Cooling Water Treatment


Chemistry Control and
Monitoring
05/01/2009

Cooling systems o er an ideal environment for microbiological fouling. Take steps now to look for and
treat scaling and fouling.

By Brad Buecker, Contributing Editor


The Second Law of Thermodynamics clearly states it is impossible to use heat solely to generate work in a cyclic
process. Even in the most efficient cycles, some heat must be exhausted for the cycle to operate. In power plants,
that means the primary heat sink is the water-cooled or air-cooled steam condenser. Similar heat exchange is
often required at large, non-utility plants as well. Waterside scaling or fouling seriously impedes heat transfer in
condensers, and can literally increase large plant fuel costs by hundreds to thousands of dollars per day.1 This
article touches upon some of the important fundamentals of cooling water treatment.

https://www.power-eng.com/articles/print/volume-113/issue-5/features/cooling-water-treatment-chemistry-control-and-monitoring.html 1/10
4/2/2018 Cooling Water Treatment Chemistry Control and Monitoring - Power Engineering

Bacteria will grow in condensers and cooling tower ll, fungi on and in cooling tower wood and algae on
wet cooling tower components exposed to sunlight. Biocide treatment is absolutely essential to maintain
cooling system performance and integrity.
Click here to enlarge image

Except along the coasts, the typical makeup water for cooling systems comes from a lake, river or, sometimes,
groundwater for plants with recirculating cooling systems; that is, systems with cooling towers. Regardless of the
makeup source, at plants with cooling towers the transfer of heat from the warm condenser water is primarily due
to evaporation in the tower. Of course, this causes the concentration of impurities in the bulk water to cycle
upwards. Blowdown is the common method to prevent excess dissolved solids buildups. But by itself blowdown
typically cannot prevent scale formation, as several compounds will exceed saturation level and precipitate on
condenser tubes and other system internals. Some of the most common scale-forming compounds, along with
their heat transfer coefficients, are shown on page 52, along with the coefficients for several common condenser
tube materials.

Table 1 shows how insulating the typical hardness compounds as compared to the metals they may coat. (The
table also shows why copper alloys were once almost universally selected for condenser tube material: Thick-
walled tubes could be used for structural integrity, but excellent heat transfer was still possible.) Conversely, other
foulants such as silica compounds and slime from microbiological deposits can be even worse than the hardness
deposits regarding heat transfer.

https://www.power-eng.com/articles/print/volume-113/issue-5/features/cooling-water-treatment-chemistry-control-and-monitoring.html 2/10
4/2/2018 Cooling Water Treatment Chemistry Control and Monitoring - Power Engineering

Click here to enlarge image

In the absence of any treatment programs, the primary scale-forming reaction produces calcium carbonate
deposits.

Ca+2 + 2HCO3- + heat → CaCO3+ CO2 + H2O

Unlike many salts, calcium carbonate is inversely soluble with temperature. Thus as temperatures rise in a
condenser or heat exchanger, the potential for CaCO3 scaling increases.

A straightforward and often used method to reduce the potential for calcium carbonate scaling is to treat the
makeup with sulfuric acid (H2SO4), where the hydrogen ions (H+) from the acid convert the bicarbonate to carbon
dioxide (CO2). The gas exits from the cooling tower.

H+ + HCO3- → CO2 + H2O

However, acid feed alone may not eliminate scaling. Upsets of acid feed can lead to corrosion or scaling, and
sulfuric acid introduces sulfate ions (SO4-2) to the water. Over time, this may lead to calcium sulfate deposition.
Accordingly, supplemental chemicals are normally used in cooling tower programs to further minimize scale
formation.

An early treatment method was feed of phosphates, either ortho-phosphate (PO4-2) or phosphate complexes that
would revert to ortho-phosphate, to precipitate calcium as [Ca3(PO4)2]. These programs also provided corrosion

protection because phosphate will react with ferrous ions (Fe+2) produced at anodic sites to form a protective
barrier, while [Ca3(PO4)2] precipitates in the local alkaline environment at cathodic sites. Zinc was a common
corrosion protection supplement, as zinc ions will also precipitate (as zinc hydroxide [Zn(OH)2] at cathodic sites)
thus enhancing the barrier film.

However, even small upsets in phosphate programs can cause severe calcium phosphate fouling. Accordingly,
treatment methods evolved to more forgiving methodologies, where, in many cases, the backbone of these
programs is an organic phosphate or phosphates (phosphonates) with a supplemental polymer to sequester and
modify the crystal structure of scale-forming ions and compounds.

https://www.power-eng.com/articles/print/volume-113/issue-5/features/cooling-water-treatment-chemistry-control-and-monitoring.html 3/10
4/2/2018 Cooling Water Treatment Chemistry Control and Monitoring - Power Engineering

Phosphonates primarily function as crystal modifiers and attach to crystals as they form, and thus alter their
structure and reduce the crystals’ adhesiveness to condenser tubes and other surfaces.

The phosphonates shown in Figure 1 (and their cousins) have been around for years and have worked well in a
large number of applications, although excess phosphonate feed can result in calcium-phosphonate scale
formation and fouling of heat transfer surfaces.

Figure 1 Two common phosphonates, HEDP and PBTC, for cooling water treatment
Click here to enlarge image

Also, many of the early phosphonates are susceptible to rapid degradation by oxidizing biocides such as chlorine,
bromine, chlorine dioxide and so on. A newer phosphonate, phosphino succinc oligomer (PSO), offers excellent
calcium carbonate scale inhibition combined with good resistance to degradation. Often in phosphonate programs,
a few parts-per-million (ppm) of ortho-phosphate [PO4] are used for both cathodic and anodic corrosion inhibition,
as outlined earlier. However, at the higher pH of these treatments, a strong possibility exists for calcium phosphate
[Ca3(PO4)2] scale formation. Thus, a small dosage of organic polymer is frequently used in the formulations to
keep calcium phosphate in suspension, such that it leaves the cooling system in the blowdown. Modern treatments
may use or rely on co- or ter-polymersin which active groups include carboxyl and sulfonic acid ions (COO- and
SO3-, respectively) and amide OC-NH2. These products are designed to control a variety of sales. A thorough
evaluation of the cooling water is necessary when considering and implementing any of these programs.

https://www.power-eng.com/articles/print/volume-113/issue-5/features/cooling-water-treatment-chemistry-control-and-monitoring.html 4/10
4/2/2018 Cooling Water Treatment Chemistry Control and Monitoring - Power Engineering

Click here to enlarge image

Some facilities will not allow the use of phosphate-containing compounds, either inorganic or organic, due to the
fact that phosphate is a nutrient for microbes, including algae. In these circumstances, an all-polymer program
(perhaps with acid treatment of the makeup) may be the only alternative to maintain reasonable cycles of
concentration in the tower. Polyacrylate and related compounds (polymers with COO- groups) can be effective at
controlling CaCO3 deposition in these situations. In once-through systems, a well-monitored biocide program
along with a polyacrylate can often keep condenser tubes in good condition through the warm weather months.

Microbiological Fouling Control


In my 20 years of direct experience at two coal-fired power plants and a manufacturing facility, the most common
cause of reduced heat transfer in condensers and auxiliary heat exchangers was microbiological fouling.

Cooling systems provide an ideal environment—warm and wet—for microbes. Bacteria will grow in condensers
and cooling tower fill, fungi on and in cooling tower wood and algae on wet cooling tower components exposed to
sunlight. Biocide treatment is absolutely essential to maintain cooling system performance and integrity.

Bacteria are separated into the following three categories,

Aerobic: Use oxygen in the metabolic process


Anaerobic: Live in oxygen-free environments and use other sources, for example,
sulfates, nitrates, or other donors for their energy supply
Facultative: Can live in aerobic or anaerobic environments.

A problem with microbes, particularly many bacteria, is that once they settle on a surface the organisms secrete a
polysaccharide layer for protection. This film then will collect silt from the water, thus growing even thicker and
further reducing heat transfer. Even though the bacteria at the surface may be aerobic, the secretion layer allows
anaerobic bacteria underneath to flourish. These bugs in turn can generate acids and other harmful compounds

https://www.power-eng.com/articles/print/volume-113/issue-5/features/cooling-water-treatment-chemistry-control-and-monitoring.html 5/10
4/2/2018 Cooling Water Treatment Chemistry Control and Monitoring - Power Engineering

that directly attack the metal. Microbial deposits also establish concentration cells, where the lack of oxygen
underneath the deposit causes the locations to become anodic to other areas of exposed metal. Pitting is often a
result, which can cause tube failure well before the expected lifetime of the material.

Fungi will attack cooling tower wood in an irreversible manner, which can eventually lead to structural failure.
Algae will foul cooling tower spray decks, potentially leading to reduced performance and unsafe working
locations.

The core of any microbiological treatment program is feed of an oxidizing biocide to kill organisms before they can
settle on condenser tube walls, cooling tower fill, and other locations. Chlorine was the workhorse for many years,
where when gaseous chlorine is added to water, the following reaction occurs.

Click here to enlarge image

null

HOCl, hypochlorous acid, is the killing agent. The functionality and killing power of this compound are greatly
affected by pH due to the equilibrium nature of HOCl in water.

Click here to enlarge image

null

OCl- is a much weaker biocide than HOCl, probably due to the fact that the charge on the OCl- ion does not allow
it to penetrate cell walls. The killing efficiency of chlorine dramatically declines as the pH goes above 7.5. Thus, for
the common alkaline scale/corrosion treatment programs, chlorine chemistry may not be efficient. Chlorine
demand is further affected by ammonia or amines in the water, which react irreversibly to form the much less
potent chloramines.

Due to safety concerns, liquid bleach (NaOCl) feed has replaced gaseous chlorine at many facilities. The major
difficulty with bleach is that the product contains a low concentration of sodium hydroxide, thus when it is injected
into the cooling water stream it raises the pH, if by only a small amount.

A popular alternative is bromine chemistry, where a chlorine oxidizer and a bromide salt, typically sodium bromide
(NaBr), are blended in a makeup water stream and injected into the cooling water. The chemistry produces
hypobromous acid (HOBr), which has similar killing powers to HOCl, but functions more effectively at alkaline pH.

https://www.power-eng.com/articles/print/volume-113/issue-5/features/cooling-water-treatment-chemistry-control-and-monitoring.html 6/10
4/2/2018 Cooling Water Treatment Chemistry Control and Monitoring - Power Engineering

Another factor in favor of bromine is that it does not react irreversibly with ammonia or amines. The primary
disadvantages are that an extra chemical is needed and feed systems are a bit more complex than for bleach
alone.

Chlorine dioxide (ClO2) has found some application as an oxidant for two primary reasons. Its killing power is not
affected by pH, and it does not form halogenated organic compounds. Also, chlorine dioxide is more effective in
attacking established bio-deposits. However, ClO2 is unstable and must be generated on-site, a common method
being reaction of sodium chlorite (NaClO2) and chlorine in a slipstream fed to the cooling water.

Click here to enlarge image

null

Costs are usually several times higher than for straight halogen treatment.

Other oxidants that have been tested for cooling water include hydrogen peroxide (H2O2) and ozone (O3), but the
short lifespan and tendency of these chemicals to escape from solution in the cooling tower typically make them
ineffective in large cooling water systems.

A method to help control microbes is a supplemental feed of a non-oxidizing biocide. Typically, feed is needed on a
temporary but regular basis, perhaps once per week. Table 2 outlines some of the properties of the most common
non-oxidizers.

Click here to enlarge image

Careful evaluation of the microbial species in the cooling water is necessary to determine the most effective
biocides. None of these chemicals should be used or even tested without approval from the appropriate regulating
agency. They must fit in with the plant’s National Pollutant Discharge Elimination System (NPDES) guidelines.
By continuing to use this site you consent to the use of cookies on your device as described in our cookie
policy
As withunless you havesafety
all chemicals, disabled
is anthem. You can
absolutely change
critical your
issue cookie
when settings
handling theatnon-oxidizers.
any time but our site
Adherence to all Ok
requires cookies to function properly. You may not be able to access content or other services correctly
handlingcookies.
without guidelines and use of proper personal protective equipment is a must. Many of these chemicals will
attack human cells as well as those of microbes.

https://www.power-eng.com/articles/print/volume-113/issue-5/features/cooling-water-treatment-chemistry-control-and-monitoring.html 7/10
4/2/2018 Cooling Water Treatment Chemistry Control and Monitoring - Power Engineering

Reference
1. B. Buecker, “Steam Generation Thermodynamics 101”; Power Engineering, pp. 106-114, Vol. 112, No. 11,
November 2008.

2. Properties of Some Metals and Alloys, The International Nickel Co., 1982.

Author: Brad Buecker is a contributing editor for Power Engineering.

Temporary Fabric Structures


A power plant is a permanent asset, but not all work site buildings need to be

By Beth B. Wilson, Maha ey Fabric Structures


The need for temporary space is at an all-time high in today’s rapidly changing environment. That need is
increased by weather delays and ever greater demands for worker productivity that can impact a plant’s bottom
line.

Whether due to frigid temperatures in northern climates or the extreme heat in the South, working conditions can
be the key factor in deadline setbacks. Productivity is boosted when the work can be completed in conditions
made comfortable by heating or air conditioning, in shaded environments, and without the threat of inclement
weather.

Warehouse and storage space at AEP power plant in Fulton, Arkansas. Photos courtesy of Maha ey
Fabric Structures
Click here to enlarge image

Problems brought about due to extreme weather conditions can be addressed by keeping employees sheltered
from whatever Mother Nature throws your way. Temporary, portable fabric structures can help a company continue
generating revenue during plant improvement projects.
https://www.power-eng.com/articles/print/volume-113/issue-5/features/cooling-water-treatment-chemistry-control-and-monitoring.html 8/10
4/2/2018 Cooling Water Treatment Chemistry Control and Monitoring - Power Engineering

Furthermore, power plants generally lack lunch and dining facilities, which can also factor into workers efficiency.
When employees have to completely stop what they’re doing, get in their vehicles and drive to find a place to eat,
the workday becomes increasingly shorter. Temporary tents and structures are the ideal solution for on-site dining
facilities. Dining facilities can be built to serve a few dozen persons to more than 3,000. Temporary fabric
structures can be equipped with such optional features as climate control, insulated steel hard sides, and an array
of flooring options. Mahaffey can even provide full-service food preparation and cooking areas, as well as on-site
catering personnel.

Because they can be easily transported to various locations when needed, these structures are economical.
Speaking of economics, money to build additional storage and warehouse space is scarce these days. Temporary
structures serve as an economic alternative to steel storage buildings, which can be a significant advantage today.

Not only can these structures protect workers from the elements and provide a comfortable dining area, they also
present a way to control interior temperature and humidity. Large clear span structures can be outfitted with
flooring, lighting, personnel or roll-up doors, tables and chairs for dining, multiple HVAC units, and power
distribution via the grid or on-site sources.

Another potential cost saving can be achieved by installing a translucent fabric roof to let in natural light, saving the
expense of an elaborate lighting system. To retain heat or cool air inside, install insulated hard sides for optimal
climate control, regardless of what the outside temperature is.

Mahaffey’s Mega Series structures are built to withstand extreme winds of up to 120 miles per hour, combined with
snow loads of 30 lb/square feet. The Tension Series, or MTS, structures are fully-engineered to meet and exceed
snow and wind loads, while also having a superior snow-shedding capability for those in snow country.

Mahaffey is currently providing two large structures for Shaw Power Group, who was awarded a contract by
Southwestern Electric Power Company (SWEPCO), a unit of AEP for its 600 MW power plant in Fulton, Arkansas.
Shaw is using two 100’ X 150’ structures as temporary warehouses for storage of equipment and parts needed for
the project. A third structure is being used as a dining facility for workers.

Mahaffey also recently provided a large warehouse facility for Bechtel. The warehouse was needed for six to eight
months. Mahaffey provided five full-engineered 10m dining facilities for the plant for Fluor at a ConocoPhillips
Refinery in Roxana, Illinois. Nine temporarily fabric structures were eventually used on the project. The project is
set to be up for more than two years. Mahaffey is also providing two large structures for S&B Engineers in
Houston, Texas, at their Petro Logistics Plant. The first, a 66’ X 115’ structure is being used as a warehouse
facility. The second – a 100’ X 66’ structure—is being used as an on-site lunch tent.

Author:
Beth B. Wilson is the Marketing Manager for Mahaffey Fabric Structures.

https://www.power-eng.com/articles/print/volume-113/issue-5/features/cooling-water-treatment-chemistry-control-and-monitoring.html 9/10
4/2/2018 Cooling Water Treatment Chemistry Control and Monitoring - Power Engineering

Copyright © 2007-2018. PennWell Corporation, Tulsa, OK. All Rights Reserved.   PRIVACY POLICY | TERMS
AND CONDITIONS

https://www.power-eng.com/articles/print/volume-113/issue-5/features/cooling-water-treatment-chemistry-control-and-monitoring.html 10/10

Vous aimerez peut-être aussi