Vous êtes sur la page 1sur 6

Modular identification system COMBIFLEX

1MRK 514 005-BEN


Page 1
Issued: April 2005
Revision: A
Data subject to change without notice

Application To be able to locate a relay unit in a protective 1,75 in), derived from the 19” standard, is the
relay, the unit is identified with a unique item vertical distance between the groups of holes
designation. Furthermore, the electrical con- in the fixing bars of cubicles. The C-module
nection point has a unique terminal designa- (7 mm, 0,28 in) is the horizontal distance
tion. These designations are used on circuit between the mounting holes in apparatus
diagrams, terminal diagrams and elsewhere to bars.
identify locations of terminals and modules.

A circuit diagram for a protective relay shows


the units of which the protective relay is built
up, the internal wiring between the units and
the external connection of the relay. The ter-
minal diagram shows in a simplified way the
functioning of the protective relay and the
(96000213)
external connection of the relay.

The item designations are based on a coordi-


nate system of U and C modules and the ter- Fig. 1 The U and C modules form a coordinate
minal designations are based on the size of system. Note that the item designations of
the unit. U is the height module and C is the each unit is the combination of U and C
width module. The U-module (44,45 mm, modules covered by that unit’s upper left
corner, e.g. 101 and 325.
ABB Network Partner Modular identification system COMBIFLEX
1MRK 514 005-BEN
Page 2

Illustration of COMBIFLEX The next unit, 107, has the same U-module
item and terminal The left unit of the protective relay in Fig. 2 position but has added 6C to the C-module
designations has the item designation 101, where the first position. Unit 325 has added 2U and 24C to
figure stands for the U-module position and its module position.
the next two for the C-module position.

101 107 113 125

325

(xx00000675.tif)

Fig. 2 Item designations for relay units

A complete terminal designation for the pro- An example of the rear of a protection assem-
tective relay shown in Fig. 2, Fig. 3 and Fig. 4 bly with COMBITEST test switch is shown i
consists of e.g. the item designation 101 and Fig. 4. Terminal positions are used for inter-
the terminal designation 11 A. nal and external connections.

This terminal, 101:11 A, is encircled in the


terminal diagram, Fig. 3 and in the connec-
tion guide, Fig. 4.
ABB Network Partner Modular identification system COMBIFLEX
1MRK 514 005-BEN
Page 3

Fig. 3 Terminal diagram 1MRK 001 083-HAA

125:26 107:116

101:3A

107:118

101:11A

101:18A

325:26 113:417 107:316


xx05000184.eps

Fig. 4 Terminal locations at the rear of a protection assembly


ABB Network Partner Modular identification system COMBIFLEX
1MRK 514 005-BEN
Page 4

Fig. 5 Circuit diagram 1MRK 001 083-HA

Terminal bases are marked with figures and One and the same terminal, 21 (see Fig. 7), in
letters according to Fig. 6. The terminal des- an RX 4 terminal base can get four different
ignation for a relay unit depends on the size terminal designations depending on the size
of the mounted unit, not on the terminal base. of the mounted relay unit.

1 1 2 1 2 2
1 1 1 1
1 2 2
2 2 2 2
1 1
3 3 3 3 2 2
4 4 4 4
3 3
5 5 5 5

6 6 6 6
4 4
7 7 7 7 5 5
8 8 8 8
6 6
7 7

1 3 2 1 4 2
1 1 1 1

2 2 2 2

3 3 3 3

4 4 4 4

5 5 5 5

6 6 6 6

7 7 7 7

8 8 8 8

xx05000202.vsd

Fig. 6 Terminal base seen from the front


ABB Network Partner Modular identification system COMBIFLEX
1MRK 514 005-BEN
Page 5

From rear side

(96000217) (96000218) (96000219) (96000220)

4-seat relay 2-seat relay 2-seat relay 1-seat relay

Fig. 7 Terminal designation for different relay units dotted mounted on the same terminal base

101 :101 101:107 101:113 101:125 131 :101 131:107 131:113 131:125

131:325

101:325
xx05000200.vsd

Fig. 8 Two of the same protective relays, the encircled 101 and 131,mounted in an
equipment frame.

The terminal designation for one terminal in tective relay has the terminal designation
the left unit of the left protective relay will be 131:101 as this relay has added 30C-modules
101:101. The same terminal in the right pro- to its position 131.
ABB Network Partner Modular identification system COMBIFLEX
1MRK 514 005-BEN
Page 6

a) Horizontal marking tape

b) Horizontal marking bar

c) Marking strips on both sides


of the marking bar

d) The C-module designation for


the right-hand relay in Fig. 8
together with the U-module
designation 131 for the right-
hand relay

(75437)

Fig. 9 C-module markings

(75430)

Fig. 10 Vertical U-module marking tape

Manufacturer ABB Automation Technologies AB


Substation Automation Products
S-721 59 Västerås
Sweden
Telephone: +46 (0) 21 34 20 00
Facsimile: +46 (0) 21 14 69 18
Internet: www.abb.com/substationautomation

Vous aimerez peut-être aussi