Offshore Wind Farm

Figure 5: Single line diagram for the HVDC system as modelled in PowerFactory

Figure 6: Frame of the onshore HVDC control system

DIgSILENT PowerFactory, r1337 8


HVDC Connected Offshore Wind Farm

Figure 7: Onshore converter control structure

Figure 8: Current limit characteristic of onshore controller

DIgSILENT PowerFactory, r1337 9


HVDC Connected Offshore Wind Farm

Figure 9: Onshore converter current control structure

Figure 10: Chopper control structure

DIgSILENT PowerFactory, r1337 10


HVDC Connected Offshore Wind Farm

Figure 11: Frame of the offshore HVDC control system

Table 1: Parameters onshore controller

Parameter Value Unit Description


umax 1.15 p.u. Max. internal voltage allowed
x 0.1487 p.u. Series reactor impedance
Trudc 0.001 s DC Voltage Filter Time Constant
Droop 0.05 p.u. Gain for Droop Control
Ku 12 - Gain of PID Droop-Controller (Q and Vac)
Kiu 100 1/s Integral Constant of PID Droop Controller (Q and Vac)
Kdu 0 1/s Derivative Constant of PID Droop Controller (Q and Vac)
fltMODE 1 - 0 = ctrl. acc. MODE, 1 = ctrl. acc. TC 2007 [3]
K flt 2 - Reactive current gain in fault mode
Kd 10 - Gain of DC PI Controller
Td 0.1 s Integral Time Constant of DC PI Controller
iqfmax 1 p.u. Max. reactive current in fault case
Ut 0.1 p.u. Voltage Deviation to enable Fault Mode
MODE 1 - 0 = voltg. ctrl., 1 = droop, 2 = Q ctrl.
i max 1.1 p.u. Current Limit

DIgSILENT PowerFactory, r1337 11


HVDC Connected Offshore Wind Farm

Figure 12: PWM Converter Characteristic [2]

Figure 13: Controller structure of offshore converter

DIgSILENT PowerFactory, r1337 12


HVDC Connected Offshore Wind Farm

Figure 14: Button to enter templates

Table 2: Parameters onshore current controller

Parameter Value Unit Description


Kpm 1.0000 p.u. Proportional Gain for d & q axis
Tpm 0.0020 s Integral Time for d & q axis
P min -3.0000 p.u. min limit Pm for d & q axis
P max 3.0000 p.u. max limit Pm for d & q axis

Table 3: Parameters chopper controller

Parameter Value Unit Description


UdcUpper 1.20 p.u. Threshold for Chopper Connection
UdcLower 1.10 p.u. Threshold for Chopper Disconnection

Table 4: Parameters offshore controller

Parameter Value Unit Description


Kuac 2.00 p.u. Proportional Gain for Voltage Controller
Tuac 0.20 s Integrator Time Const. for Volt. Controller
Kiac 2.00 p.u. Proportional Gain for Current Controller
Tiac 0.02 s Integrator Time Const. for Cur. Controller
F ref 1.00 p.u. Reference Frequency
Tfilter U 0.005 s Time constant for PT1-Filter
UdcHigh 99.00 p.u. Upper Udc Limit for Frequ. Lifting (high value disables function)
UdcLow 0.00 p.u. Lower Udc Limit for Frequ. Lifting
plusFrequ 0.03 p.u. Value of Frequ. Lifting
i min -0.70 p.u. Min Limit Value for Current Limitation
Uac min -0.10 p.u. Min Limit for Offshore Voltage
i max 0.70 p.u. Max Limit Value for Current Limitation
Uac max 1.10 p.u. Max Limit for Offshore Voltage
Frequ Grad 1.00 1/s Gradient for Frequ.

DIgSILENT PowerFactory, r1337 13

Vous aimerez peut-être aussi