ABB RED 670:

LOCAL END REMOTE END


RED670 RED670 RELAY
RELAY
87L
CTR:
87L CTR:
1600/1 A 1500/1A

VT

TWO END LINE DIFFERENTIAL CT


COMPENSATION WITH TWO DIFFERENT CT
RATIOS

LOCAL END:

I BASE(Reference Current) : 1600A(To be set in the relay, CT Primary current whichever is maximum of two ends)

Id Min(Differential Min Pick up): 0.25 IB (Primary current considered as 400A)

REMOTE END:

I BASE(Reference Current) : 1600A(To be set in the relay, CT Primary current whichever is maximum of two ends)

Id Min(Differential Min Pick up): 0.25 IB (Primary current considered as 400A)