1 Introduction
As it is known, concrete presents a good resistance when exposed at high temperatures. It is non-
combustible and has a slow rate of heat transfer, which makes it a highly effective barrier to the spread
of fire.
Most International Codes and Standards allow performing member analysis, thus neglecting the effects
of the indirect fire actions. This method does not take into consideration the arising of members internal
forces and can lead to non conservative results. The increase of shear force in the columns induced by
thermal expansion of beams and slabs can cause the collapse of the structure.
The main objective of this work is to understand the global behaviour of concrete structures when
exposed to fire. Hence, it is performed a simplified analysis to a building that suffered a fire. This analysis
consists in the application of temperature variations (uniform and linear gradient) to the slabs and beams
of the building and comparing the results with those verified in-situ. It is used a commercial computer
programme named SAP2000 for the modelling of the structure and for the application of temperature
variations.
• advanced calculations, that can be used on simulation of global behaviour of the structure, parts of
the structure (frames) and isolated elements (beams, columns or slabs), neglecting the interaction
between them;
• full scale fire tests.
According to Part 1-2 of Eurocode 1 [2], fire resistance of structures should take into account the
following steps:
• definition of the thermal action;
• definition of the mechanical actions in fire situation;
1
• calculation of the temperature evolution θd in structural elements;
• determination of the design value of the relevant effects of actions in the fire situation at exposure
time t, Ef i,d,t ;
• determination of the design value of the relevant resistance in fire situation at exposure time t,
Rf i,d,t ;
• verification of the fire resistance, that can be done in three different domains:
1. in time domain:
tf i,d ≥ tf i,requ (1)
2. in strength domain:
Rf i,d,t ≥ Ef i,d,t (2)
3. in temperature domain:
θd ≤ θcr,d (3)
Where,
tf i,d - is the design value of the fire resistance;
2
1 - Time domain.
2 - Strength domain.
3 - Temperature domain.
3
The analysed frames are shown in figure 2. The geometry of the frames and the reinforcement of the
critical sections satisfy the tabulated values in [5] for R60. In the following, the results of the analysis
carried out on a frame with a 6 m span beam having rectangular section and with the column heated on
one side are discussed.
With the obtained results, which are shown in figure 3, the following comments can be drawn:
• Both bending moment and shear force increase dramatically in the columns for the first 30 minutes,
because of the heating of the beam. However, no further increase is observed later on, because of
the progressive damage of the beam.
Figura 3: R/C frame with the columns exposed to fire on one side and with 6 m span beam (rectangular
section) [4].
• The bending moments in the lower columns increase approximately seven times because of the
thermal deformations of the beam (elongation and end rotation), while the bending moments in
the upper columns change sign, and their values increase more than twice of the value at ambient
temperature.
• The shear forces in the lower columns increase approximately four times with respect to ambient
conditions. As a result, the columns which are lightly reinforced in shear and not confined, may
exhibit a shear failure, as often observed during real fires.
• Neglecting the effects of beam in the design of R/C frames may lead to highly non conservative
results because of the increasing bending moments and shear forces in the columns during the first
30 minutes of fire exposure.
4
For practical applications, detailing rules for columns similar to those generally adopted in seismic
design are recommended for fire design as well. The adoption of closely spaced hoops is important
in improving section strength and ductility in combined bending and axial force, and helps controlling
concrete spalling [4].
The column exposure to fire on three sides do not shown relevant differences, except that the increase
of the bending moment and shear is less pronounced, due to the smaller temperature gradient in the
column.
4 Analysis
4.1 The building
A simplified analysis to a building that suffered a fire was conducted. The building has four floors,
the ground floor and three elevated floors. The beams and columns of the building were made with in
situ concrete and they are structurally connected. The slabs of the ground floor are solid concrete slabs
and those of the upper floors are one way slabs with pretensioned beams and ceramic blocks. On the
ground floor there is a ramp that connects to the first floor, which is used as truck’s access. This ramp
was made with concrete beams, a solid concrete slab and is monolithic to some columns.
After the real fire, the columns of the ramp were excessively damaged and so far, they did not suffer
any repair (figure 4). The connection between the slab of the ramp and the columns lead to an imposed
displacement of the columns, with the direction of the ramp, due to the expansion of the concrete resulting
from the increase of temperature during the fire.
4.2 Modelling
The structural modelling of the building was done with a commercial computer program named
SAP2000. To simulate the beams and the columns, frame elements were used. The slabs were simulated
with rectangular finite elements of Shell-Thick type and one meter side length. In the base, the columns
are considered as fully clamped.
In figure 5 is shown a tri-dimensional view of model.
The increase of temperature inside a section can be divided into two parts, one linear and one self-
equilibrated (figure 6). In turn, the linear part is divided into the sum of a constant and a linear
temperature gradient.
5
Figura 5: 3D model view.
In the analysis it was study the influence of the two previous parts separately, with the objective of
assessing the global behaviour of the structure, namely in the columns of the ground floor. Hence, two
kinds of analyses were performed (temperature variations applied to the beams or to the columns) in
three different cases. In the first case, the temperature variations were applied only to beams and then
to the slab of the ramp (figure 7). In the second case, all beams and slabs of the ground floor (ramp
and ceiling) were separately submitted to temperature variations (figure 8). Finally, in the third case,
the same elements of the second analysis were submitted to temperature variations, but considering the
building without the ramp (figure 9). Temperature variations were not applied to the upper floors since
they were only slightly affected by the fire.
6
Figura 9: Case 3.
The temperature variation part ∆T that causes the section bending failure is obtained by solving the
following equation:
7
Tabela 1: Resistance forces and moments of the columns.
The temperature variation part ∆T that causes the section shear failure is obtained by solving the
following equations:
VRd = VEd,x,(G+ψ1 Q) + ∆T × VEd,x,∆T =1o C (6)
5 Analyses results
Due to the amount of the results, it is only shown in table 2 the following points:
• The values for the occurrence of the first plastic hinge in the columns that are interrupted by the
crossing of the ramp (figures 11 and 7). These columns were more damaged with the fire than the
remaining.
• The values for the Case 2 and 3.
• The values for the application of the uniform temperature variation, because it causes higher forces
in the columns than the linear temperature gradient.
8
Tabela 2: Analyses results.
6 Conclusions
With the results of the analyses, the following comments can be made:
• The existence of a ramp monolithic with the columns in the building was the responsible factor for
the premature shear failure in the columns P10 to P13 and P16 to P19. If the ramp slab would be
repaired/replaced, it should not be monolithic with the columns this time. These columns should
be strengthened or replaced because the seismic safety of the building can be in danger.
• The results of Case 2 show the significant influence of ”short column”to the premature failure. For
Case 3, this phenomenon does not exist and the results are similar of the values for real cases [4].
• The thermal expansion of the beams and slabs exposed to fire causes a high increase of the shear
forces and bending moments in the columns. Hence, to avoid premature failures, appropriate
detailing of the reinforcement is necessary. It should be adopted closely spaced hoops, in order to
improve section strength and ductility in combined bending and axial force.
• The short columns, likely in the seismic design, should be avoided and the detailing rules for columns
for fire design should be similar to those generally adopted in seismic design.
• In case of frame design, the indirect actions arising in the structures due to thermal expansion should
be taken into consideration because the individual element analysis leads to non-conservative results.
Referências
[1] FIB - Fédération Internationale du Béton. State-of-art Report - Bulletin 38 - Fire Design of Concrete
Structures - Materials, Structures and Modelling, 2007.
[2] CEN - Comité Européen de Normalisation. EN 1991-1-2, Eurocode 1: Actions on structures - Part
1-2: General actions - Actions on structures exposed to fire, April 2002.
9
[3] VILA REAL, Paulo M. M. Incêndio em Estruturas Metálicas - Cálculo Estrutural. Edições Orion,
2003.
[4] TAERWE, Luc. From member design to global structural behaviour. Proceedings of the International
Workshop: Fire Design of Concrete Structures - From Materials Modelling to Structural Permor-
mance, Coimbra, Portugal, 2007.
[5] CEN - Comité Européen de Normalisation. EN 1992-1-2, Eurocode 2: Design of concrete structures
- Part 1-2: General rules - Structural fire design, December 2003.
10