Académique Documents
Professionnel Documents
Culture Documents
13
ENTEC ENTEC
ELECTRIC & ELECTRONIC CO., LTD
Copyright © 2002 by ENTEC ELECTRIC & ELECTRONIC CO., LTD all right reserved. Forerunner Distribution & Automation
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
Release Note:
ENHANCED TECHNOLOGY i
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
ii ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
iv ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
TABLE OF CONTENTS
1. INTRODUCTION ........................................................................................................... 1
1.1. Description .......................................................................................................................... 1
1.2. Summary of Features .......................................................................................................... 2
2. TECHNICAL SPECIFICATIONS................................................................................. 5
2.1. Inputs and Outputs .............................................................................................................. 5
2.2. Type Withstand Tests ........................................................................................................... 8
2.3. Metering Accuracy .............................................................................................................. 9
2.4. Protection Elements........................................................................................................... 11
2.5. Monitoring......................................................................................................................... 16
2.6. Recorder ............................................................................................................................ 19
2.7. Communications................................................................................................................ 22
ENHANCED TECHNOLOGY v
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
vi ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
1. INTRODUCTION
1.1. Description
y EVRC2A with the microprocessor-based digital control technology is designed to provide
protective coordination and fault clearance of distribution systems for the continuous best
quality of electric service.
y Remote monitoring and control can be provided by RTU(Remote Terminal Unit - Option)
which fundamentally installed.
y In order to perform the protection function, line voltage and current signal filtered with
analog filter and digital DFT full-cosin filter is used.
y EVRC2A provides protection, control, and monitoring functions with both local and remote.
It also displays the present trip/alarm conditions, and measured system parameters.
y Recording of past trip, alarm or control events, maximum demand levels, and energy
metering is also performed.
y Users can operate Close and Trip, and also control EVRC2A with key buttons on the user
interface panel; Protection Enabled, Ground Enabled, SEF Enabled, Reclose Enabled,
Control Locked, Remote enabled, Alternate-settings, Program 1, Program 2, Hot line tag.
y Users can manage the Recloser interface software using a portable PC for modification of
settings, acquisition of event data, and management of operation history.
y EVRC2A contains many T-C characteristic curves developed by IEEE C37.112, IEC255-3,
McGraw Edison, and KEPCO to provide fully protective coordination for the continuous
best quality of electric distribution. Users can select any time of current curve simply by
programming and modifying.
ENHANCED TECHNOLOGY 1
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
METERING
y Phase, Ground and Sensitive Ground Current and Phasors
y Line and Phase Voltage and Phasors(Source Side and Load Side)
y Current and Voltage Symmetrical Component Phasors
y Frequency Magnitude and Rate
y Synchronizing Voltage, Phasor and Frequency
y Synchronizing Delta㎸, Delta ㎐ and Delta Leg
y Single and Three Phase Power(MW, Mvar, MVA, PF)
y Energy(MWh, Mvarh)
y Maximum Demand(Ia, Ib, Ic, MW, Mvar, MVA)
y Voltage and current harmonics - Option
y Voltage and current unbalance - Option
2 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
MONITORING
y Fault Locator
y Demand trip and alarm(Ia, Ib, Ic, Ig, I2)
y Trip Counter Limit
y Synchronism Check
y Recloser main contact Wear(Per Phase)
y Recloser Operation Failure
y Voltage Transformer Failure
y Battery Automatic Load Test
y Breaker Failure with Current Supervision
y Power Quality - Option
y Recloser Gas Over and Low pressure - Option
COMMUNICATIONS
y Front Panel PORT1 RS232 Serial Port : EVRC2A interface software
y Side panel PORT2 RS232 Serial Port : EVRC2A interface software , DNP 3.0, MODBUS or
IEC60870-5-101 Protocol - Option
y Side panel PORT3 RS485 or R232* Serial Port : DNP 3.0, MODBUS or IEC60870-5-101
Protocol – Option
y Side panel PORT4 RJ45 Port : DNP 3.0, MODBUS or IEC60870-5-104 Protocol and
EVRC2A interface software – Option
NOTE : The Port3 type of EVRC2A-N is a fixed RS485 port. However, the Port3 type of
EVRC2A-N6,NT can be selected as RS485 or RS232 by a user. In order to use
RS485 port for EVRC2A-N6,NT, the Pin4 and Pin5 of RS485 should be connected.
ENHANCED TECHNOLOGY 3
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
RECORDER
y Trip and fault counter
y Supply outage counter and time – Option
y Sag/Swell detection counter – Option
y Voltage and current unbalance detection counter - Option
y System event recorder - last 2048 events
y Diagnostic event recorder - last 512 events
y Load profile recorder - last 213days
y Fault Waveform - 15 cycles × 32 events
y Fault trip event recorder - last 512 events - Option
y Power Quality event recorder - last 512 events - Option
USER INTERFACE
y Fault indicators
y Manual Battery Load Test: Battery Voltage and Charge Voltage
y Dual Functional keypads
y 20×4 Character Display(LCD or VFD : Vacuum Fluorescent Display)
y 32 LED indicators - Fault indications, sequence status, battery status, etc
y RS232 port
y Context Help Messages
y Access Security(Passcode)
4 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
2. TECHNICAL SPECIFICATIONS
2.1. Inputs and Outputs
Systems
y 3phase-3wire or 3phase-4wire, 38㎸ maximum, 800 Amp maximum
Frequency
y 50 / 60㎐ system and ABC/ACB phase rotation
ENHANCED TECHNOLOGY 5
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
6 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
ENHANCED TECHNOLOGY 7
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
Impulse Voltage
y IEEE C62.45 (1992) Withstand Capability of Relay Systems to Radiated Electromagnetic
Interference Transceivers, 6㎸(1.2×50㎲), 3㎄(8×20㎲)
Vibration Test
y IEC 255-21-1 - 1988 Electrical relays, Part 21 : Vibration, shock, bump, and seismic tests on
measuring relays and protection equipment, Section One - Vibration tests (sinusoidal), Class 2.
8 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
Phase A, B, C
POWER FACTOR Rate ±0.02 –1.000 to 1.000
3Φ Phase
Phase A, B, C
3ΦREAL POWER MW ±2% –32.000 to 32.000
3Φ Phase
3ΦREACTIVE Phase A, B, C
MVar ±2% –32.000 to 32.000
POWER 3Φ Phase
3ΦAPPARENT Phase A, B, C
MVA ±2% –32.000 to 32.000
POWER 3Φ Phase
Phase A, B, C
WATT-HOURS MWH ±2% –32000 to 32000
3Φ Phase
Phase A, B, C
VAR-HOURS MVarH ±2% –32000 to 32000
3Φ Phase
ENHANCED TECHNOLOGY 9
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
If the VT connection type is set to delta, all single phase voltage quantities are displayed as zero.
10 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
ENHANCED TECHNOLOGY 11
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
NOTE
As per the user’s request, for the products that are dispatched with ZCT installed, the “Pickup
Level” setting range of the protection element is “OFF, 0.1 to 16.0 in steps of 0.1A”. To check
whether the product is dispatched with ZCT installed, check “MAIN MENU/ STATUS/
CONTROL TYPE” menu.
Reclose Control
Operations to Lockout - phase trip ............................ 1 to 5 in steps of 1
Operations to Lockout - ground trip .......................... 1 to 5 in steps of 1
Operations to Lockout - SEF trip .............................. 1 to 5 in steps of 1
Operations to Lockout - Negative Seq’ trip ............... 1 to 5 in steps of 1
Operations of Fast curve - phase trip......................... 0 to 5 in steps of 1
Operations of Fast curve - ground trip ...................... 0 to 5 in steps of 1
Operations of Fast curve - Negative Seq’ trip ........... 0 to 5 in steps of 1
Reclose interval 1 ...................................................... 0.50 to 600.00 in steps of 0.01(prior to Ver 6.11)
0.10 to 600.00 in steps of 0.01(from Ver 6.11)
Reclose interval 2 ...................................................... 1.00 to 600.00 in steps of 0.01
Reclose interval 3 ...................................................... 1.00 to 600.00 in steps of 0.01
Reclose interval 4 ...................................................... 1.00 to 600.00 in steps of 0.01
Reset time for Auto Reclose Cycle............................ 1.00 to 600.00 in steps of 0.01
Reset time from lockout ............................................ 1.00 to 600.00 in steps of 0.01
Timing Accuracy ....................................................... ± 5%
12 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
NOTE
As per the user’s request, for the products that are dispatched with ZCT installed, the “SEF
Pickup Level” setting range of the protection element is “0.4 to 200.0 in steps of 0.1A”. To
check whether the product is dispatched with ZCT installed, check “MAIN MENU/ STATUS/
CONTROL TYPE” menu.
ENHANCED TECHNOLOGY 13
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
Under/Over frequency
Minimum Voltage ...................................................... 0.00 to 1.25 in steps of 0.01 x VT in Phase A
Minimum Current ...................................................... 10 to 1600 in steps of 1A in Phase A
Under frequency Pickup Level .................................. 40.00 to 60.00 in steps of 0.01㎐
Over frequency Pickup Level .................................... 50.00 to 70.00 in steps of 0.01㎐
Dropout Level ........................................................... at VT Pickup ±0.02㎐
at VD Pickup ±0.05㎐
Under/Over frequency Time Delay ........................... 0.00 to 600.00 in steps of 0.01s(definite time)
Normal frequency CLOSE function .......................... OFF/ON
Normal frequency CLOSE time delay ...................... 0.0 to 6000.0 in steps of 0.1sec
Level Accuracy .......................................................... at VT ± 0.02㎐, at VD ± 0.05㎐
Timing Accuracy ....................................................... 2cycle
14 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
ENHANCED TECHNOLOGY 15
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
2.5. Monitoring
Demand
Measured Values........................................................ Phase A/B/C/G Current(A)
Phase A/B/C/G 3Φ Real Power(MW)
Phase A/B/C/G 3Φ Reactive Power(Mvar)
Measurement Type .................................................... Thermal Exponential/Rolling Demand
Time Constant ........................................................... 5, 10, 15, 20, 30 or 60 min.
Phase Pickup Level ................................................... OFF, 10 to 1600 in steps of 1A
Ground Pickup Level................................................. OFF, 10 to 1600 in steps of 1A
Negative Seq’ Pickup Level ...................................... OFF, 10 to 1600 in steps of 1A
Level Accuracy .......................................................... ± 5%
Synchronism Check
Dead Voltage Maximum ............................................ 0.00 to 1.25 in steps of 0.01 x VT
Live Voltage Maximum ............................................. 0.00 to 1.25 in steps of 0.01 x VT
Maximum Voltage Difference ................................... 0.00 to 1.25 in steps of 0.01 x VT
Maximum Angle Difference ...................................... 0 to 100° in steps of 1°
Maximum Frequency Difference .............................. 0.00 to 5.00㎐ in steps of 0.01
Synchro-check Phase................................................. R(AB), S(CB), T of Load side
Trip Counters
Number of Pickup Limit............................................ 1 to 20000 in steps of 1
Trip Counter Set ........................................................ 0 to 10000 in steps of 1
Recloser Wear
Pickup Wear............................................................... 0 to 100% in steps of 0.1
Rate System ............................................................... 15㎸, 27㎸, 38㎸
Rate Interrupt(㎸) ...................................................... 5.0 to 50.0㎸ in steps of 0.1
Number of Maximum Interruption ............................ 1 to 999 in steps of 1
Set Phase A Wear ....................................................... 0.0 to 100.0 % in steps of 0.1
Set Phase B Wear....................................................... 0.0 to 100.0 % in steps of 0.1
Set Phase C Wear....................................................... 0.0 to 100.0 % in steps of 0.1
Battery Test
Period for automatically check a battery ................... OFF, 1 to 7 in steps of 1day
16 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
Fault Locator
Total Length of Feeder .............................................. 0.1 to 99.9 of 0.1km
Real impedance of the feeder positive seq. ............... 0.1 to 6000.0 of 0.1ohms
Imaginary impedance of the feeder positive seq. ...... 0.1 to 6000.0 of 0.1ohms
Real impedance of the feeder zero seq. ..................... 0.1 to 6000.0 of 0.1ohms
Imaginary impedance of the feeder zero seq ............. 0.1 to 6000.0 of 0.1ohms
NOTE : The setting for voltage/current unbalance is supported from version 6.12 of
EVRC2A-N6,NT.
ENHANCED TECHNOLOGY 17
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
18 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
2.6. Recorder
WAVEFORM CAPTURE
y Trigger Source
Protection pickup Elements
Trip command active
y Data Channels
5 currents, 4 voltages, 85 logic input states, 8ch output relays, 8ch Input
y Sample Rate : 16 per cycle
y Trigger Position : 1 to 15cycle
y Storage capacity : 32 events with 15cycle
ENHANCED TECHNOLOGY 19
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
NOTE : According to a recloser type, there may be no diagnosis of gas pressure status.
LOAD PROFILE
y Trigger Source
Demand Current(A, B, C, G)
Demand Real Power(A, B, C, 3ф)
Demand Reactive Power(A, B, C, 3ф)
Demand Power Factor(3ф)
Demand Energy( 3ф)
Trigger Time : 5, 10, 15, 20, 30, 60minute
y Storage Capacity : Total 5120 Events, 213days/60min.
20 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
COUNTER
y Trip Counter : 0 to 65,534
y Fault Counter : 0 to 65,534
y System Restart Counter : 0 to 65,534
y Supply Outage Counter : 0 to 60,000 - Option
y Supply Outage Time : 0 to 9,999 hours - Option
y Sag Counter : 0 to 60,000 - Option
y Swell Counter : 0 to 60,000 – Option
y Voltage Unbalance(Source Side) Counter : 0 to 60,000 - Option
y Voltage Unbalance(Load Side) Counter : 0 to 60,000 - Option
y Current Unbalance Counter : 0 to 60,000 - Option
RECLOSER WEAR
y Phase A Wear : 0.0 to 100.0%
y Phase B Wear : 0.0 to 100.0%
y Phase C Wear : 0.0 to 100.0%
ENHANCED TECHNOLOGY 21
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
2.7. Communications
Table 2-2. Communications
RS232, 57600bps, No Parity, 8 Data Bits, 1 Stop bit
Front Panel Port1
EVRC2A Interface software
RS232, 1200-19200bps, No Parity, 8 Data bits, 1 Stop bit
Side panel Port2 - Option DNP 3.0, Modbus or IEC60870-5-101 Protocol
and EVRC2A Interface software
RS485 or RS232*, 1200-19200bps, No Parity, 8 Data bits, 1
Stop bit
Side panel Port3 – Option
DNP 3.0, Modbus or IEC60870-5-101 Protocol
and EVRC2A Interface software
RJ-45, 10BASE-T/100BASE-T
Side panel Port4 – Option DNP 3.0, Modbus or IEC60870-5-104 Protocol,
and EVRC2A Interface software
NOTE : The Port3 type of EVRC2A-N is a fixed RS485 port. However, the Port3 type of
EVRC2A-N6,NT can be selected as RS485 or RS232 by a user. In order to use
RS485 port for EVRC2A-N6,NT, the Pin4 and Pin5 of RS485 should be connected.
22 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
ENHANCED TECHNOLOGY 23
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
3.1. Construction
Panel consists of 8 sections as below;
y Operation section
y Local control section
y Fault indication section
y Voltage elements section
y Sequence status section
y System diagnostic section
y Battery test section
y Menu control section
OPEN
Pressing OPEN push-button sends a trip signal to the Recloser.
CLOSE
Pressing CLOSE push-button sends a close signal to the Recloser.
Units operating with firmware version 2.18 or later have a feature of Close Time Delay. The Close
Time Delay allows a delay of 0.00 to 600.00 seconds after pressing the close push-button before
closing the recloser.
POSITION LED
Indicates the position of the Recloser. Position indicator is based on the Recloser 52a contacts.
24 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
All indicators show status of Control function. The indicators are continuously ON when the
control function is enabled and the indicators are continuously OFF when control function is
DISABLE. The push-button toggles Enable/Disable.
PROTECTION ENABLED
All Protection elements are enabled
GROUND ENABLED
Ground Protection elements are enabled
SEF ENABLED
SEF Protection elements are disabled
RECLOSE ENABLED
Reclose function is enabled
CONTROL LOCKED
Front panel function is unlocked
REMOTE ENABLED
Remote control is enabled
ALTERNATE SETTINGS
Alternate setting is disabled Figure 3-3. Local Control Section
Primary Setting is enabled
PROGRAM 1
Program 1 function is disabled
PROGRAM 2
Program 2 function is disabled
HOT LINE TAG
Hot Line Tag function is disabled
ENHANCED TECHNOLOGY 25
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
Protection Enabled
When illuminated, all protection elements are enabled. The protection enabled condition can be
disabled by pressing the Protection Enabled push button on the front panel. The front panel LED
will illuminate on each source of all protection enabling.
NOTE : Although all protection elements are enabled, ground protection elements and SEF
element are operated individually.
Ground Enabled
When Ground Enable LED is ON, the ground over-current elements are enabled. The enabled
Ground can be disabled by pressing the Ground Enabled push-button on the front panel.
SEF Enabled
When SEF Enable LED is on, the Sensitive Earth Fault(SEF) element is enabled. The enabled
SEF can be disabled by pressing the SEF Enabled push-button on the front panel.
Reclose Enabled
When Reclose Enable LED is on, the reclose(79) element is enabled. The enabled reclose
element can be disabled by pressing the Recloser Enabled push-button on the front panel.
Control Locked
When Control Locked LED is on, all functions in operation section and all functions in Local
control section are locked. These can be unlocked by pressing the Control Locked push-button
on the front panel.
NOTE : Even though Control Locked function is locked, OPEN, Lamp Test, Battery Load
Test and menu control section can be normally operated.
Remote Enabled
When Remote Enabled LED is on, all remote control functions (e.g. SCADA system) are
enabled. This can be disabled by pressing the Remote Enabled push-button on the front panel.
SCADA control refers to supported communications protocol such as DNP3.0.
Alternate Enabled
When Alternate Enabled LED is on, the Alternate setting is activated.
When Alternate Enabled LED is off, the primary setting is activated.
26 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
Program 1
A function installed in Program1 is operated when Program1 LED is On.
Depending on user’s request, Manufacturer sets a function in Program1.
Program 2
A function installed in Program2 is operated when Program2 LED is On.
Depending on user’s request, Manufacturer sets a function in Program2.
Indicates current on the phase or neutral lines is above the minimum pickup setting as programmed
in any of the EVRC2A over-current elements.
ENHANCED TECHNOLOGY 27
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
TRIP TYPE
y INST : Shows high current trip (50-1)
y DELAY : Shows delay trip(51)
y HIGH CURR’ : Shows high current lockout(50-2)
FAULT INDICATION
y A, B, C : Indicates an over-current fault has occurred on one of the phase lines
y G : Indicates an over-current fault has occurred on the neutral line
y SEF : Indicates a sensitive earth fault has occurred on the neutral line
y FI RESET : Reset fault indication/Lamp test
28 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
Indicates Diagnostic status of the EVRC2A. Control run indicates (green) the EVRC2A has
successfully passed its internal diagnostic test. Self Check (Red) indicates the EVRC2A has failed
in its internal diagnostic test.
CONTROL RUN
Status of EVRC2A systems shows normal
SELF CHECK
Status of EVRC2A systems shows warning
NOTE : Control Run LED is blinking when system functional status is normal.
ENHANCED TECHNOLOGY 29
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
Indicates the system power status of the EVRC2A. AC supply indicates the EVRC2A has external
power source. Charge indicates the EVRC2A is charging Battery. Discharge indicates the EVRC2A
has failed in battery load testing.
AC SUPPLY
Status of supplying the external AC
power.
CHARGE
Figure 3-8. Battery Test Section
Status of charging the battery.
DISCHARGE
Status of discharged battery.
30 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
LCD DISPLAY
4x20 Characters display
CONTROL KEYS
[▲] [▼] [◀] [▶]
Arrow keys are used for moving through the menu window and the changing of the setting value
[▲] (METER) : Up arrow key is used to move to the meter menu, operable in menu starting mode
[▼] (AWAKE) : Down arrow key is used for panel awake from sleep mode
[◀] (EVENT) : Left arrow key is used to move to the event menu, operable in menu starting mode
[▶] (SET) : Right arrow key is used to move to the setting menu, operable in menu starting mode
[FUN] : To move to main menu when present mode is in starting mode
[ESC] : To cancel for data input mode or return the display to the previous level
[ENT] : To select sub menu or data input
ENHANCED TECHNOLOGY 31
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
[FUN] Key
Press [FUN] key to enter Main menu for displaying information or changing settings. [FUN] key
is also used to display a help message in setting change mode and to cancel the help message
display.
[ESC] Key
The ESC key can be used to cancel data input mode and return to the previous menu.
[ENT] Key
ENT key is used to select a menu by using Up and Down arrow key. Enter key is also used to
accept a new setting by using Up or down arrow key.
PORT1
PORT1 is the port to communicate whit an Interface Software. Communication frame between
EVRC2A and a master can be monitored and saved by using “DNP Frame Monitor” menu of the
Interface Software.
32 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
ENHANCED TECHNOLOGY 33
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
SYSTEM SETUP
Consists of CURRENT SENSING, LINE (VS, VL) SENSING, SYSTEM POWER, PANEL
SLEEP TIME, OPTO INPUT SET, OUTPUT RELAY SET, LOOP CONTROL(option) and SET
GROUP CHANGE(option).
PROTECTION
Set items related to protection elements.
MONITORING
Set items related to measurement and maintenance.
SAVE SETTINGS
Save all changed values.
3.2.6. Status
OPTO INPUTS : Shows status of External port.
RELAY OUTPUTS : Shows status of Output port.
CLOCK : Shows the present time.
CONTROL TYPE : Shows specs of Hardware.
3.2.7. Metering
It shows metering values. For more details, refer to (see 10. METERING)
34 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
3.2.8. Maintenance
COUNTERS : Shows counters related with SYSTEM.
WEAR MONITOR : Shows any damage Interrupter.
RELAY OUTPUT TEST : Tests External Output port.
POWER QUALITY : Shows counters and time related with supply outage and counters related
with swell, sag and unbalance – Option. For more details, refer to (see 11. MAINTENANCE)
ENHANCED TECHNOLOGY 35
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
[LINE CURRENT(A)]
A: 0 B: 0
C: 0 G: 0
SG: 0 I2: 0
[MAIN MENU]
[EVENT RECORDER]
>1.SELECT SETBANK
>1.FAULT CYCLE
2.PRIMARY SETTING
2.SYSTEM STATUS
3.ALTERNATE SETTING
3.LOAD PROFILE
4.EDITBANK SETTING
4.DIAGNOSTIC
5.STATUS
5.FAULT TRIP
6.METERING
6.POWER QUALITY
7.MAINTENANCE
8.EVENT RECORDER
36 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
MAIN MENU
[MAIN MENU] Main Menu consists of 8 sub-menus.
>1.SELECT SETBANK
>2.PRIMARY SETTING You can choose any sub-menu by using [▲] [▼] key.
>3.ALTERNATE SETTING
>4.EDITBANK SETTING Press [ENT] key to select the sub-menu.
>5.STATUS
>6.METERING
>7.MAINTENANCE
>8.EVENT RECORDER
ENHANCED TECHNOLOGY 37
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
2) As above screen, to move to Phase, use [▲] [▼] key and press [ENT] key to move into
value column.
3) Use [▲] [▼] keys and [◀] [▶] keys to change a new value.
Press [ENT] key and then you can see the changed Phase value.
NOTE: You must save all changed values at Setting Save menu.
38 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
0000
2) If Passcode is correct, screen ②(Left) appears; otherwise screen ①
② (Left) appears again.
SETTING VALUE SAVE
<ENT>:SETTING SAVE 3) If screen ② appears, press [ENT] key to save changed value.
③ NOTE :
The changed setting can be effective after it is saved.
SAVE SETTING
If the “save” procedure is canceled, the setting keeps previous
value.
However, by EVRC2A version 5.30, if a setting related with
communication is changed and then saved, the changed setting is
applied after rebooting.
ENHANCED TECHNOLOGY 39
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
4. SELECT SETBANK
There were only Primary and Alternative banks before version 4.40 and 4 more banks added
since version 4.40.
EVRC2A has 6 setting banks and the user can have 6 different sets depending on Distribution
circumstance.
40 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
5. RELAY SETUP
Relay set shall be set independently for each bank. However, from version 4.41, regardless of
bank, it will be applied to all other banks if it is set in a bank.
5.1. Passcode
PRIMARY, ALTERNATE or EDITBANK SETTING / RELAY SETUP / PASSCODE
① y Press PASSCODE to store changed value.
[PASSCODE CHANGE] y PASSCODE has 4 digits.
ENTER PASSCODE
0000 y Passcode change procedure is as follows;
④
[PASSCODE CHANGE]
ENTER NEW PASSCODE
0000
PASSCODE SAVED: 0000
ENHANCED TECHNOLOGY 41
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
5.2. Communication
5.2.1. Overview
EVRC2A has four ports for communication.
The EVRC2A has the front panel RS232 port, the side panel RS232 port, the side panel RS485
port(or RS232 port) and the side panel Ethernet port.
Communication port settings are available as follows in “Table 5-1. Communication Ports
setting of EVRC2A”.
PORT2 RS-232 1200 - 19200 bps No parity 8 1 User Interface Side Panel
RS-485
PORT3 1200 - 19200 bps No parity 8 1 User Interface Side Panel
or RS-232
PORT4 RJ45 10BASE-T/100BASE-T User Interface Side Panel
PORT1(RS232)
A port to interface with Interface Software.
PORT2(RS232) – Option
The Port2 is a port for a serial communication for MODBUS, DNP3.0 or IEC60870-5-101
protocol. A user can select the protocol and configure the Port2 for the selected protocol by
changing baud rate and/or other settings for the Port2.
42 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
PORT4(RJ-45) – Option
The Port4 is a Ethernet port for TCP/IP communication (10 BASE-T /100 BASE-T speed) for
Modbus, IEC60870-5-104 or DNP3.0 Protocol. A user can select the protocol and configure the
Port4 for the selected protocol by changing its settings.
NOTE: From EVRC2A version 5.30, if a setting related with communication is changed and
then saved, the changed setting is applied after rebooting.
During IEC60870-5-104 or DNP3.0 communication through Port2, Port3 or Port 4, a user can
connect with the Interface Software “ETIMS(ENTEC Integration Management Software)” and
use it.
Please refer to “DNP3.0 Protocol Technical Manual”, “MODBUS Protocol Technical Manual”
or “IEC60870-5-101/-104 Protocol Technical Manual” for more information about setting for
each protocol.
ENHANCED TECHNOLOGY 43
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
44 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
ENHANCED TECHNOLOGY 45
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
46 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
ENHANCED TECHNOLOGY 47
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
[DNP3.0-1]
Range 0 ~ 255
>Master IP Oct1: 192
>Master IP Oct2: 168
Default ~ Step 1
>Master IP Oct3:
>Master IP Oct4:
7
2
Select the IP Address for DNP3 Communication.
IP Address : 192.xxx.xxx.xxx
① ② ③ ④
IP Addr´1,2,3,4 is ①,②,③,④
48 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
ENHANCED TECHNOLOGY 49
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
50 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
ENHANCED TECHNOLOGY 51
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
52 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
NOTE : The above set values marked with * are indicated from Ver 7.06 of EVRC2A_NT.
ENHANCED TECHNOLOGY 53
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
Select the Timeout for sending test frame in case of a long idle state.
54 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
ENHANCED TECHNOLOGY 55
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
NOTE : The above set values marked with * are indicated from Ver 7.06 of EVRC2A_NT.
56 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
ENHANCED TECHNOLOGY 57
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
NOTE : The above set values marked with * are indicated from Ver 7.04 of EVRC2A_NT.
58 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
ENHANCED TECHNOLOGY 59
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
Set the delay time of starting transmission after CTS signal is received.
60 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
5.2.3.2. PORT3-RS232/485
EVRC2A side panel PORT3 and related elements are set.
Move to “PRIMARY, ALTERNATE or EDITBANK SETTING/ COMMUNICATION/ PORT
SETUP/ POR3-232/485” to select setting for PORT3.
The setting item of this menu is same as “PORT2-RS232”. Refer to “5.2.3.1. PORT2-RS232”.
5.2.3.3. PORT4-TCP/IP
EVRC2A side panel PORT4 and related elements are set.
[PORT4-TCP/IP]
Range 0 ~ 255
>IP Addr’1:
IP Addr’2:
0
0
Default ~ Step 1
IP Addr’3:
>IP Addr’4:
0
0
Select the IP Address for EVRC2A.
IP Address : 192.xxx.xxx.xxx
① ② ③ ④
IP Addr´1,2,3,4 is ①,②,③,④
[PORT4-TCP/IP]
Range 0 ~ 255
>Gateway Addr’1:
Gateway Addr’2:
0
0
Default ~ Step 1
Gateway Addr’3:
>Gateway Addr’4:
0
0
Select the Gateway Address.
Gateway Address : 192.xxx.xxx.xxx
① ② ③ ④
ENHANCED TECHNOLOGY 61
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
62 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
ENHANCED TECHNOLOGY 63
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
CONNECT 9600
The modem has a "quiet mode" that disables these messages.
The AT command is ATQ1. There will be no OK printed in response to this command.
Dialing
y The user should insert an order for Reset.
y Wait 0.5 second
y Make a phone call by using Dialing String and Dialing Number.
y Checks DCD is Asserted
※. Dial connection waiting time is depending on “ Data Link Timeout” set by the user.
64 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
Hang up
y DTR Line is deasserted
y Wait 2 second
y DTR Line is asserted
y Wait 2 second
※. EVRC2A will hang up the modem after a delay of 30 seconds with no valid packet received or
transmitted.
Device Name:
This is the device name sending a short message.
※ The current SMS function supports to send a message only for Binary Input event.
ENHANCED TECHNOLOGY 65
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
66 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
Calling Number
ENHANCED TECHNOLOGY 67
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
Initial String
68 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
Connect Parameter
ENHANCED TECHNOLOGY 69
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
NOTE: The setting items, SMS Use, SMS Time and SMS Type, are shown on the menu of
EVRC2A supporting SMS function.
70 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
5.2.5. EVENT&ETC
Move to “PRIMARY, ALTERNATE or EDITBANK SETTING / RELAY SETUP /
COMMUNICATION / EVENT&ETC”.
COMMUNICATION/ EVENT&ETC / AI Evt Method
Range OFF,TH,DB,BOTH
[EVENT&ETC]
> AI Evt Method: OFF Default OFF Step ~
> SKIP at Fault: YES
> Fault ‘I’ Evt: YES Select the Analog Event Type. This setting value is applied only to the
AI point with vitalized “Event Active” in DNP point map.
OFF : AI Point Event doesn’t occur.
TH : Event occurs when the AI Point data is over or less than
Threshold value.
DB : Event occurs when the AI data change value is over the Deadband
value.
BOTH : TH and DB are both used.
Use EVRC2A interface program to set “Event Active” enable or disable
of AI point and the Threshold value and Deadband value.
ENHANCED TECHNOLOGY 71
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
72 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
ENHANCED TECHNOLOGY 73
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
NOTE :
This setting is set to be GMT and the setting values associated
with GMT(in “TIME SET&DIS TYPE” menu) are set up
incorrectly, the time internal clock in EVRC2A can be changed
incorrectly at time synchronization.
74 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
NOTE :
The location of “Evt Time Type” setting depends on
EVRC2A_NT version.
y Ver 7.04 and later : Within “RELAY SETUP / COMMUNICTION
/ EVENT&ETC” menu.
y Prior to Ver 7.04 : Within “RELAY SETUP / TIME SET&DIS
TYPE”. The name of this setting is indicated as "Evt Sent
Type".
ENHANCED TECHNOLOGY 75
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
5.3. Clock
In order to configure current date and time, go to “PRIMARY, ALTERNATE or EDITBANK
SETTING / RELAY SETUP / CLOCK” menu.
The “CLOCK” menu screen can vary according to the EVRC2A version.
[SAVE TIME]
* SUCCESS *
[SAVE TIME]
* ABORT *
76 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
[CURRENT TIME] Press [ENT] button at ① and then as shown at ②, a cursor is marked
L ⓐ
G ⓑ to be able to change current date and time.
PRESS <ENT> TO SET
It sets the present time to GMT Time or Local time according to the
② “TIME SET&DIS’ TYPE” menu’s “Set Type” setting.
[SETTING TIME]
L2009/01/01 09:00:00
1) Use [▲][▼] button to change number and press [▶] button to
PRESS <ENT> TO SAVE
move to next item.
③ 2) After all settings for time are changed, press [ENT] button to save.
[SAVE TIME]
L2009/01/01 09:00:00 Press [ENT] button at ③ to save the changed time settings
PRESS <ENT> TO SAVE
[SAVE TIME]
If [ESC] button is pressed at ③, ⑤ is shown and the changed time
* SUCCESS *
settings are not saved.
⑤
[SAVE TIME]
* ABORT *
ENHANCED TECHNOLOGY 77
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
78 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
ENHANCED TECHNOLOGY 79
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
NOTE : According to a recloser type, they may be no this setting on the menu.
80 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
NOTE
Korea Local time is 9 hour faster than UTC time, set it as follows (+9:00);
Sing : +, Hour : 9, Min : 0
NOTE
If the setting values associated with GMT are set up incorrectly, the problems can be happened
as follows.
- If the "Time Syn’ Ref" is set to be GMT, the time of the internal clock in EVRC2A can
be changed incorrectly at time synchronization.
- If the time type of the DNP communication event is set to be GMT, the time of event
transmitted is not correct.
NOTE : The above set values marked with * are indicated from Ver 6.15 of EVRCA.
ENHANCED TECHNOLOGY 81
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
6. SYSTEM SETUP
System set shall be set independently for each bank. However, from version 4.41, regardless of
bank, it will be applied to all other banks if it is set in a bank.
For additional details on CT connections, refer to (see 13.12. Current Inputs Wiring Diagram).
82 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
6.1.2. Setting
PRIMARY SETTING / SYSTEM SETUP / CURRENT SENSING / PHA CT Ratio
[CURRENT SENSING] Range 1 ~ 1200
>PHA CT Ratio: 1000
GND CT Ratio: 1000 Default 1000 Step 1
SEF CT Ratio: 1000
ENHANCED TECHNOLOGY 83
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
6.2.2. Setting
PRIMARY SETTING / SYSTEM SETUP / LINE VS SENSING / Connect Type
[LINE VS SENSING] Range NONE, WYE, DELTA, VD-W, VD-D
>Connect Type: NONE
VT 2nd(v): 100.0 Default VD-W Step ~
VT Ratio: 155.9
Enter None if line VTs are not to be used.
NONE : VT uninstalled.
If used, external PT by user, enter the VT connection made to the
system as Wye or Delta.
WYE : Install type wye.
DELTA : Install type delta.
If installed VT of Capacitor Voltage Divide type.
VD-W : If the user system made to 3 phase 4 wire.
VD-D : If the user system made to 3 phase 3 wire.
84 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
Hence,
15㎸Ф-Ф = 8.66㎸Ф-N, therefore 8.66㎸Ф-N = 55.5(V) × 155.9
If user line voltage between phases (VoltageФ-Ф) is 11㎸, set VT2nd(v) of 40.7V and set VT Ratio
of 155.9 (11㎸Ф-Ф => 6.35㎸Ф-N, 6.35㎸ = 40.7(V) × 155.9)
27㎸Ф-Ф = 15.59㎸Ф-N, therefore 15.59㎸Ф-N = 100(V) × 155.9
38㎸Ф-Ф = 21.94㎸Ф-N, therefore 21.94㎸Ф-N = 140.7(V) × 155.9
Line with Delta connection type and has VФ-Ф= 15㎸. If external rated PT is 14400 : 120, then
VT Ratio is 14400/120 and VT2nd(v) is 15㎸Ф-Ф / 120 = 125V
120 120
15㎸ 100 86.6 71.2 125
(14400:120) (14400:120)
215 215
27㎸ 100 155.9 72.5 125.6
(25800:120) (25800:120)
300 300
38㎸ 100 219.4 73.1 126.7
(36000:120) (36000:120)
ENHANCED TECHNOLOGY 85
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
6.3.2. Setting
PRIMARY SETTING / SYSTEM SETUP / LINE VL SENSING / Connect Type
[LINE VL SENSING] Range NONE, WYE, DELTA, VD-W, VD-D
>Connect Type: NONE
VT 2nd(v): 100.0 Default VD-W Step ~
VT Ratio: 155.9
Enter None if line VTs are not to be used.
NONE : VT uninstalled.
If used, external PT by user, enter the VT connection made to the
system as Wye or Delta.
WYE : Install type wye.
DELTA : Install type delta.
If installed VT of Capacitor Voltage Divide type.
VD-W : If the user system made to 3 phase 4 wire.
VD-D : If the user system made to 3 phase 3 wire.
86 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
ENHANCED TECHNOLOGY 87
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
6.4.2. Setting
PRIMARY SETTING / SYSTEM SETUP / SYSTEM POWER / Frequency
[SYSTEM POWER] Range 50, 60 ㎐
>Frequency: 50
Phase Rotation: ABC Default 50 Step ~
>Install Dir’: NOR
Select the nominal power system frequency. This value is used as a
default to set the optimal digital sampling rate.
88 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
NOTE: The voltage sensing type to the load side can be checked on the setting of "Install
Type" in the "LINE VL SENSING" menu.
NOTE: The “Phase Combination” setting will be shown from version 6.04 of EVRC2A-
N6,NT. In order to get the details relevant to the connection for EVRC2A-N6,NT
from version 6.04, refer the following figure and table.
ENHANCED TECHNOLOGY 89
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
90 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
6.5.2. Setting
PRIMARY SETTING / SYSTEM SETUP / PANEL SLEEP TIME
[PANEL SLEEP TIME] Range OFF, 1 ~ 100 min
>Interval(m): 5
Default 5 Step 1 min
Enter the sleep mode entering time
Setting the interval time of which Panel indicator turns into Sleep
mode.
On “sleep mode”, press [▼] button to be out from the “sleep mode”.
Debounce
time Triger
EXTERNAL X
INPUT X Function execute
REMOTE mode
ENHANCED TECHNOLOGY 91
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
6.6.2. Setting
PRIMARY SETTING / SYSTEM SETUP / OPTO INPUT SET / I1 Func
[OPTO INPUT SET] Range NONE, TRIP, … , OUT8 RESET
>I1 Func: NONE
I1 Debounce: 0.02 Default NONE Step ~
I2 Func: NONE
Enter the function of External input terminal Opto input can have
following functions.
NONE TRIP CLOSE
92 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
Protective Elements
Relay Setting
( 50.51,27,59...etc )
Function Occurrence
Status LCD Display
S/R LATCH
Pulse T
Latch
LATCH S
Q
R
ENHANCED TECHNOLOGY 93
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
6.7.2. Setting
PRIMARY SETTING / SYSTEM SETUP / OUTPUT RELAY SET / O1 Func
[OUTPUT RELAY SET] Range NONE, TRIP, … , NEQ FLT*
>O1 Func: NONE
O1 Type: S/R LATCH Default NONE Step ~
O1 Pulse T: 0.05
Enter the function of External output terminal.
Output Relay can have following function.
NONE TRIP CLOSE
FAIL TRIP FAIL CLOSE FAIL AC
FAIL BATTTERY 27 ELEMENT 59 ELEMENT
25 ELEMENT 81 ELEMENT 79 RESET
79CYCLE 79LOCKOUT SELFCHECK
PROTECTION Enable GROUND Enable SEF Enable
RECLOSE Enable CONTROL Locked REMOTE Enable
ALTERNATE SETTINGS
PROGRAM1 Enable PROGRAM2 Enable
Enable
HOT LINE TAG Enable LO/RE OPEN ALARM
CLOSE - 52A INPUT 1~ 8 GAS LOW*
OPEN - 52B* SYSTEM OK* CLOSE BLOCK*
MECHANISM LOCK* GAS LOW LOCK* EXT’ TRIP LOCK*
HIGH CURRENT
INST FAULT* DELAY FAULT*
LOCKOUT FAULT*
PHASE FAULT* GROUND FAULT* SEF FAULT*
NEQ FAULT*
94 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
ENHANCED TECHNOLOGY 95
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
Sectionalizing Recloser(SEC)
When a fault is occurred from the source side of Sectionalizing Recloser and backup C/B
operates, the line becomes DV and if it continues, it is figured as a permanent fault. Hence,
Sectionalizing Recloser is opened. After Sectionalizing Recloser is opened and TIEpoint
Recloser is closed, the current flows in opposite way. Therefore, the load side of Sectionalizing
Recloser can keep the live line. When Load side of Sectionalizing Recloser has a fault, OCR
Function is operated and the load side is disconnected.
MIDpoint Recloser(MID)
When a fault is occurred in the source side of MIDpoint Recloser and backup C/B or
Sectionalizing Recloser operates, the line becomes DV status and if it continues, it is figured as a
permanent fault, then automatically the setting is changed to Alternate setting. After changed to
Alternate setting, when TIEpoint Recloser is closed, the current flows in opposite way. During
TIEpoint Recloser closed, when a fault occurs, MIDpoint Recloser trips once and lockouts. After
recovering the fault, connect C/B and when the line becomes LV, the setting is automatically
changed to Primary setting and MIDpoint Recloser is closed.
When Load side of MIDpoint Recloser gets a fault, OCR Function is operated and disconnects
the load side.
96 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
ENHANCED TECHNOLOGY 97
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
6.8.1. Setting
PRIMARY SETTING / SYSTEM SETUP / LOOP CONTROL / Type Select
[LOOP CONTROL] Range NONE, SEC, MID, TIE
>Type Select: NONE
>VRS - S/M: VS Default NONE Step ~
>VRS - Tie: VS
Select the Recloser Type and add Loop Control function.
After selecting, press Program 1 Key to enable Loop Control.
NONE : Loop control is not in use.
SEC : SECtionalizing Recloser
MID : MIDpoint Recloser
TIE : TIEpoint Recloser
98 ENHANCED TECHNOLOGY
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
3PN : 3 Phase-Neutral
3PP : 3 Phase-Phase
1PN(A) : Phase A-Neutral
1PN(B) : Phase B-Neutral
1PN(C) : Phase C-Neutral
1PP(AB) : Phase A-Phase B
1PP(BC) : Phase B-Phase C
1PP(CA) : Phase C-Phase A
3PN : 3 Phase-Neutral
3PP : 3 Phase-Phase
1PN(A) : Phase A-Neutral
1PN(B) : Phase B-Neutral
1PN(C) : Phase C-Neutral
1PP(AB) : Phase A-Phase B
1PP(BC) : Phase B-Phase C
1PP(CA) : Phase C-Phase A
ENHANCED TECHNOLOGY 99
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
After TIE closed, source and load sides become dead line for a certain
period, TIE opens by Loop control.
MID, if a voltage selected form “VRS – S/M” becomes dead line, and
when Loop control (“Chg Alt-Tie” is on, it automatically changes to
Alternate Setting. After Loop control, Live Line becomes Tie Close,
and during operation, it figures as a fault and Trip Lockout. After it
becomes Live line, Restore (auto close and change to Primary setting).
Cng Alt-Mid - X ON X ON X -
Cng Alt-Tie - X X ON X X -
LC After Op - - X ENABLE X - -
OT Both DL - X X 10.00 X X -
Step1 : When Permanent Fault occurs at F1, CB1 operates reclosing sequence and then Trip
Lockouts. During CB1 operation, accumulates Dead line time and the accumulated time
becomes “DL Pick T”. When a line is Dead Line, “LL Regain T” operates.
“DL Pick T” is set by summing all reclosing time of back line equipment.
SEC, MID, TIE has the same setting time.
Step2 : “LL Regain T” is set, and if the line is not becoming Live line within a set time,
SEC(RC1), MID(RC2), TIE(RC3) operate.
To operate “LL Regain T” from SEC→MID→TIE in turn, MID shall have longer time set
than SEC, TIE shall have longer time set than MID. When “LL Regain T” is enable,
SEC(RC1) is opened automatically, MID(RC2) changes to Alternate setting.
Step3 : When “LL Regain T” is finished, TIE(RC3) changes to Alternate setting automatically,
and then automatically close. F1 is isolated by Loop control operation, the rest of region
shall be alive by backward distributing line.
Step4 : After removing a Fault, close CB1, then, SEC(RC1) automatically close after Auto-
Restoration Time.
Step5 : Manually open TIE(RC3), change MID(RC2), TIE(RC3) setting to Primary setting.
Enable Loop control of TIE(RC3) to recover the line as previous normal line.
Step1 : When Permanent Fault occurs at F2, SEC(RC1) operate reclosing sequence and tirp
lockout. During SEC(RC1) operation, accumulate Dead line time, and the accumulated
Dead line time becomes “DL Pick T”. When the line is Dead Line, “LL Regain T”
operates.
“DL Pick T” is set by summing all reclosing time of back line equipment.
MID, TIE point recloser has the same setting time.
Step2 : “LL Regain T” is set, and if the line is not becoming Live line within a set time,
MID(RC2), TIE(RC3) operate. To operate “LL Regain T” from MID→TIE in turn, TIE
shall have longer time set than MID.
When “LL Regain T” is enable, MID(RC2) changes to Alternate setting automatically.
Step3 : When “LL Regain T” is finished, TIE(RC3) automatically close after changing to
Alternate setting.
Step4 : When closing TIE(RC3), MID(RC2) trip once and lockout because of F2 fault.
F2 is isolated by Loop control operation, the rest of region shall be alive by backward
distributing line.
Step5 : After removing a Fault, close SEC(RC1), then, MID(RC3) automatically changes to
Alternate setting after Auto Restoration Time.
Step6 : Manually open TIE(RC3) and change to Primary setting.
Enable Loop control of TIE(RC3) to recover the line as previous normal line.
Step1 : When Permanent Fault occurs at F3, MID(RC2) operate reclosing sequence and tirp
lockout. During MID(RC2) operation, accumulate Dead line time, and the accumulated
Dead line time becomes “DL Pick T”. When the line is Dead Line, “LL Regain T”
operates.
“DL Pick T” is set by summing all reclosing time of back line equipment.
Step2 : “LL Regain T” is set, and if the line is not becoming Live line within a set time, TIE(RC3)
operate. When “LL Regain T” is enable, TIE(RC3) changes to Alternate setting
automatically.
Step3 : When closing TIE(RC3), TIE(RC3) trip once and lockout because of F3 fault.
F3 is isolated by Loop control operation, the rest of region shall be alive by backward
distributing line.
Step4 : After removing the fault, close MID(RC3)
Step5 : Manually open TIE(RC3) and change to Primary setting.
Enable Loop control of TIE(RC3), and recover the previous the line as the previous
normal line.
Cng Alt-Mid - X X X -
Cng Alt-Tie - X ON X -
LC After Op - - ENABLE - -
OT Both DL - X 10.00 X -
Step1 : When Permanent Fault occurs at F1, CB1 operates reclosing sequence and then Trip
Lockouts. During CB1 operation, accumulates Dead line time and the accumulated time
becomes “DL Pick T”. When a line is Dead Line, “LL Regain T” operates.
“DL Pick T” is set by summing all reclosing time of back line equipment.
SEC, TIE has the same setting time.
Step2 : “LL Regain T” is set, and if the line is not becoming Live line within a set time,
SEC(RC1), TIE(RC2) operate. To operate “LL Regain T” from SEC→TIE in turn, TIE
shall have longer time set than SEC.
When “LL Regain T” is finished, SEC(RC1) is opened automatically, TIE(RC2)
automatically changes to Alternate setting and close.
F1 is isolated by Loop control operation, the rest of region shall be alive by backward
distributing line.
Step3 : After removing the fault, close CB1, SEC(RC1) is automatically closed after Auto
Restoration Time.
Step4 : Manually open TIE(RC2) and change to Primary setting.
Enable Loop control of TIE(RC2) and recover the line as the previous normal line.
Step1 : When Permanent Fault occurs at F2, SEC(RC1) operates reclosing sequence and then Trip
Lockouts. During SEC(RC1) operation, accumulates Dead line time and the accumulated
time becomes “DL Pick T”. When a line is Dead Line, “LL Regain T” operates.
Step2 : “LL Regain T” is set, and if the line is not becoming Live line within a set time,
TIE(RC2) automatically changes to Alternate setting and close.
When closing TIE(RC2), MID(RC2) trip once and lockouts because of F2.
Step3 : After removing the fault, close SEC(RC1).
Step4 : Manually open TIE(RC2) and change to Primary setting.
Enable Loop control of TIE(RC2) and recover the line as the previous normal line.
If power flow is changed for this set time, setting group is changed.
Applying rules
y This function is operated when Power line system is in normal condition. During fault
detecting(pickup status) or in fault condition, it does not work.
y This function shall be operated when 3 phase voltages are more than 50% of rated voltage
and at least 1 phase has more than 10% of rated current.
7. PROTECTION
Protective Elements Block diagram - ANSI Designations
If the fault is transient, then the reclose logic is reset by the reset logic.
The reclosing element can be disabled in the Primary, Alternate settings by one operating lockout
or by [RECLOSE ENABLED] push button on user interface panel.
7.1.1. Lockout
The lockout state occurs under any of the following conditions :
y After a fault of distribution systems, the RECLOSE ENABLED LED in user interface panel
is not lighted(ON).
y When the high current lockout has occurred.
y The recloser is manually closed and a fault occurs before the expiration of the reset time.
y When recloser is manually opened.
y After TRIP occurs, the fault current is not removed or the recloser’s 52a contacts do not
change status of the recloser opened.
y The close power waiting time delay has expired.
The Lockout State is cleared when the recloser has been manually closed by local/remote control
and the reset time has expired.
The following diagram shows the typical full protection sequence containing 2F2D (two fast and
two delay) operations followed by lockout.
AMP
(1) (2) (3) (4) (5) (6) (7)
FAULT
CURRENT
* LOCK-OUT *
PICKUP
CURRENT
NORMAL
CURRENT
TIME
(1) 1st Trip - 1st TCC (2) 1st Reclose Interval Time
(3) 2nd Trip - 2nd TCC (4) 2nd Reclose Interval Time
(5) 3rd Trip - 3rd TCC (6) 3rd Reclose Interval Time
(7) 4th Trip - 4th TCC
7.1.2. Reset
If the faulted current is cleared before the lockout condition, the reclosing sequence
automatically reset after passing the reset time interval.
If the fault condition occurs again during the reset time, the recloser will operate lockout after the
completion of the remaining sequence.
The following block diagram shows the reset sequence operation after the 3rd reclosing as the
fault current is cleared.
AMP
(1) (2) (3) (4) (5)
FAULT
CURRENT
AUTO RESET
TIME
* RESET *
PICKUP
CURRENT
NOMAL
CURRENT
TIME
(1) 1st Trip - 1st TCC (2) 1st Reclose Interval Time
(3) 2nd Trip - 2nd TCC (4) 2nd Reclose Interval Time
(5) 3rd Trip - 3rd TCC
Figure 7-3. Reset Sequence operation after the 3rd reclosing as the fault current is cleared
Multiple time curves and time dials are available for the phase time overcurrent element to
respectively coordinate with other protection elements in the EVRC2A and other external
devices on the distribution system. ANSI, IEC, ESB, USER and non-standard time current
curves are included in the EVRC2A.
A User Programmable curve option is also available for user to allow creating custom’s time
current curves for more enhanced coordination than the standard curve types.
The Reset type can be either instantaneous or linear. The phase time delay reset mode applies to
the ANSI, IEC, ESB, USER curves. The instantaneous mode is used to coordinate with other
instantaneous reset devices such as a recloser or other protective equipment on the distribution
system. In the instantaneous mode, the time overcurrent element will reset instantaneously when
the measured current level drops below the pickup setting for one cycle.
If the recloser is closed by pressing the CLOSE button on the front panel, or by an remote
control or via SCADA, the phase time overcurrent element is prevented from tripping for a
period specified by the Cold load pickup scheme.
Multiple time curves and time dials are available for the ground time overcurrent element to
closely coordinate with other protection elements within the EVRC2A and other external devices
on the distribution system. ANSI, IEC, ESB, USER and non-standard time current curves are
included in the EVRC2A.
A User Programmable curve option is also available allowing the user to create customer time
current curves for more enhanced coordination than the standard curve types.
The Reset type can be either instantaneous or linear. The ground time delay reset mode applies to
the ANSI, IEC, ESB, USER curves. The instantaneous mode is used to coordinate with other
instantaneous reset devices such as a recloser or other protective equipment on the distribution
system. In the instantaneous mode the time overcurrent element will reset instantaneously when
the current level measured by the EVRC2A drops below the pickup setting for one cycle.
If the recloser is closed by pressing the CLOSE button on the front panel, or by an remote
control or via SCADA, the ground time overcurrent element is prevented from tripping for a
period specified by the Cold load pickup scheme.
Selects the relays required to operate when the feature generates a Trip.
For user systems, a directional SEF is available. The directional control is polarized by a zero
sequence voltage(V0). The VD or PTs should be connected Wye-grounded.
NOTE : For the products that are dispatched with ZCT installed, the
setting range of this item is “OFF, 0.1~16.0 (0.1A Step)”. It
is possible to check whether the product is dispatched with
ZCT installed by checking “MAIN MENU/ STATUS/
CONTROL TYPE” menu. Refer to “9.4. Control Type”.
Selects the relays required to operate when the feature generates a Trip.
If the recloser is closed by pressing the CLOSE button on the front panel, or by an remote
control or via SCADA, the negative sequence time overcurrent element is prevented from
tripping for a period specified by the Cold load pickup scheme.
Selects the relays required to operate when the feature generates a Trip.
PRIMARY SETTING / PROTECTION / NEG SEQ FAST / Low Set Definite Time
[NEG SEQ FAST] Range OFF, 1 ~ 600sec
>M.R.T: 0.00
>Reset Method: INST Default OFF Step 1sec
>Low Set DT: OFF
Low set definite time is used to restrict a trip time to be a definite time
adjacent to a pickup current by T-C curve. When the trip time is greater
than the low set definite time, low set definite time is applied for
operation.
The phase high current trip element in the following five settings should be enabled for phase
high current trip.
Selects the required relays to operate when the feature generates a Trip.
Selects the required relays to operate when the feature generates a Trip.
The ground high current trip element in the following five settings should be enabled for
negative sequence high current trip.
When high current lockout element is enabled, high current lockout element is operated prior to
any other phase protection elements. If a fault current is higher than the pickup setting value,
Lockout is operated.
The phase high current lockout element can be set by a number of its active trip that is applied to
the full operation to lockout, time delay and fault current.
This function is very useful to prevent widespread line faults due to reclosing operations in case
of permanent fault.
The operating time of phase high current lockout element should be set for equal to or faster than
and phase high current trip element. The phase high current lockout element is enabled in the
Primary, Alternate setting and [PROTECTION ENABLED] in user interface panel.
The phase high current lockout element is not affected by the cold load pickup scheme.
The phase high current lockout element in the following five setting should be enabled for phase
high current trip.
Selects the required relays to operate when the feature generates a Trip.
The ground high current lockout element in the following five settings should be enabled for
ground high current lockout.
Selects the required relays to operate when the feature generates a Trip.
The negative sequence high current lockout element in the following five settings should be
enabled for the negative sequence high current lockout.
Selects the required relays to operate when the feature generates a Trip.
In the state of the function to restrain the inrush current activated, the overcurrent protection
element will be operated under settings of “CLPU-Type 1” function at the restoration of load
supply.
NOTE:
According to setting of “Make use ‘I’”, the condition to decide the restoration of load supply will
be changed. If “YES” is set, the decision is made when the load current becomes over 2A. If
“NO” is set, the decision is made when a recloser is closed (52A) by local or remote control.
When a distributed system is closed after long-time outage, the inrush current over overcurrent
pickup level may occur. At occurrence of the cold load pickup, EVRC2A increases the pickup
level of overcurrent element during a certain period of time, the Fast overcurrent protection
element is not operated and the Delay overcurrent protection element is always operated
regardless of the cold load pickup function. (The High Current Trip and High Current Lockout
are always operated regardless of the cold load pickup function)
If a fault occurs on distributed system, an overcurrent protection element is operated by the cold
load pickup function and a recloser becomes lockout after oneshot trip regardless of total number
of shots.
A power is lost and then after certain outage time, the algorithm of cold load pickup function is
applied at the restoration of load supply. If the “Make use ‘1’” is set to be “YES”, the algorithm
is applied when a load current becomes 0 and then it is restored after certain outage time. If “NO”
is set, the algorithm is applied when a recloser is opened and then after certain outage time, the
recloser is closed manually. If the fault current over the cold load pickup level occurs, the
protection element by the cold load pickup function is operated immediately.
If the power loss (opening or load current loss) is sustained for a long time more than certain
outage time, the pickup current of time overcurrent element is changed to be the setting value of
the cold load pickup current. After the restoration of load supply (manually closing or restoration
of load current), protection functions are normally operated when the Restore minimum time
(RMT) is expired.
Delay Curve
Current
Overcurrent Cold load
Pickup Level Pickup Level
The cold load pickup function is operated according to the following rules.
The setting to use the cold load pickup function is set to be ON (set to TRIP or TR&AR), the
cold load pickup level is preset and then the cold load pickup function is activated at manual
close or restoration of load current.
If the level of over current occurring at the restoration of load supply is over the cold load
pickup current, the Lockout is done by protection function after oneshot trip (Refer the Inrush
Current 1 in “Figure 7-5. The Restore Minimum Time Characteristic”).
If the over current is below cold load pickup current and overcurrent pickup current, protection
functions are not operated during a period of Restore minimum Time (RMT), (Refer the Inrush
Current 2 in “Figure 7-5. The Restore Minimum Time Characteristic”). After RMT, the
protection functions are operated. However, if the over current is dropped below overcurrent
pickup current during the RMT, the cold load pickup function is reset after reset time (Refer the
Inrush Current 3 in “Figure 7-5. The Restore Minimum Time Characteristic”).
Current
Inrush current 1
CLPU Trip
Pickup Level
Inrush current 2
Trip
Overcurrent
Pickup Level
Inrush current 3
Time
If high current trip and high current lockout functions are activated and the fault current is higher
than the current setting of High current trip and high current lockout, the high current trip and
high current lockout functions will be operated prior to the cold load pickup function.
As example, when E-CLP Multi and E-CLT Time are set to be 3.0 and 60min respectively, over
30 min after power loss, the applied cold load multiple is 2. If the minimum working currentis
set to be 200A, the current of Over Current Pickup becomes 400A, twice as much as the
minimum working current. In addition, after 60 min, the cold load multiple is fixed to be 3.
When E-CLP Multi and E-CLP Time are set to be 3.0 and 60 min respectively, the graph of the
cold load multiple in “Figure 7-6. Cold Load Multipilier” is shown as follows.
NOTE:
The risen level of overcurrent pickup by multiple of cold load is the pickup level to operate
overcurrent protection element. The standard current level of TC curve is a minimum working
current.
Selects the relays required to operate when the feature generates a Trip.
PRIMARY SETTING / PROTECTION / COLD LOAD PICKUP / CLPU-COMMON/ Make use ‘I’
[CLPU-COMMON] Range NO,YES
Function: TRIP
Relays(0-8): OFF Default NO Step ~
>Make use ‘I’: NO
This setting changes the point of time to activate a cold load pickup
function.
If “YES” is set, the cold load pickup function is activated when a load
current is restored (over 2A).
If “NO” is set, the cold load pickup function is activated when a
recloser is manually closed by local or remote control.
CLPU-TYPE1 Setup
This setting is to restrain the inrush current occurring at restoration of load supply.
NOTE : For the products that are dispatched with ZCT installed, the
setting range of this item is “0.4~200.0A (0.1A Step)”. It is
possible to check whether the product is dispatched with
ZCT installed by checking “MAIN MENU/ STATUS/
CONTROL TYPE” menu. Refer to “9.4. Control Type”.
※. NOTE : RMT Func-GND, RMT Func-SEF and RMT Func-NEG, the same as RMT Func-
PHA above.
CLPU-TYPE2 Setup
This setup is to rise or drop the current for Over Current Pickup of a protection element
If directional controls are selected, it will determine whether current flow in each phase is in
forward or reverse direction, as determined by the connection of the phase CTs, selected
Maximum Torque Angle (MTA), voltage and current phasors. To increase security of all
directional controls, add one power frequency cycle of intentional delay to prevent incorrect
operation.
The directional controls have each three settings. The directional controls settings can be
different in the Primary and Alternate settings.
NOTE : In case of VD(CVD or RVD) type Recloser, EVRC2A only measures voltages
without checking directional elements.
The phase direction control can be programmed for non-direction or to provide a trip for current
flow in the forward or reverse direction only.
Following diagram shows the phasor diagram for I1 directional polarization in the complex plane.
Polarizing Referance
Voltage:
V1
Ze
ro
T
e
orq
Lin
ue
ue
o rq
I1 T
Lin
um
im
e
M ax
ard
rw
Fo
rse
ve
Re
The phase direction control in the following four settings should be enabled.
NOTE )
EVRC2A version prior to 5.1 this setting is applied conversely.
For example, “NO” indicates that directional elements will be
blocked by M.P.V. “YES” indicates that directional elements will
be operated regardless of M.P.V.
The ground direction control can be programmed to either non-direction or provide a trip for
current flow in the forward or reverse direction only.
The following diagram shows the phasor diagram for Ig directional polarization in the complex
plane.
-V0
ne
Li
ue
Fault Current
rq
Ze
To
Ig
ro
um
To
im
rq
ax
ue
M
Li
ne
d
ar
rw
Fo
e
rs
ve
Re
Polarizing Referance
V0
Voltage:
The ground direction control in the following four settings should be enabled.
NOTE )
EVRC2A version prior to 5.1 this setting is applied conversely.
For example, “NO” indicates that directional elements will be
blocked by M.P.V. “YES” indicates that directional elements will
be operated regardless of M.P.V.
The negative sequence direction control can be programmed for non-direction or to provide a trip
for current flow in the forward or reverse direction only.
The following diagram shows the phasor diagram for I2 directional polarization in the complex
plane.
-V2
ne
Li
ue
Fault Current
rq
Ze
To
ro I2
um
To
im
rq
ax
ue
M
Li
ne
d
ar
rw
Fo
e
rs
ve
Re
Polarizing Referance
Voltage:
V2
The negative sequence directional controls in the following four settings should be enabled.
NOTE )
EVRC2A version prior to 5.1 this setting is applied conversely.
For example, “NO” indicates that directional elements will be
blocked by M.P.V. “YES” indicates that directional elements will
be operated regardless of M.P.V.
Undervoltage 1 Setup
The undervoltage 1 should be enabled to the following settings.
Selects the relays required to operate when the feature generates a Trip.
Undervoltage 2 Setup
The undervoltage 2 settings process a very similar method to the undervoltage 1.
Overvoltage 1 Setup
The overvoltage 1 should be enabled to the following settings.
Selects the relays required to operate when the feature generates a Trip.
Overvoltage 2 Setup
The overvoltage 2 settings process a very similar method to the overvoltage 1.
7.16. Frequency(81)
EVRC2A has underfrequency and overfrequency elements to detect unusual frequency in power
system. Explanation for each element is below.
Underfrequency (81U)
Underfrequency element is provided for trip, alarm and control when the frequency drops below
a specified frequency setting for a specified time delay.
The underfrequency element can be ON or OFF in the Primary, Alternate settings.
The power system frequency is measured from the zero crossing on the VA-N voltage input for
Wye connected VTs and VA-B voltage for Delta connected VTs.
The underfrequency minimum voltage and underfrequency minimum current are used to prevent
incorrect operation when the recloser is closed by a local/remote control and the underfrequency
is disabled from tripping for cold load pickup during periods.
Overfrequency (81O)
Overfrequency element is provided for trip, alarm and control when the frequency rises above a
specified frequency setting for a specified time delay.
The overfrequency element can be ON or OFF in the Primary, Alternate settings.
The power system frequency is measured from the zero crossing on the VA-N voltage input for
Wye connected VTs and VA-B voltage for Delta connected VTs.
The overfrequency minimum voltage and overfrequency minimum current are used to prevent
incorrect operation when the recloser is closed by a local/remote control and the overfrequency is
disabled from tripping for cold load pickup during periods.
Frequency Setup
The underfrequency and overfrequency element should be enabled to the following settings.
Selects the relays required to operate when the feature generates a Trip.
1) The same characteristics of fast and delay operations in the total number of the trip
operations and identical basic Time Current Curves should be set for all Reclosers connected
in series.
2) The identical reclose interval time should be set for all Reclosers in series.
3) To coordinate the protection characteristics, an additional delay operation time (at least 100
ms) should be applied to the Time Current Curve characteristics of Back-up Recloser, not to
those of Down-line Reclosers.
4) The reset time of Back-up Recloser should be set longer than any reclose interval time of all
Down-line Reclosers. This setting will prevent the reset operation of Back-up Recloser
during the reclose operation of Down-lines.
Starting
Reset Time
Counter
Close
Close
Down line EVR 2
Lockout Status
Open
Time
Faulted
ANSI/IEEE
Trip Time(Sec) = TD × ( (α / (Mβ-1) + γ) + TA)
IEC
Trip Time(Sec) = TD × ( (α / (Mβ-1)) + TA)
ESB
Trip Time(Sec) = TD × ( (α / (Mβ-1) + γ) + TA)
USER-DEFINED
Trip Time(Sec) = TD × ( (α / (Mβ-1) + γ) + TA)
Reset Time(Sec) = TD × (Rt / (1-M2))
NOTE )
1) “Time Dial” and “Time Adder” settings of each Time Overcurrent(Fast/Delay) menu are
applied to Time dial(TD) and Time adder(TA) respectively.
2) “Recloser clearing time curves” are used when rated voltage of recloser is 15㎸ or 27㎸,
otherwise which added 30㎳(±4㎳) are used when it is 38㎸.
1) USER CURVE 1
PRIMARY SETTING / PROTECTION / USER CURVE SET / USER CURVE 1 / Factor a
[USER CURVE 1] Range 0.0000 ~ 150.9999
>Factor a: 59.5000
Factor b: 2.0000 Default 59.5000 Step 0.0001
Factor r: 1.8000
2) USER CURVE 2, 3, 4 :
USER CURVE 2 ~ 4, the same as USER CURVE 1 above
100
200
300
400
500
600
700
800
900
10k
1k
3k
4k
5k
6k
7k
8k
9k
2k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : ANSI MODERATELY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
40
VARIATIONS ±5% OR 0.01 SECONDS 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
15.00
13.00
2 2
11.00
TIME(SECONDS)
9.00
7.00
1 1
0.9 0.9
0.8
5.00 0.8
0.7 4.00 0.7
0.6 0.6
0.5 3.00 0.5
0.4 0.4
2.00
0.3 0.3
0.2 0.2
1.00
0.1 0.1
0.09 0.09
0.08
0.05 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
7k
9k
6k
8k
10k
100
200
300
400
500
600
700
800
900
100
200
300
400
500
600
700
800
900
10k
1k
3k
4k
5k
6k
7k
8k
9k
2k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : ANSI NORMALLY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
15.00
13.00
2 11.00 2
9.00
TIME(SECONDS)
7.00
1 1
0.9 5.00 0.9
0.8 0.8
0.7 4.00 0.7
0.6 0.6
3.00
0.5 0.5
0.4 0.4
2.00
0.3 0.3
0.2 0.2
1.00
0.1 0.1
0.09 0.50 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
7k
9k
10k
100
200
300
400
500
600
700
800
900
6k
8k
100
200
300
400
500
600
700
800
900
10k
1k
3k
4k
5k
6k
7k
8k
9k
2k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : ANSI VERY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
40
VARIATIONS ±5% OR 0.01 SECONDS 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
15.00
13.00
1
11.00 1
0.9 9.00 0.9
0.8 0.8
0.7 7.00 0.7
0.6 0.6
0.5 5.00 0.5
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
7k
9k
10k
100
200
300
400
500
600
700
800
900
6k
8k
100
200
300
400
500
600
700
800
900
10k
1k
3k
4k
5k
6k
7k
8k
9k
2k
100 100
90 90
80 80
70 70
RECLOSER CLEARING TIME CURVE
60 60
: ANSI EXTREMELY INVERSE
50 50
CURVES ARE AVERAGE CLEARING TIME
40 VARIATIONS ± 5% OR 0.01 SECONDS 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 15.00 0.6
0.5 13.00 0.5
11.00
0.4 0.4
9.00
0.3 0.3
7.00
4.00
3.00
0.1 0.1
0.09 0.09
0.08 2.00 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.03 0.03
0.01 0.01
1k
2k
3k
4k
5k
7k
9k
10k
100
200
300
400
500
600
700
800
900
6k
8k
100
200
300
400
500
600
700
800
900
10k
6k
7k
8k
9k
1k
2k
3k
4k
5k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : ANSI SHORT TIME INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
1 15.00 1
0.9 13.00 0.9
0.8 0.8
0.7 11.00 0.7
0.6 9.00 0.6
0.5 7.00 0.5
0.4 0.4
5.00
0.3 0.3
4.00
2.00
0.1 0.1
0.09 0.09
0.08 0.08
0.07 1.00 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.50
0.03 0.03
0.02 0.02
0.01 0.01
1k
3k
4k
5k
10k
100
200
300
400
500
600
700
800
900
2k
6k
7k
8k
9k
100
200
300
400
500
600
700
800
900
10k
1k
3k
4k
5k
6k
7k
8k
9k
2k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : ANSI SHOTR TIME VERY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
1 1
0.9 0.9
0.8 0.8
0.7 15.00 0.7
0.6 13.00 0.6
11.00
0.5 0.5
9.00
0.4 0.4
7.00
0.3 0.3
5.00
0.2 4.00 0.2
3.00
0.04 0.04
0.03 0.03
0.50
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
7k
9k
10k
100
200
300
400
500
600
700
800
900
6k
8k
100
200
300
400
500
600
700
800
900
10k
1k
3k
4k
5k
6k
7k
8k
9k
2k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : IEC STANDARD INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 1 2
TIME(SECONDS)
0.8
0.7
0.6
1 0.5 1
0.9 0.9
0.8 0.4 0.8
0.7 0.7
0.6 0.3 0.6
0.5 0.5
0.3 0.3
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
7k
9k
10k
100
200
300
400
500
600
700
800
900
6k
8k
100
200
300
500
600
700
800
400
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : IEC VERY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
40
VARIATIONS ± 5% OR 0.01 SECONDS 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
1.00
0.4 0.4
0.8
0.3 0.7 0.3
0.6
0.5
0.2 0.2
0.4
0.3
0.1 0.1
0.09 0.2 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.1
0.04 0.04
0.03 0.03
0.05
0.02 0.02
0.01 0.01
4k
6k
7k
9k
1k
2k
3k
5k
8k
100
200
300
400
500
600
700
800
900
10k
100
200
300
400
500
600
700
800
900
10k
1k
3k
4k
5k
6k
7k
8k
9k
2k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : IEC EXTREMELY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
0.1 0.1
0.09 0.09
0.08
1.00 0.08
0.07 0.8 0.07
0.06 0.7 0.06
0.05 0.6 0.05
0.3
0.02 0.02
0.2
0.1
0.05
0.01 0.01
1k
2k
3k
4k
5k
7k
9k
10k
100
200
300
400
500
600
700
800
900
6k
8k
100
200
300
400
500
600
700
800
900
10k
1k
3k
4k
5k
6k
7k
8k
9k
2k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : IEC LONG TIME VERY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
1.00
4 4
0.8
3 0. 7 3
0. 6
0. 5
2 2
0. 4
TIME(SECONDS)
0. 3
1 1
0.9 0.2 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.1
0.4 0.4
0.3 0.3
0.05
0.2 0.2
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
7k
9k
10k
100
200
300
400
500
600
700
800
900
6k
8k
100
300
200
400
500
600
700
800
900
10k
1k
3k
8k
9k
2k
4k
5k
6k
7k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : IEC SHORT TIME INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
40
VARIATIONS ± 5% OR 0.01 SECONDS 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
1.00
0.3 0.3
0.8
0.7
0.2 0.6 0.2
0.5
0.4
0.04 0.04
0.1
0.03 0.03
0.02 0.02
0.05
0.01 0.01
4k
200
400
500
600
700
1k
2k
3k
5k
6k
7k
8k
9k
10k
100
300
800
900
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : ESB INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
40
VARIATIONS ± 5% OR 0.01 SECONDS 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 15.00 3
13.00
2
11.00 2
9.00
TIME(SECONDS)
7.00
1 5.00 1
0.9 0.9
0.8 4.00 0.8
0.7 0.7
0.6 3.00 0.6
0.5 0.5
0.3 0.3
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
100
200
300
400
500
600
700
800
900
10k
100
200
300
400
500
600
700
800
900
10k
1k
3k
4k
5k
6k
7k
8k
9k
2k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : ESB VERY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
40
VARIATIONS ±5% 0.01 SECONDS 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
15.00
TIME(SECONDS)
13.00
11.00
1 9.00 1
0.9 0.9
0.8 7.00 0.8
0.7 0.7
0.6 0.6
5.00
0.5 0.5
4.00
0.4 0.4
3.00
0.3 0.3
2.00
0.2 0.2
1.00
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
7k
9k
10k
100
200
300
400
500
600
700
800
900
6k
8k
100
200
300
400
500
600
700
800
900
10k
1k
3k
4k
5k
6k
7k
8k
9k
2k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : ESB LONG TIME VERY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 15.00 7
6 6
13.00
5 11.00 5
4 9.00 4
3 7.00 3
5.00
2 2
4.00
TIME(SECONDS)
3.00
1 1
0.9 2.00 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
1.00
0.4 0.4
0.3 0.3
0.50
0.2 0.2
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
7k
9k
10k
100
200
300
400
500
600
700
800
900
6k
8k
100
300
200
400
500
600
700
800
900
10k
1k
3k
8k
9k
2k
4k
5k
6k
7k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : D1, D2 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 D2 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
1 D1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
4k
200
400
500
600
700
1k
2k
3k
5k
6k
7k
8k
9k
10k
100
300
800
900
100
200
300
400
500
600
700
800
900
10k
1k
3k
4k
5k
6k
7k
8k
9k
2k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : A, B, C, D, E 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
0.1 0.1
0.09 C 0.09
0.08 0.08
0.07 0.07
B
0.06 D E 0.06
0.05 0.05
A
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
7k
9k
10k
100
200
300
400
500
600
700
800
900
6k
8k
100
200
300
400
500
600
700
800
900
10k
8k
1k
2k
3k
4k
5k
6k
7k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : KP, L, M, N 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
KP
0.1 0.1
0.09 L 0.09
0.08 M 0.08
0.07 0.07
N
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
10k
100
200
300
400
500
600
700
800
900
1k
2k
3k
4k
5k
6k
7k
8k
9k
100
200
300
400
500
600
700
800
900
10k
1k
3k
8k
9k
2k
4k
5k
6k
7k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : P, R, T, V 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
V
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
0.1
T 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 R 0.06
0.05 P 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
2k
4k
5k
6k
7k
100
200
300
400
500
600
700
800
900
1k
3k
8k
9k
10k
100
300
200
400
500
600
700
800
900
10k
1k
3k
8k
9k
2k
4k
5k
6k
7k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : W, Y, Z 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
Z
0.4 0.4
0.3 0.3
W
0.2 0.2
Y
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
4k
200
400
500
600
700
1k
2k
3k
5k
6k
7k
8k
9k
10k
100
300
800
900
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
6k
7k
8k
9k
5k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : 1, 2, 3, 4, 5 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
1 1
0.9 3 0.9
0.8 0.8
0.7 0.7
0.6 0.6
2
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
0.1 0.1
0.09 0.09
0.08 0.08
0.07 4 0.07
0.06 1 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
7k
9k
10k
100
200
300
400
500
600
700
800
900
6k
8k
100
200
300
500
600
700
800
400
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 60
: 6, 7, 8, 8*, 9
50 CURVES ARE AVERAGE CLEARING TIME 50
30 7 30
20 20
10 10
9 9
8 8
7 7
6 6
5 9 5
4 4
3 3
2 2
TIME(SECONDS)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
8
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 8* 0.05
6
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
6k
7k
10k
100
200
300
400
500
600
700
800
900
1k
2k
3k
4k
5k
8k
9k
22) Non
N Standardd Curves (11,, 13, 14, 15, 16, 17, 18)
Figure 7-333. Non Standdard Curvess (11, 13, 14, 15, 16, 17, 118)
ENHA
ANCED TEC
CHNOLOGY
Y 205
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
100
200
300
400
500
600
700
800
900
10k
1k
3k
4k
5k
6k
7k
8k
9k
2k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : F, H, J, KG 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
TIME(SECONDS)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
F J
0.1 KG 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
H
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
7k
9k
10k
100
200
300
400
500
600
700
800
900
6k
8k
The loss of phase element in the following four settings should be enabled for loss of phase.
Selects the required relays to operate when the feature generates a Trip.
8. MONITORING
EVRC2A has Monitoring function for following items and also has functions for user to output
Alarm signal or Trip signal.
y DEMAND
y SYNCHRO CHECK
y TRIP COUNTER
y RECLOSER WEAR
y BATTERY TEST
y FAULT LOCATOR
y GAS LOW LOCK – Option
y EXT’ TRIP & LOCK – Option
y LIVE LOAD BLOCK – Option
8.1. Demand
8.1.1. Description
EVRC2A is programmed to monitor following items to be operated as user sets.
y Phase Current demand value
y Ground current demand value
y Negative sequence current demand value
When either or both of the synchronism check voltages are de-energized, the synchronism check
can allow for local/remote close.
If EVRC2A is the type of VD, the synchronism check voltage input VL is connected to load
side(VR phase) in recloser. The other synchronizing phase can be connected for phase-neutral
voltage Vr, Vs or Vt; for phase-phase voltages Vab or Vcb. on load side in recloser.
2) Pickup Setting
PRIMARY SETTING / MONITORING / RECLOSER WARE / Pickup(%)
[RECLOSER WEAR] Range 0.0 ~ 50.0 %
Function: ALARM
>Pickup(%): 20.0 Default 20.0 Step 0.1 %
Rated Volt(kV): 15
mZ (1-m)Z
IA
IF L
O
VA
RF A
D
The calculated “Fault Location” can be checked on the “FAULT CYCLE” event menu. For more
details, refer to “12.1. Waveform Capture”.
9. STATUS
This menu shows the current status of EVRC2A like below
y OPTO INPUTS
y RELAY OUTPUTS
y CLOCK
y CONTROL TYPE
9.3. Clock
Move to “MAIN MENU / STATUS / CLOCK” to see current time.
The “CLOCK” menu screen can vary according to the EVRC2A version.
STATUS / CLOCK
Check current time
[CURRENT TIME]
2009/11/05 21:02:38
STATUS / CLOCK
Check current time
[CURRENT TIME]
ⓐ Indicates the local time type’s present time.
L2009/01/01 09:00:00
G2009/01/01 00:00:00 ⓑ Indicates the GMT time type’s present time.
[CURRENT TIME]
L ⓐ
G ⓑ
[CONTROL TYPE]
If the letter located at `ⓐ’ is `X’ then it is a product that was
10. METERING
The following values are contained in the metering elements of EVRC2A.
y Current
y Voltage(Source Side, Load Side)
y Frequency
y Synchronism Voltage
y Power
y Energy
y Demand
y System
y Harmonics
y Unbalance
Display measured values of current and current phase per phase. Use [▲] [▼] button to check
metering information of current.
Display measured values of voltage and voltage phase. Use [▲] [▼] button to check metering
information of voltage.
10.1.3. Frequency
The following values are contained in the frequency metering.
y Frequency(㎐)
y Frequency decay rate(㎐/Sec)
[SYNCHRO DELTA]
A: 0.09 kV 0.0 Deg
B:15.59 kV 59.9 Deg
C:15.59 kV 359.9 Deg
[SYNCHRO DELTA]
50.00 Hz
10.1.5. Power
The following values are contained in the power metering.
y Real power(MW)
y Reactive power(Mvar)
y Apparent power(MVA)
y Power factor(%)
[POWER FACTOR]
Pa: 0.0
Pb: 0.0 P3: 0.0
Pc: 0.0
Display measured values of power and power factor per phase. Use [▲] [▼] button to check
metering information of power.
10.1.6. Energy
The following values are contained in the energy metering.
y Positive watthour(MWh) & start date (Year/Month/Date Hour:Minute,Second)
y Negative watthour(MWh) & start date (Year/Month/Date Hour:Minute,Second)
y Positive varhour(Mvar) & start date (Year/Month/Date Hour:Minute,Second)
y negative varhour(Mvar) & start date (Year/Month/Date Hour:Minute,Second)
The updated rate of the energy meters is based on the “Time Constant” setting “MAIN MENU /
SETTING / MONITORING / DEMAND” The meters will update every 1/15 of the Demand
Constant. For example : if the Demand Constant is set to 15 minutes, the energy meters will
update every 1 minute (15min × 1/15 = 1 min)
The watt-hour and VAR-hour meters can be reset to 0 through “PRIMARY SETTING / RELAY
SETUP / CLEAR SAVED DATA / ENERGY”. The “SD(start date)” on LCD indicates the
time when the watt-hour and VAR-hour meters are reset.
[NEGATIVE V/H(MVar)]
Pa: 0 Pb: 0
Pa: 0 Pb: 0
SD:09/12/31 00:00:00
10.1.7. Demand
The following values are contained in the demand metering.
Actual demand & maximum demand with Value (Current, Real power, Reactive power) and Date
(Year/Month/Date Hour:Minute,Second)
During each demand value, the EVRC2A also captures and stores maximum values for the
measurements listed below. It functions as a standard maximum meter. When a new maximum
value is determined, the old value is replaced. A time stamp in the following format (Date:
Year/Month/Day and Time: Hour:Minute,Second), is placed with the latest maximum values.
The Max demand meters can be reset to 0 through “PRIMARY SETTING / RELAY SETUP /
CLEAR SAVED DATA / MAX DEMAND”
[P-A REACTIVE POWER] [3P REAL POWER (MW)] [PHASE C REAL POWER]
DEMAND: 0.00 MWar DEMAND: 0.00 MW DEMAND: 0.00 MW
MAX : 0.00 MWar MAX : 0.00 MW MAX : 0.00 MW
10/01/01 00:00:00 10/01/01 00:00:00 10/01/01 00:00:00
10.1.8. System
The following values are contained in the system metering.
y Board power(±12, +5V)
y Temperature(℃)
y Battery voltage(V)
y Gas pressure(Bar)
NOTE : According to recloser type, there may be no gas pressure measurement.
10.1.9. Unbalance
The following values are contained in the unbalance metering.
y Voltage unbalance(V2/V1) – Source Side
y Voltage unbalance(V2/V1) – Load Side
y Current unbalance(I2/I1)
10.1.10. Harmonics
The following values are contained in harmonics metering.
y 1st~7th Harmonic of Current
y 1st~7th Harmonic of Voltage
y THD of Current
y THD of Voltage
THD
You can confirm in “MAIN NEMU / METERING / HARMONICS / THD”.
MAIN MENU / METERING / HARMONICS / THD
[Total Har’ Dis’(%)] This menu is to display the total harmonic distortion of current and
>Ia : 0 Va : 0
>Ib : 0 Vb : 0 voltage.
>Ic : 0 Vc : 0
Current-A
You can confirm in “MAIN NEMU / METERING / HARMONICS / Current-A”.
MAIN MENU / METERING / HARMONICS / Current-A
This menu is to display the 1st~7th harmonic of current through phase
A.
Current-B(C)
The same Menu as “Current-A” function.
You can confirm in “MAIN NEMU / METERING / HARMONICS / Current-B(C)”.
Voltage-A
You can confirm in “MAIN NEMU / METERING / HARMONICS / Voltage-A”.
MAIN MENU / METERING / HARMONICS / Current-A
This menu is to display the 1st~7th harmonic and THD of voltage in
phase A.
Voltage -B(C)
The same Menu as “Voltage-A” function.
You can confirm in “MAIN NEMU / METERING / HARMONICS / Voltage-B(C)”.
10.2. Accuracy
The harmonic components of current and voltage are removed from the input voltage and current
parameters, so all measurements based on these quantities respond to the fundamental
components only.
Phase A, B, C
POWER FACTOR Rate ±0.02 –1.000 to 1.000
3Φ Phase
Phase A, B, C
3ΦREAL POWER MW ±2% –32.000 to 32.000
3Φ Phase
3ΦREACTIVE Phase A, B, C
MVar ±2% –32.000 to 32.000
POWER 3Φ Phase
3ΦAPPARENT Phase A, B, C
MVA ±2% –32.000 to 32.000
POWER 3Φ Phase
Phase A, B, C
WATT-HOURS MWH ±2% –32000 to 32000
3Φ Phase
Phase A, B, C
VAR-HOURS MVarH ±2% –32000 to 32000
3Φ Phase
If the VT connection type is set to delta, all single phase voltage quantities are displayed as zero.
11. MAINTENANCE
EVRC2A has maintenance function for following items.
y COUNTERS
y WEAR MONITOR
y OUTPUT RELAY TEST
y POWER QUALITY - Option
11.1. Counters
EVRC2A records counter related with system operation. The recorded counter items are below.
In order to check counter information, go to “MAINTENANCE / COUNTERS”. For more detail
information, refer to “8.3.1. Trip Counter Explanation”.
y Trip
y Fault
y System Restart
Press [FUN] button at ② and then ③ is shown. The output signal has
② been “asserted” for 2 sec. If the test is completed, the message, “END
[OUTPUT RELAY TEST] TESTING”, is shown and then back to the previous menu.
SELECT RELAY :RLY 1
Press <FUN> : Start
Press <ESC> : Cancel
If the [ESC] button is press at ②, ④ is shown and the output test is
③ canceled.
[OUTPUT RELAY TEST]
SELECT RELAY :RLY 1
Press <FUN> : Start
TESTING
④
[OUTPUT RELAY TEST]
SELECT RELAY :RLY 1
Press <FUN> : Start
TEST Canceled
[PQ COUNT] UNBALANCE NOTE : The number of times and the hour do not increase
SOURCE-VOLT : ⑪
LOAD-VOLT : ⑫ during the outage if the power of EVRC2A is off. The
CURRENT : ⑬
number of times and the hour of outage will be recorded
[PQ COUNT] UNBALANCE by the end of outage.
SOURCE-VOLT : 000
LOAD-VOLT : 000
CURRENT : 000
NOTE : These counter for unbalance are supported from version
6.12 of EVRC2A-N6,NT.
⑤ Fault Location
Indicated when “Fault Locater” function is ON.
For more details about settings of “Fault Locater” function, refer to
“8.6. Fault Locator”.
③
REAC POW(Mvar)[0001]
A : 0 B : 0
C : 0 3P: 0
10/01/22 21:45:00
④
PF&ENERGY-3P [0001]
P-F(%) : 0.0
MWh: 0.0 MVh: 0.0
10/01/22 21:45:00
[001/1] ABCG
IS: 0
IQ: 0
10/01/01 00:00:00
Power Quality event can be viewed at “MAIN MENU / EVENT RECORDER / POWER
QUALITY”
MAIN MENU / EVENT RECORDER / POWER QUALITY
① Displays the order of the event occurrence and events from the
most recent event to the oldest event.
Total 512 events can be stored.
[NO-001] OUTAGE-S ② Displays the event type and detect value.
OT: 0000 h 00 m 00 s
DATE : 10/01/01 - OUTAGE-S : power supply side outage
TIME : 00:00:00:000
- OUTAGE-L : load side outage
[NO-①] ② - SAG-A(B,C) : A(B,C) phase sag.
OT: ③
DATE : ④ - SWL-A(B,C) : A(B,C) phase swell.
TIME : ⑤
- UBL-SV : Voltage Unbalance on source side
- UBL-LV : Voltage Unbalance on load side
- UBC : Current Unbalance
③ Displays the duration of outage as in hour/ minute/second and
cycle message added after duration.
④ Displays the time of outage, sag, swell or unbalance detected.
13. INSTALLATION
13.1. User Interface Door and Power Switch
Outer Cover
It is for blocking the direct ray of light to delay raising temperature inside of Control Cubicle.
The gap between control cubicle and cover is 10mm.
Air Vent
To protect control part from humidity by temperature fluctuation, Vents are on left and right side
covered with Outer Cover.
y EVRC2A has Small size and Large size depending on Recloser Type.
y Small size is available for EVR1, EVR2, Large size is available for EVR3.
y Large size is able to make “User available Space” larger, the space unit is referred to
“Figure 13-6. Mount Accessories Dimensions”
y Standard for EVR1, EVR2 is small size and for EVR3 is large size.
y EVR1 (Recloser Rated Voltage : 15.5㎸) / EVR2 (27㎸) / EVR3 (38㎸)
y For installation on a Pole, the lifting hole is indicated.
y Weight of EVRC2A small size is 85㎏ and large size is 90㎏.
y EVRC2A should be fixed top and bottom with 16㎜(5/8") Bolt.
y There is an Exit hole for external cable that can be connected to additional functioning
hardware.
y The diameter of the hole is 22㎜(0.866") and two of Standard Receptacle "MS22" Series
can be extended.
y Shows base plate measurements that can be attached in User Available Space.
y On Base plate, 10㎜/M6 Nut is used to fix the base plate.
y Available space for height of base plate is from 101.6㎜ (4”) to 177.8㎜ (7”)
y 30W DC Power is provided. In case of the necessity of larger than 30W, additional power
should be attached. For more details, contact manufacturer. Input of the additional power is
referred to “Figure 13-7. Terminal Block and Fuses”
y Remove cable coating at the end of cable length of 8mm(0.315"). With using (+) CN5
connector terminal on side panel should be connected to Wire size AWG24 up to 12.
y To change Voltage ratings, disconnect Jumper Pin in JP3 “Figure 13-31. ANALOG
BOARD”, and connect Jumper Pin to either JPI (24Vdc) or JP2 (15Vdc). Be sure of the
voltage rating due to disassembly.
y When overload, automatically circuit breaks current. In case long-term overload time, there
is a fuse on analog circuits to protect circuits from failure.
y “Figure 13-9. EVRC2A Wiring Diagram - VT Type” is wiring diagram of VT type of which
Voltage Input is optional.
y CN2 is Voltage Input Connector. For wiring, refer to “Figure 13-13. VT Wiring Diagram”
y VD type and VT type are not exchangeable. VT type is standard and VD type is optional.
NOTE :
1) I/O Terminal (CN10, CN9) has functions to
control basic operation of Recloser and can be
connected with SCADA System for use.
2) Remove the coating of cable length of 8㎜
(0.315"). Side panel connector for user should be
connected to Wire size AWG24 to 12 Figure 13-10. Side Panel
Recloser Phase should match with User system. Refer to “Figure 13-14. Phase Rotation”
CT Phase rotation must be arranged comparing with Voltage Inputs Phase rotation.
y VD(CVD or RVD) Type can not be used when VT(Voltage Transformer) Type was selected.
y VT wiring should match Current Inputs.
y Voltage Inputs VA, VB, VC, VR, VS, VT
Input Voltage Range : Vphase-Vcom Continuous < 300V
Burden : 0.6VA(300V), 0.2VA(220V), 0.05VA(120V), 0.02VA(67V)
y For Metering accuracy, phase rotations of User system and Recloser should be the same.
y “Figure 13-14. Phase Rotation” shows the same phase rotation between User System and
Recloser.
y If the phase rotation is not the same in User system and Recloser, correct CT and VD(CVD
or RVD) wiring in side panel to be matched.
y EVR Recloser phase A is the Bushing the nearest from Trip lever on the side.
“Figure 13-15. Control Receptacle” shows Female Receptacle installed in Control EVRC2A.
A AC Power Input
B AC Power Input (Neutral)
C not connected
13.20. Fuses
Table 13-4. Fuses
Rating /
Positions Dimensions Purpose
External AC - Power Input
voltage.
UPS Module supplies through P2 Connector of UPS Module. Figure 13-20. Open Circuit Voltage
13.25. Communications
1) RS232 Pin Functions for Port1 and Port2
Table 13-6. RS232 Pin Functions for Port1 and Port2
Pin Serial Port1 Serial Port2 Definition
1 N/C DCD Data Carrier Detect
2 RXD RXD Receive Data
3 TXD TXD Transmit Data
4 N/C DTR Data Terminal Ready
5 GND GND Ground
6 N/C DSR Data Set Ready
7 N/C RTS Request To Send
8 N/C CTS Clear To Send
9 N/C N/C No Connection
Positions User Interface Panel(Male) Side Panel (Male)
Cable CC201 CC201,202,203
※. Note) ① PORT3 provides RS-485 communication and uses Digital power and insulated
power of CPU Part for surge protection. Each terminal is Anti-Over-voltage.
② To minimize the noise of communication line, Terminal Resistor is used in the both
end of the line and Twisted Shied Cable is advisable for connecting cable.
③ In order to use RS-485, the Pin4 and Pin5 of RS485 Port should be connected.
y Recloser Trip and Close Power is charged from C1, C2, C3 in UPS module.
y C1 is used for Trip power, C2, C3 are used for Close power.
y Trip(Close) runs when IGBT is “ON”. MC runs and the charged Capacitor transfer the Power
to TC(CC), eventually Recloser runs.
y F1, F2 are Fuses to protect IGBT from MC damage. These are on Analog Board.
y UPS Module charges Capacitor for Trip/Close. Its rated output voltage is 120Vdc.
y Trip and Close Capacitor are individually located and do not affect to each other during Trip
and Close.
y UPS Module runs by 120Vac Power or by Backup Battery.
y Transformer in EVRC2A connected with External AC Power generates 120Vac.
y Sealed lead-acid Type is used for Battery. Battery voltage does not run under 20Vac, runs
over 20Vdc.
Indicates Firmware Upgrade Port, RTC(Real Time Clock), and main parts location. Also
indicates backup battery type.
y JP1, JP2, JP3 are Jumper Connecter, defining User Available DC Power Output Rating.
y F1, F2 are use to protect IGBT for Close and Trip.
y F3 is for Relay Module protection.
y JP1, JP2, JP3 are Jumper Connectors and define User Available DC Power rating.
Figure 13-35. Pressure Changes depending on Temperature and Sensor Output voltage
5.0
4.5
4.0
3.5
Output voltage(Vdc)
3.0
2.5
2.0
1.5
1.0
0.5
0.0
-0.8 -0.7 -0.6 -0.5 -0.4 -0.3 -0.2 -0.1 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Pressure (bar)
13..39. Re
ecloser Test Kit
1) RTS
R 2010 Moodel tests EV
VRC2A by Faault Simulatiion.
2) RTS
R 2010 cann display Fuull Sequence of Trip timee, Trip currennt, Interval oon LCD screeen and
allso can varioously test Callibration Moode, OCR Mo
ode, Externaal Mode, Mannual Mode.
F
Figure 13-377. Recloser Test
Te Kit - RTS
S2010
Stan
ndard Ratin
ngs and Features
Tablee 13-15. Stan
ndard Ratinggs and Featu
ures
CLA
ASSIFICATION
N RATINGS AND
A FEATUR
RES
ENHA
ANCED TEC
CHNOLOGY
Y 293
RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr
14. MAINTANANCE
14.1. Warning Events
In control panel warning led if is lighted up bellow table refer and inspects.
D-RAM FAIL Data RAM FAIL SYS ALARM display Replace Main Processing Module
4. Replace Recloser