Bulletin 140U/UE

Molded Case Circuit Breakers

Time-Current Curves, Continued

Bul.140U/UE
Time-Current Curves for Bulletin 140U-J Electronic LSG & LSIG Molded Case Circuit Breakers
.1 .2 .3 .4 .5 .7 1.0 2.0
10000
9000
8000
7000
6000
5000
Circuit Breaker Time/Current Curves
4000
Ground Fault Delay Response (LSG, LSIG)
3000

2000

1000
900
800 Switch
700 tSD tGF
Setting
600
500 J Inst. Inst.
K Inst. 120
400
L Inst. 300
M 120 Inst.
300 120
N 120
O 120 300
P 300 Inst.
200
Q 300 120
R 300 300

100
90
80
1 MINUTE

70
60
50

40

30

Cat. No. 140U-JTI3-D25


TIME IN SECONDS

20

10
9
8
7
6 Ground Fault Pickup Settings
(Tolerance 10%)
5

3
Cat. No. 140U-JTG3-D25
2

0.4X
0.2X 1X
0.6X
1
.9 0.3X
.8
.7
0.8X
.6
.5 NOTE: Labels shown are for 250A style.
.4

.3 300ms
(L,O,R)

.2

Notes:
120ms
.1 (K,N,Q) 1. Curve accuracy applies from -20°C to +55°C ambient. Temperatures above +88° C
.09 cause an over-temperature protection trip. For possible continuous ampere derating for
.08 ambient above 40°C, consult Rockwell Automation.
.07
.06 2.Application frequency is 50/60 Hertz.
.05 Inst. 3. Trip units are suitable for functional field testing with test kit style # 70C1056G52.
(J,M,P)
.04
4. For LD Response & SD with Flat Response curve, see: 40752-622
2
.03 5. For LD Response & SD with I T Response curve, see: 40752-621

6. For Ground Fault Delay Response (this curve): 40752-623


.02

.01
.1 .2 .3 .4 .5 .7 1.0 2.0

Ground Current in Multiple of (In)

40752-623 (1)
TC01203004E
Effective September 2003

38 Visit our website: www.ab.com/catalogs