80
Pickup 0.5
Settings α 50
60
β 2
VA 10 20
VB 20 40
20 Trip Zone
VC 30 90 Pickup
Inputs α
Current Magnitude Angle
β
IA 0 50 0 VA
‐80 ‐60 ‐40 ‐20 0 20 40 60 80 VB
IB 3 60
VC
IC 4 70
IA
‐20
IB
IC
Positive Magnitude Angle V1
Calculated V1 5.75 344.1 ‐40 I1
I1 1.03 262.0
‐60
If the current is greater than the 67 pickup setting in any
phase and the positive sequence current angle relative to the
positive sequence voltage angle is within the Alpha and Beta ‐80
operating range for the duration of the 67 time characteristic,
then a trip output will be issued. * Pickup and Current Values shown in the diagram multiplied by 10