1. ALL ELECTRICAL DEVICES FOR THE PRE-ACTION SYSTEM TO BE MOUNTED AND INSTALLED PER
12-153
SD SD
DRC
PER NFPA 72 AND THE DEVICE MOUNTING DETAILS SHOWN ON THIS SHEET.
SD
PARP
2. ALL WIRING FROM THE DEVICES TO THE RELEASING PANEL TO BE DONE IN ACCORDANCE WITH ALL
APPLICABLE CODES, THE LOCAL AUTHORITY AND THE SPECIFICATIONS.
3. ALL WIRING FROM RELEASING PANEL TO FACP AND POWER WIRING TO BE DONE BY OTHERS.
BELL
SD
MECH/ELECTRICAL ROOM
5. IN THE CONDITION THAT A SMOKE DETECTOR AND THE LOSS OF AIR PRESSURE BELOW
20 PSI IS MET THE SOLENOID VALVE IS TRIPPED AND THE DELUGE VALVE IS OPEN, ALARM
PRESSURE SWITCH SENDS A SIGNAL TO FACP THAT PRE-ACTION SYSTEM IS IN A FLOWING
CONDITION INITIATING BUILDING FIRE ALARM SYSTEM.
6. IF EMERGENCY RELEASE LOCATED ON TRIM OF DELUGE VALVE IS PULLED SOLENOID IS ENERGIZED
TRIPPING THE DELUGE VALVE AND A SIGNAL TO FACP THAT PRE-ACTION SYSTEM IS IN A
BELL
FLOWING CONDITION. (NO WATER IS SENT INTO THE PIPING OR DISCHARGED UNTIL A SPRINKLER
PARP
IS ACTIVATED.)
SD
(7) -
(1) -
(1) -
EOLR
5.1K
BASEMENT - DETECTION PLAN
1/4"=1'-0"
SD
SD
EOLR
5.1K SD
TS SD
TS SD
N L + - + - S + - + - + - + - + - + - + -
24 VNR DC RS-485 AUX. POWER SUP1 SUP2 ZONE 1 ZONE 2 ZONE 3 ZONE 4
24 VR DC
SYMBOL LEGEND
SD SMOKE DETECTOR
7 ZONE 1 OUTPUT 1
APS ALARM PRESSURE SWITCH POTTER ELECTRIC PS10-2A
1 ZONE 2 OUTPUT 2
TS TAMPER SWITCH INTERNAL ON BUTTERFLY VALVES
4 ZONE 3 OUTPUT 3
LAS LOW AIR PRESSURE SWITCH POTTER ELECTRIC PS40-2A PROGRAM RUN
1 MODE MODE
ZONE 4 OUTPUT4
SOL PRE-ACTION SYSTEM RELEASING SOLENOID VALVE SCROLL-UP
1 BUZZER SILENCE
AC POWER SUPERVISORY 1
BELL ELECTRIC BELL 24VDC WITH BACK BOX POWER TBL SUPERVISORY 2
1 LAMP
TEST
SYSTEM TBL COMMON ALARM
PARP PRE-ACTION SYSTEM RELEASING PANEL VIKING VFR-400 SET SCROLL-DOWN
1 SUP TBL ALARM SILENCE BUZZER SILENCE
GROUND STEADY DISCHARGED
FAULT FLASHING PRE-
NOTE: DISCHARGED
TAMPER SWITCHES ARE INTERNALLY WIRED
INTO EACH BUTTERFLY VALVE. SELECT SIGNAL SILENCE
VIEWING ANGLE
BATTERY CABLE
OBSERVE POLARITY BELL SOL 5.1K 5.1K
EOLR EOLR WIRED TO BUILDING
BLACK
RED +
BLACK - B B FIRE ALARM CONTROL PANEL
RED
NON-POWERED LIMITED (BY OTHERS)
AND SUPERVISED
5.1K 5.1K
EOLR EOLR
+ - + -
POS NEG POS NEG