NOTICE
Do not re-format the card. The card has proprietary formatting to allow it to work with the drive. Formatting will erase
this.
Figure 62: CU320-DP Controller Module
18
17
16
15
01
14
02
13
12
11
03
10
09
04
08 05
06
07 ESGN_C_TR_P_00007_1
© 2014 Joy Global Inc. or one of its affiliates. -133- Version 0001
Centurion AC Commissioning TripRite Commissioning and Setup
07 - Diag Pushbutton 11 - Slot for CompactFlash Card 16 - X124 Electronic Power Supply
08 - Equipotential Bonding 12 - X127 LAN (Ethernet) 17 - Digital Inputs / Outputs
Connection, e.g. for Profibus
13 - Type Plate 18 - Lug for Connecting the Cable
M5 / 2.2 ft-lb (3 N·m)
Shielding
14 - X126 Profibus
09 - Profibus Address Switch
19 - X100-X103 DRIVE-CLiQ
15 - Option Slot
10 - Reset Button Interfaces
Step 2: Insert the card into your CF card reader and open to view the files.
The files and folders should look like the following figure.
Figure 63: CF Card Contents
Step 3: Open the CONTENT.TXT file. At the top of the file, verify the version shown in the header.
If you do not have V04.06, proceed to Step 4. If you do have V04.06, proceed to Establishing Communication with
the Drive on page 136.
Version 0001 -134- © 2014 Joy Global Inc. or one of its affiliates.
TripRite Commissioning and Setup Centurion AC Commissioning
Step 4: Retrieve the 4.6 Firmware with 4.3 technology package.zip file from Dimensions.
Extract the contents to a folder in a location of your choice on your computer.
Step 5: Select and delete all of the firmware files on the compact flash card.
© 2014 Joy Global Inc. or one of its affiliates. -135- Version 0001
Centurion AC Commissioning TripRite Commissioning and Setup
Step 6: With all of the firmware files deleted, select and copy in all of the files and folders you extracted from the
4.6 Firmware with 4.3 technology package.zip file.
Figure 65: Copy In New Firmware Files
Step 7: Re-insert the CF card into the CU-320 drive controller and restore the 24V power to the drive.
The status LEDs on the front of all of the drive modules will flash red while the drive controller is upgrading its own
and its subordinate components’ firmware. When finished, the status LEDs on the infeed and motor (Servo) module
will be orange, while the RDY status light on the front of the CU-320 controller will flash green, indicating you are
ready to load parameters onto the drive.
Step 2: If your drive controller is part of a complete TripRite drive lineup supplied by the P&H factory,
communications will have already been set up and tested as part of the factory’s commissioning/test
procedures. Verify this is the case by pinging the 192.168.1.12 IP address of the CU-320 drive controller.
If you are able to communicate with the drive as shown in the following figure, skip to Opening STARTER and De-
Archiving / Opening Drive Parameter Set on page 146.
Version 0001 -136- © 2014 Joy Global Inc. or one of its affiliates.
TripRite Commissioning and Setup Centurion AC Commissioning
If you have a previously unconfigured drive controller, such as a replacement for a failed unit, you will need to set the
IP address of the controller as described in the following steps before moving on to Opening STARTER and De-
Archiving / Opening Drive Parameter Set on page 146.
Step 3: In order to use the Primary Setup Tool software, first disable the McAfee network security protocols on your
computer as shown in the following figure.
Make sure the Host IPS, Network IPS, and Firewall are all de-selected and turned off. These services prevent the
PST Tool from seeking out Siemens devices with factory default IP settings across subnets. Access these settings
through the icon bar at the bottom right of your Windows desktop by clicking on the McAfee shield symbol (Windows
7).
Figure 67: Disabling McAfee
ESGN_C_CC_P_00006_1
© 2014 Joy Global Inc. or one of its affiliates. -137- Version 0001
Centurion AC Commissioning TripRite Commissioning and Setup
Step 4: Once the McAfee security features are disabled, run the Siemens Primary Setup Tool.
Figure 68: Siemens Primary Setup Tool
Step 5: Under the Settings drop-down menu, select Set PG/PC Interface....
Figure 69: Set PG/PC Interface
ESGN_C_CC_P_00008_1
Step 6: In the Set PG/PC Interface dialog box, select S7ONLINE (STEP 7) for the access point of the application,
and your built-in wired Ethernet adapter card for the Interface Parameter Assignment Used.
The correct selection with be similar to the Intel(R) 82577LM Gigabit Network Connection.TCPIP.1 shown in the
following figure.
Version 0001 -138- © 2014 Joy Global Inc. or one of its affiliates.
TripRite Commissioning and Setup Centurion AC Commissioning
Once the PG/PC interface is set, you can search the shovel network for Siemens devices.
NOTICE
Once the PG/PC interface is set the first time, you will not need to reset it for future uses of the PST Tool.
ESGN_C_CC_P_00010_1
© 2014 Joy Global Inc. or one of its affiliates. -139- Version 0001
Centurion AC Commissioning TripRite Commissioning and Setup
Step 8: An error message may appear before it begins to browse the network. If it does, ignore it by selecting OK.
Figure 72: Primary Setup Tool Error Message
ESGN_C_CC_P_00011_1
You should see the status bar while the software is searching the network for Siemens Ethernet devices.
ESGN_C_CC_P_00012_1
Step 9: If you see the error in the following figure: No station was detected on the network, verify that the McAfee
security protocols have not re-enabled automatically.
Per corporate IT settings, they will do so after 10 – 15 min. Select OK to acknowledge the error and repeat Step 3 to
disable the protocols again before repeating Step 7 and Step 8.
Figure 74: No Station Detected Error
ESGN_C_CC_P_00013_1
Step 10: Upon successfully browsing the network, you should see various Siemens devices show up in the PST
Tool window similar to those shown in the following figure.
NOTICE
The Sinamics S device is the CU-320 TripRite drive controller, and any Scalance devices are Ethernet network
switches.
Version 0001 -140- © 2014 Joy Global Inc. or one of its affiliates.
TripRite Commissioning and Setup Centurion AC Commissioning
© 2014 Joy Global Inc. or one of its affiliates. -141- Version 0001
Centurion AC Commissioning TripRite Commissioning and Setup
Step 11: Expand the Sinamics S device and select Ind. Ethernet interface.
Figure 76: Setting the IP Address
Version 0001 -142- © 2014 Joy Global Inc. or one of its affiliates.
TripRite Commissioning and Setup Centurion AC Commissioning
Step 12: Set the IP address for the drive controller as shown in the previous figure.
Step 13: To download the new settings to the drive controller, select the main device, then select Download from the
Module drop-down menu.
Figure 77: Select the Main Device
ESGN_C_CC_P_00017_1
© 2014 Joy Global Inc. or one of its affiliates. -143- Version 0001
Centurion AC Commissioning TripRite Commissioning and Setup
Step 14: The software will first prompt you to confirm that IP settings on the controller will be lost and that you wish
to continue; select Yes.
Figure 79: Continue Downloading Message
ESGN_C_CC_P_00018_1
ESGN_C_CC_P_00019_1
ESGN_C_CC_P_00020_1
Step 15: If this does not happen, and you see the following error, acknowledge it by selecting OK.
Figure 82: Could Not Reach Node Error
ESGN_C_CC_P_00021_1
Version 0001 -144- © 2014 Joy Global Inc. or one of its affiliates.
TripRite Commissioning and Setup Centurion AC Commissioning
Step 16: You will then see the second error; acknowledge it as well by selecting OK.
Figure 83: Unknown Error
ESGN_C_CC_P_00022_1
What has occurred is that the McAfee security protocols have reset automatically.
Step 18: Once the new IP addressing information has successfully downloaded, the IP address next to the main
device listing should read 192.168.1.12, as shown.
Figure 84: New IP Address
ESGN_C_CC_P_00023_1
© 2014 Joy Global Inc. or one of its affiliates. -145- Version 0001
Centurion AC Commissioning TripRite Commissioning and Setup
NOTICE
You can prevent the Getting Started screen from opening every time at start-up by selecting Settings from the
Options pull-down menu and de-selecting the Display “Getting Started” at start check box.
Version 0001 -146- © 2014 Joy Global Inc. or one of its affiliates.
TripRite Commissioning and Setup Centurion AC Commissioning
At this point, you should have also downloaded the appropriate TripRite drive parameter set from Dimensions and
have the .zip file stored somewhere on your computer.
NOTICE
Do not unzip or extract the files; the STARTER software will do this itself as described in the following steps.
NOTICE
If you have previously de-archived the parameter set you will be using, complete Step 3.
If you have not previously de-archived the parameter set you will be using, complete Step 4.
ESGN_C_CC_P_00031_1
© 2014 Joy Global Inc. or one of its affiliates. -147- Version 0001
Centurion AC Commissioning TripRite Commissioning and Setup
b. The Open Project dialog box will open. Select the parameter set you wish to open and select OK.
Figure 88: Select Parameter to Open
c. Proceed to Step 5.
Version 0001 -148- © 2014 Joy Global Inc. or one of its affiliates.
TripRite Commissioning and Setup Centurion AC Commissioning
b. In the Select an archive dialog box that opens, find the zipped parameter file that you downloaded from
Dimensions and select Open.
Figure 90: Select an Archive
ESGN_C_CC_P_00027_1
© 2014 Joy Global Inc. or one of its affiliates. -149- Version 0001
Centurion AC Commissioning TripRite Commissioning and Setup
c. Another dialog box will open, asking you to select a destination directory for the new project. Allow it to
save the new project in the default location (shown in the following figure) and select OK.
Figure 91: Default Project Location
d. If a previous parameter set save on your machine has used the same project directory name, a dialog
box will appear asking if you want to rename the new folder or replace the existing one. If this is the
latest update to a parameter set you have used before, select Replace; otherwise, select Rename.
Figure 92: Directory Already Exists
ESGN_C_CC_P_00029_1
Version 0001 -150- © 2014 Joy Global Inc. or one of its affiliates.
TripRite Commissioning and Setup Centurion AC Commissioning
e. After the de-archiving process is complete, the software will ask you if you would like to open the
project. Select Yes.
Figure 93: Open the Project?
f. Proceed to Step 5.
Step 5: A dialog box may appear warning you of missing software packages. These may have been present on the
computer used to develop the parameter set, but are not necessary to download the project or interface
with the drive. Select OK to ignore the missing software packages.
Figure 94: Missing Software Packages
ESGN_C_CC_P_00033_1
© 2014 Joy Global Inc. or one of its affiliates. -151- Version 0001
Centurion AC Commissioning TripRite Commissioning and Setup
Version 0001 -152- © 2014 Joy Global Inc. or one of its affiliates.
TripRite Commissioning and Setup Centurion AC Commissioning
Step 2: You should see a dialog box similar to the following figure open. This dialog box details the major
differences between what is in the drive controller’s memory (if anything) and what you are about to
download. Select <== Download.
Figure 96: Online / Offline Comparison
© 2014 Joy Global Inc. or one of its affiliates. -153- Version 0001
Centurion AC Commissioning TripRite Commissioning and Setup
Step 3: Once you have selected Download, you will see the following dialog box open. Leave After loading, copy
RAM to ROM selected as shown and select Yes.
Figure 97: Downloading Options
During the downloading process, you should see the following progress display:
Figure 98: Downloading Progress
ESGN_C_CC_P_00038_1
You should then see the Copy RAM to ROM status display:
NOTICE
If the load progress bar does not advance to 100%, and if the Copy RAM to ROM window does not appear and close
successfully, proceed to Step 4.
Figure 99: Copy RAM to ROM Status
ESGN_C_CC_P_00039_1
If the Copy RAM to ROM window appears and closes successfully, proceed to Step 5.
Version 0001 -154- © 2014 Joy Global Inc. or one of its affiliates.
TripRite Commissioning and Setup Centurion AC Commissioning
Step 4: If you see a dialog box that looks like the following, with the only difference between projects in the custom
DCC chart programming, you are likely to see the error illustrated in Step 4a.
Figure 100: DCC Chart Programming Differences
NOTICE
This is a known and expected error.
If this error occurs, complete the following substeps. If you do not see this error, follow the procedures in Step 3.
© 2014 Joy Global Inc. or one of its affiliates. -155- Version 0001
Centurion AC Commissioning TripRite Commissioning and Setup
b. Acknowledging the previous error will take you back to the download dialog box shown in Step 4. You
will notice errors in red text (similar to the following) in the Target system output tab behind the
download dialog box.
Figure 102: Target System Output
ESGN_C_CC_P_00041_1
Version 0001 -156- © 2014 Joy Global Inc. or one of its affiliates.
TripRite Commissioning and Setup Centurion AC Commissioning
c. To reload the parameter set (which usually corrects any errors encountered on the first attempt), select
<== Download again in the dialog box. If you have closed the dialog box, select the Load project to
target system button from the tool bar at the top of the screen.
Figure 103: Load Project to Target System
d. Proceed to Step 5.
© 2014 Joy Global Inc. or one of its affiliates. -157- Version 0001
Centurion AC Commissioning TripRite Commissioning and Setup
Step 5: When the project has finished downloading, you should see a blank download dialog box similar to the
following, indicating that there are no longer any differences between the drive controller’s memory and the
project. Close the window.
Figure 104: No Differences
Version 0001 -158- © 2014 Joy Global Inc. or one of its affiliates.
TripRite Commissioning and Setup Centurion AC Commissioning
Under each of the components previously named, there are a number of sub-areas. The area we are concerned with
in each of these components is the Expert list. Double-clicking the Expert list under each component will open a tab
on the right-hand side of the STARTER window with a complete list of all of the parameters available for that module.
Open the Expert list for the infeed and Servo modules.
© 2014 Joy Global Inc. or one of its affiliates. -159- Version 0001
Centurion AC Commissioning TripRite Commissioning and Setup
Version 0001 -160- © 2014 Joy Global Inc. or one of its affiliates.
TripRite Commissioning and Setup Centurion AC Commissioning
Step 3: In the Expert list tab for the line (infeed) module, find parameter 210 (line supply voltage) as shown. Set this
value to the nominal three-phase auxiliary voltage appropriate for your machine: 380, 415, or 460VAC.
Figure 107: Parameter 210: Drive Unit Line Supply Voltage
Step 4: In the Expert list tab for the motor (Servo) module, find the following variables and verify or change their
values as appropriate:
• p210 – Drive unit line supply voltage: 510, 584, or 678VDC ([p210 Infeed * 2.1] - 288)
• p1244 – DC Link Voltage Threshold Upper: 576, 659, or 765VDC (p210 Servo * 1.129)
• p1248 – DC Link Voltage Threshold Lower: 328, 376, or 437VDC (p210 Servo * 0.644)
• p1821 – Direction of rotation:
– 0 (clockwise) – TripRite mounting orientations with the motor facing to the shovel’s right, away from the crowd
motor. These TripRite assemblies will have right-hand orientation cable drums and guards.
– 1 (counterclockwise) – TripRite mounting orientations with the motor facing to the shovel’s left, toward the
crowd motor. These TripRite assemblies will have left-hand orientation cable drums and guards.
© 2014 Joy Global Inc. or one of its affiliates. -161- Version 0001
Centurion AC Commissioning TripRite Commissioning and Setup
Step 2: Allow the drive system to automatically adjust the resolver commutation offset:
a. With the drive running, set p1990 in the Expert list of the Servo module to 1.
The parameter will perform the recalculation, then automatically reset to 0.
b. Verify that this has completed by looking at p431 in the Servo module to see if it has changed from its
factory default of 62.95°.
To preserve the newly calculated resolver offset and any parameter values changed during commissioning, it is
necessary to save the current values in the drive controller’s RAM memory to ROM (the firmware compact flash
card).
Step 3: Highlight the drive set’s main component and select the Copy RAM to ROM button in the tool bar.
Figure 108: Copy RAM to ROM
Version 0001 -162- © 2014 Joy Global Inc. or one of its affiliates.
TripRite Commissioning and Setup Centurion AC Commissioning
ESGN_C_CC_P_00049_1
© 2014 Joy Global Inc. or one of its affiliates. -163- Version 0001
Centurion AC Commissioning TripRite Commissioning and Setup
Version 0001 -164- © 2014 Joy Global Inc. or one of its affiliates.