2. Input the vendor data in sections 1 to 5. If seismic & wind loads in section 5 are
not provided by vendor, Input these loads from section 19.
3. Input the soil report data (soil & pile parameters) in sections 6 to 8.
4. Input the specifications data (material strength & unit weights) in section 9 & 10.
7. Design Conditions, Seismic & Wind Load Calculations & Anchorage Length Check Deatails
are provided in the A, B & C sections respectively of this sheet
A DESIGN CONDITIONS
According to UBC 97
V = (Cv I / R T) x W
Vmax = (2.5 Ca I / R) x W
Vmin = (0.56 Ca I) x W
Ct 0.0448
Z Zone-2A 0.15 (Ref: Table 16-I) 30.2 kN
Cv 0.5 (Ref: Table 16-R)
Ca 0.3 (Ref: Table 16-Q)
R 2.9 (Ref: Table 16-P)
I 1.25 (Ref: Table 16-K)
T = Ct (hn)3/4 0.36
V 0.60 W
Vmax 0.32 W
Vmin 0.21 W
V 30.2 kN
Seismic Moment
M = 2/3 H V 325.2 kN-m
Fw = G qz Cf Ae
Kz = 2.01 (z/Zg)^2/α
qz = 0.613 Kz Kzt Kd V² I
Ae = D' H
ASCE 7-02
6.5.6.2 Surface Roughness Categories
Surface Roughness B:
Urban & suburban areas, wooded areas or other terrain with numerous closely spaced obstructions
having the size of single-family dwellings or larger.
Surface Roughness C:
Open terrain with scattered obstructions having heights generally less than 30 ft (9.1 m). This
category includes flat open country, grasslands, and all water surfaces in hurricane-prone regions.
Surface Roughness D:
Flat, unobstructed areas and water surfaces outside hurricane-prone regions. This category
includes smooth mud flats, salt flats, and unbroken ice.
Structure Type Kd
Buildings
Main Wind Force Resisting System 0.85
Components and Cladding 0.85
Arched Roofs 0.85
Chimneys, Tanks and Similar Structures
Square 0.90
Hexagonal 0.95
Round 0.95
Solid Signs 0.85
Open Signs and Lattice Framework 0.85
Trussed Towers
Triangular, Square, Rectangular 0.85
All other cross-sections 0.95
Figure 6-19
Force Coefficients, Cf for Chimneys, tanks, Rooftop Equipment & Similar Structures
Table 6-2
Terrain Exposure Constants Area Increase Factor
10.77 m
Z Z Kz qz G G qz
(ft) (m) (kN/m²) (kN/m²)
13.12 4.00 0.849 0.675 0.85 0.573
14.76 4.50 0.849 0.675 0.85 0.573
16.41 5.00 0.865 0.687 0.85 0.584
18.05 5.50 0.883 0.701 0.85 0.596
19.69 6.00 0.899 0.714 0.85 0.607
21.33 6.50 0.914 0.726 0.85 0.617
22.97 7.00 0.929 0.738 0.85 0.627
24.61 7.50 0.942 0.749 0.85 0.636
26.25 8.00 0.955 0.759 0.85 0.645
27.89 8.50 0.967 0.769 0.85 0.653
29.53 9.00 0.979 0.778 0.85 0.661
31.17 9.50 0.990 0.787 0.85 0.669
spaced obstructions 32.81 10.00 1.001 0.795 0.85 0.676
34.45 10.50 1.011 0.804 0.85 0.683
36.09 11.00 1.021 0.812 0.85 0.690
(9.1 m). This 37.73 11.50 1.031 0.819 0.85 0.696
ane-prone regions. 39.37 12.00 1.040 0.827 0.85 0.703
41.01 12.50 1.049 0.834 0.85 0.709
his category 42.65 13.00 1.058 0.841 0.85 0.715
44.29 13.50 1.066 0.847 0.85 0.720
45.93 14.00 1.074 0.854 0.85 0.726
47.57 14.50 1.082 0.860 0.85 0.731
49.22 15.00 1.090 0.866 0.85 0.736
ce Roughness B, 50.86 15.50 1.098 0.872 0.85 0.741
mes the height of the 52.50 16.00 1.105 0.878 0.85 0.746
n or equal to 30 ft 54.14 16.50 1.112 0.884 0.85 0.751
55.78 17.00 1.119 0.889 0.85 0.756
57.42 17.50 1.126 0.895 0.85 0.761
59.06 18.00 1.133 0.900 0.85 0.765
60.70 18.50 1.139 0.905 0.85 0.770
ce Roughness D, 62.34 19.00 1.146 0.911 0.85 0.774
mes the height of the 63.98 19.50 1.152 0.916 0.85 0.778
e for a distance of 65.62 20.00 1.158 0.920 0.85 0.782
67.26 20.50 1.164 0.925 0.85 0.786
68.90 21.00 1.170 0.930 0.85 0.790
70.54 21.50 1.176 0.935 0.85 0.794
72.18 22.00 1.182 0.939 0.85 0.798
73.82 22.50 1.187 0.944 0.85 0.802
75.46 23.00 1.193 0.948 0.85 0.806
77.10 23.50 1.198 0.952 0.85 0.809
78.74 24.00 1.204 0.956 0.85 0.813
80.38 24.50 1.209 0.961 0.85 0.816
82.03 25.00 1.214 0.965 0.85 0.820
83.67 25.50 1.219 0.969 0.85 0.823
85.31 26.00 1.224 0.973 0.85 0.827
86.95 26.50 1.229 0.977 0.85 0.830
88.59 27.00 1.234 0.980 0.85 0.833
90.23 27.50 1.239 0.984 0.85 0.837
91.87 28.00 1.243 0.988 0.85 0.840
93.51 28.50 1.248 0.992 0.85 0.843
95.15 29.00 1.252 0.995 0.85 0.846
96.79 29.50 1.257 0.999 0.85 0.849
98.43 30.00 1.261 1.002 0.85 0.852
100.07 30.50 1.266 1.006 0.85 0.855
101.71 31.00 1.270 1.009 0.85 0.858
103.35 31.50 1.274 1.013 0.85 0.861
104.99 32.00 1.279 1.016 0.85 0.864
106.63 32.50 1.283 1.019 0.85 0.867
108.27 33.00 1.287 1.023 0.85 0.869
109.91 33.50 1.291 1.026 0.85 0.872
111.55 34.00 1.295 1.029 0.85 0.875
113.19 34.50 1.299 1.032 0.85 0.877
114.84 35.00 1.303 1.035 0.85 0.880
116.48 35.50 1.307 1.039 0.85 0.883
118.12 36.00 1.311 1.042 0.85 0.885
119.76 36.50 1.315 1.045 0.85 0.888
121.40 37.00 1.318 1.048 0.85 0.891
123.04 37.50 1.322 1.051 0.85 0.893
124.68 38.00 1.326 1.054 0.85 0.896
126.32 38.50 1.329 1.056 0.85 0.898
127.96 39.00 1.333 1.059 0.85 0.900
129.60 39.50 1.337 1.062 0.85 0.903
131.24 40.00 1.340 1.065 0.85 0.905
Abolt L
24 595
30 820
L/Cs 36 1055
Empty + Wind + Uplift 42 1250
Empty + Wind 48 1430
Empty + 0.71 Seismic 56 1675
Operation 64 1930
Operation + Wind 72 2180
Operation + 0.71 Seismic 80 2410
Test pt&s
Test + Wind p max
L/Cs
1.4 Operation 1.4
1.2 Operation + 1.6 Wind 1.2
0.9 Operation + 1.6 Wind 0.9
1.32 Operation + 1.1 Seismic 1.32
0.99 Operation + 1.1 Seismic 0.99
0.9 Empty + 1.6 Wind 0.9
1.4 Test 1.4
1.2 Test + 0.95 Wind 1.2
Fw #REF! kN
P hef nt B
105 414 8 110
140 590 7 110
195 750 6 130
210 910 5 160
225 1060 4.5 200
240 1265 4.5 250
255 1480 4 260
275 1685 4 270
280 1890 4 270
0.0020
0.0235
6 - 600φ Piles
BCD = 1700
5100 2150 3600
150
850
1000
50
5100
100 100
IN MM
6.5 1384
B: 18 bars # 20 @ 300 mm
T: 18 bars # 20 @ 300 mm
B: 18 bars # 20 @ 300 mm
T: 18 bars # 20 @ 300 mm
48 - # 20
# 10 @ 150 mm 16 - # 20
300
# 10 @ 200 mm
# 10 @ 150 mm
# 10 @ 200 mm
Doc. No. 1013-XX-XX-XX-XXX PAGE: 1 of 15
X X-XX-2005 XXXXXX XX XX XX
Initial Dated Initial Dated Initial Dated
Rev Date Description
Prepared by Checked by Approved By
EL WASTANI PETROLEUM COMPANY CLIENT
REFERENCE
(WASCO)
CLIENT P.O Box 52 El Maadi
El Safa Office Tower, Block 42, Sector No. 6 EW-T-13-2005
Zahraa El-Maadi, Cairo, Egypt
PRESSON ENERFLEX ENERFLEX
2103-8th STREET NISKU, ALBERTA, PROJECT NO.
XX XX XX 4/9/2018 1013-XX-XX-XX-XXX Ao
CLIENT: EL WASTANI PETROLEUM COMPANY (WASCO) PAGE: 2 of 15
PROJECT: EL WASTANI GAS FIELD DEVELOPMENT, PHASE-III DOC. NO: 1013-XX-XX-XX-XXX
TITLE: FOUNDATION DESIGN FOR ADSORPTION TOWERS (A,B,C) REV : Ao
CONTENTS
1. GENERAL 3
3. MATERIAL SPECIFICATIONS 3
4. SOIL CONDITION 3
5. FOUNDATION DETAIL 3
9. OUTPUT CALCULATIONS 6
1. GENERAL
Service ADSORPTION TOWERS (A,B,C)
Document No.: 1013-XX-XX-XX-XXX
3. MATERIAL SPECIFICATIONS
3.1 Strength
Reinforcement bar yield strength 350 MPa
Concrete compressive strength at 28 days (Cylinder) 24 MPa
Anchor bolts : fy(bolt) 570 MPa
4. SOIL CONDITION
5. FOUNDATION DETAIL
5.2 Elevation
Top of pedestal 0.15 m
Unit 0.00 m
Ground water level -1.50 m
y2
y1
EL +0.15 m
EL +0.00 m
GWL EL -1.50 m
h2
h4
hw
h1
EL -1.85 m
Where
1.3843 m Fp = Seismic Force
Fp, Fw Fw = Wind Force
We = Weight of Equipment
16.1544 m Wf = Weight of footing
M = Seismic or Wind Moment
We
Wf Pedestal
Footing
CLIENT: EL WASTANI PETROLEUM COMPANY (WASCO) PAGE: 22+2 of 56+2
PROJECT: EL WASTANI GAS FIELD DEVELOPMENT, PHASE-III DOC. NO: 1013-XX-XX-XX-XXX
TITLE: FOUNDATION DESIGN FOR ADSORPTION TOWERS (A,B,C) REV : Ao
CLIENT: EL WASTANI PETROLEUM COMPANY (WASCO) PAGE: 23+2 of 56+2
PROJECT: EL WASTANI GAS FIELD DEVELOPMENT, PHASE-III DOC. NO: 1013-XX-XX-XX-XXX
TITLE: FOUNDATION DESIGN FOR ADSORPTION TOWERS (A,B,C) REV : Ao
8.3 Piles
number of piles (1st P.C.D) n1 6
number of piles (2nd P.C.D) n2 0
number of piles (TOTAL) n 6
8.5 Dimension
Footing Thickness h1 1.000 m OK !
Pedestal Height h2 1.000 m
Projection of Pedestal h3 0.150 m
Soil Cover h4 0.850 m
Height of Foundation Hf = h1 + h2 2.000 m
Depth of Foundation df = h1 + h4 1.850 m
Height of GWL from footing base hw 0.350 m
Pedestal size d2 2.150 m
Equivalent Square Size (d2') /2 0.978 m
Footing size d1 5.100 m
(d1-d2)/2 1.475 m
Dimension of Pile (Dp) 0.600 m
length of pile 36.000 m
1st Pile circle diameter /2 R1 1.800 m
2nd Pile circle diameter /2 R2 0.000 m
Pile pitch (1st P.C.D) 1.800 m OK !
Pile pitch (2nd P.C.D) 0.000 m OK !
CLIENT: EL WASTANI PETROLEUM COMPANY (WASCO) PAGE: 24+2 of 56+2
PROJECT: EL WASTANI GAS FIELD DEVELOPMENT, PHASE-III DOC. NO: 1013-XX-XX-XX-XXX
TITLE: FOUNDATION DESIGN FOR ADSORPTION TOWERS (A,B,C) REV : Ao
9. OUTPUT CALCULATIONS
9.1 Area
A(Pedestal) 3.83 m²
A(footing) 21.55 m²
A(pedestal+d/2) 7.66 m²
A(pedestal+d) 12.79 m²
A(pile) 0.28 m²
A(pile+d) 1.74 m²
IR n1 R1² / 2 + n2 R2² / 2 9.72 m²
Zp IR / R 5.40 m
9.3 Weight
pedestal 91.91 kN
footing 517.14 kN
pile 1465.74 kN
soil above footing 245.48 kN
buoyancy 73.98 kN
concrete + soil(Dself) 854.53 kN
concrete + soil(Dself) - buoyancy 780.54 kN
Footing weight per 1 meter 24.00 kN/m
Soil cover weight per 1 meter 13.86 kN/m
y1 y2
a
d A2
d2'/2
A1
b
a'
A2'
Q(y1) Q(y2)
d2'/2+d
number of re-bar 18
Bottom-bar pitch (S) 300 mm
Total area of Bottom-bar (As) 5341 mm² OK !
number of re-bar 18
Top-bar pitch 300 mm
Total area of Top-bar (As) 5341 mm² OK !
φVc 8235 kN OK !
Vc = fc'0.5bwd /6 727 kN
f Vc 545 kN OK !
CLIENT: EL WASTANI PETROLEUM COMPANY (WASCO) PAGE: 32+2 of 56+2
PROJECT: EL WASTANI GAS FIELD DEVELOPMENT, PHASE-III DOC. NO: 1013-XX-XX-XX-XXX
TITLE: FOUNDATION DESIGN FOR ADSORPTION TOWERS (A,B,C) REV : Ao
Bolt size 36 mm
Fy (bolt) 570 MPa
nt = no. of threads per inch 6
Ase = π (do - 0.9743/nt)² / 4 (in) 798 mm²
Max force in bolts = no of bolts x Fy (bolt) x Ase x 0.75 2729 kN
number of re-bar 64
Inner Side bar line perimeter 3645 mm
Pedestal edge bar line perimeter 6627 mm
Inner Side 16 bars
Outer Side 48 bars
Provided As 20106 mm² OK !
Provided p 0.0053
BCD
300
TIES
re-bar size 10 mm
Sectional Area 79 mm²
CLIENT: EL WASTANI PETROLEUM COMPANY (WASCO) PAGE: 33+2 of 56+2
PROJECT: EL WASTANI GAS FIELD DEVELOPMENT, PHASE-III DOC. NO: 1013-XX-XX-XX-XXX
TITLE: FOUNDATION DESIGN FOR ADSORPTION TOWERS (A,B,C) REV : Ao
Nn
35° 35°
hef
t t
14.1 ASSUMPTIONS:
14.1.1 Calculation will be carried out according to Appendix D ACI 318-02 and PCA Notes.
14.1.2 For calculations of concrete Break out Strength in tension Clause D 4.2.1 of
ACI 318-02 shall apply I.e. the entire tensile face shall be taken up by reinforcing steel.
14.1.3 Clause D 3.3 shall apply to all anchorage strengths except break out strength (which
is determined by reinforcement). So all anchorage strengths in which √(f c') is
included in calculations shall be multiplied by 0.75 in order to ensure a ductile failure.
(Reinforcing Steel fy shall not be multiplied by 0.75)
14.1.4 The design of anchorage shall ensure that the anchorage strength (least of all failure
modes) is greater than (0.75 fult x Ase of bolt tensile force) and (0.39fult x Ase of bolt)
for shear faces (0.65 x 0.6 = 0.39 see Art D 4.4, D 5.12 and D 6 ACI 318-02).
Nu
Vu
hef
C1
CLIENT: EL WASTANI PETROLEUM COMPANY (WASCO) PAGE: 35+2 of 56+2
PROJECT: EL WASTANI GAS FIELD DEVELOPMENT, PHASE-III DOC. NO: 1013-XX-XX-XX-XXX
TITLE: FOUNDATION DESIGN FOR ADSORPTION TOWERS (A,B,C) REV : Ao
C1 = 225 mm
hef = 750 mm
CLIENT: EL WASTANI PETROLEUM COMPANY (WASCO) PAGE: 36+2 of 56+2
PROJECT: EL WASTANI GAS FIELD DEVELOPMENT, PHASE-III DOC. NO: 1013-XX-XX-XX-XXX
TITLE: FOUNDATION DESIGN FOR ADSORPTION TOWERS (A,B,C) REV : Ao
φNs = 431 kN
φVs 224 kN
C1 225 mm
C2 978 mm (Assume)
φ 0.70 D-4.4 c (i)
Av / Avo 1.0
y6 1.0
y7 1.0
Vb = 7 (l/do)^0.2 √do √fc'(C1)^1.5
do 36 mm
l = 8do 288 mm
Vb 1053 kN
φVcb = φ(Av/Avo y6 y7 Vb) x 0.75 As per ACI: D3.3
φVcb 553 kN > φVs OK !
Kcp 2 D-6.3.1
φ 0.70 D-4.4 c (i)
C1 225 mm
1. GENERAL
Service ADSORPTION TOWERS (A,B,C)
Document No.: 1013-XX-XX-XX-XXX
3. MATERIAL SPECIFICATIONS
3.1 Strength
Reinforcement bar yield strength 50000 psi
Concrete compressive strength at 28 days (Cylinder) 3500 psi
Anchor bolts : fy(bolt) 80000 psi
4. SOIL CONDITION
5. FOUNDATION DETAIL
5.2 Elevation
Top of pedestal 0.49 ft
Unit 0.00 ft
Ground water level -4.92 ft
y2
y1
EL +0.49 ft
EL +0.00 ft
GWL EL -4.92 ft
h2
h4
hw
h1
EL -6.07 ft
4.5 Where
Fp = Seismic Force
Fp, Fw Fw = Wind Force
53.0 We = Weight of Equipment
Wf = Weight of footing
M = Seismic or Wind Moment
We
Wf Pedestal
Footing
CLIENT: EL WASTANI PETROLEUM COMPANY (WASCO) PAGE: 40+2 of 56+2
PROJECT: EL WASTANI GAS FIELD DEVELOPMENT, PHASE-III DOC. NO: 1013-XX-XX-XX-XXX
TITLE: FOUNDATION DESIGN FOR ADSORPTION TOWERS (A,B,C) REV : Ao
CLIENT: EL WASTANI PETROLEUM COMPANY (WASCO) PAGE: 41+2 of 56+2
PROJECT: EL WASTANI GAS FIELD DEVELOPMENT, PHASE-III DOC. NO: 1013-XX-XX-XX-XXX
TITLE: FOUNDATION DESIGN FOR ADSORPTION TOWERS (A,B,C) REV : Ao
8.3 Piles
number of piles (1st P.C.D) n1 6
number of piles (2nd P.C.D) n2 0
number of piles (TOTAL) n 6
8.5 Dimension
Footing Thickness h1 3.28 ft OK !
Pedestal Height h2 3.28 ft
Projection of Pedestal h3 0.49 ft
Soil Cover h4 2.79 ft
Height of Foundation Hf = h1 + h2 6.56 ft
Depth of Foundation df = h1 + h4 6.07 ft
Height of GWL from footing base hw 1.15 ft
Pedestal size d2 7.05 ft
Equivalent Square Size (d2') /2 3.21 ft
Footing size d1 16.73 ft
(d1-d2)/2 4.84 ft
Dimension of Pile (Dp) 1.97 ft
length of pile 118.12 ft
1st Pile circle diameter /2 R1 5.91 ft
2nd Pile circle diameter /2 R2 0.00 ft
Pile pitch (1st P.C.D) 5.91 ft OK !
Pile pitch (2nd P.C.D) 0.00 ft OK !
CLIENT: EL WASTANI PETROLEUM COMPANY (WASCO) PAGE: 42+2 of 56+2
PROJECT: EL WASTANI GAS FIELD DEVELOPMENT, PHASE-III DOC. NO: 1013-XX-XX-XX-XXX
TITLE: FOUNDATION DESIGN FOR ADSORPTION TOWERS (A,B,C) REV : Ao
9. OUTPUT CALCULATIONS
9.1 Area
A(Pedestal) 41.22 ft²
A(footing) 231.96 ft²
A(pedestal+d/2) 82.42 ft²
A(pedestal+d) 137.74 ft²
A(pile) 3.04 ft²
A(pile+d) 18.77 ft²
IR n1 R1² / 2 + n2 R2² / 2 104.64 ft²
Zp IR / R 17.72 ft
9.3 Weight
pedestal 20.7 kips
footing 116.3 kips
pile 329.5 kips
soil above footing 55.2 kips
buoyancy 16.6 kips
concrete + soil(Dself) 192.1 kips
concrete + soil(Dself) - buoyancy 175.5 kips
Footing weight per 1 ft 1.64 kip/ft
Soil cover weight per 1 ft 0.95 kip/ft
y1 y2
a
d A2
d2'/2
A1
b
a'
A2'
Q(y1) Q(y2)
d2'/2+d
number of re-bar 18
Bottom-bar pitch (S) 11.8 in
Total area of Bottom-bar (As) 8.28 in² OK !
number of re-bar 18
Top-bar pitch 11.8 in
Total area of Top-bar (As) 8.28 in² OK !
BCD
300
TIES
re-bar size 3
Sectional Area 0.12 in²
CLIENT: EL WASTANI PETROLEUM COMPANY (WASCO) PAGE: 51+2 of 56+2
PROJECT: EL WASTANI GAS FIELD DEVELOPMENT, PHASE-III DOC. NO: 1013-XX-XX-XX-XXX
TITLE: FOUNDATION DESIGN FOR ADSORPTION TOWERS (A,B,C) REV : Ao
Nn
35° 35°
hef
t t
14.1 ASSUMPTIONS:
14.1.1 Calculation will be carried out according to Appendix D ACI 318-02 and PCA Notes.
14.1.2 For calculations of concrete Break out Strength in tension Clause D 4.2.1 of
ACI 318-02 shall apply I.e. the entire tensile face shall be taken up by reinforcing steel.
14.1.3 Clause D 3.3 shall apply to all anchorage strengths except break out strength (which
is determined by reinforcement). So all anchorage strengths in which √(f c') is
included in calculations shall be multiplied by 0.75 in order to ensure a ductile failure.
(Reinforcing Steel fy shall not be multiplied by 0.75)
14.1.4 The design of anchorage shall ensure that the anchorage strength (least of all failure
modes) is greater than (0.75 fult x Ase of bolt tensile force) and (0.39fult x Ase of bolt)
for shear faces (0.65 x 0.6 = 0.39 see Art D 4.4, D 5.12 and D 6 ACI 318-02).
Nu
Vu
hef
C1
CLIENT: EL WASTANI PETROLEUM COMPANY (WASCO) PAGE: 53+2 of 56+2
PROJECT: EL WASTANI GAS FIELD DEVELOPMENT, PHASE-III DOC. NO: 1013-XX-XX-XX-XXX
TITLE: FOUNDATION DESIGN FOR ADSORPTION TOWERS (A,B,C) REV : Ao
C1 = 8.9 in
hef = 29.5 in
CLIENT: EL WASTANI PETROLEUM COMPANY (WASCO) PAGE: 54+2 of 56+2
PROJECT: EL WASTANI GAS FIELD DEVELOPMENT, PHASE-III DOC. NO: 1013-XX-XX-XX-XXX
TITLE: FOUNDATION DESIGN FOR ADSORPTION TOWERS (A,B,C) REV : Ao
C1 8.9 in
C2 38.5 in (Assume)
φ 0.70 D-4.4 c (i)
Av / Avo 1.0
y6 1.0
y7 1.0
Vb = 7 (l/do)^0.2 √do √fc'(C1)^1.5
do 1.4 in
l = 8do 11.3 in
Vb 236.6 kips
φVcb = φ(Av/Avo y6 y7 Vb) x 0.75 As per ACI: D3.3
φVcb 124.2 kips > φVs OK !
Kcp 1 D-6.3.1
φ 0.70 D-4.4 c (i)
C1 8.9 in