Académique Documents
Professionnel Documents
Culture Documents
ABSTRACT: Push-out tests were conducted to investigate the shear performance of FRP perfobond shear
connectors. Shear failure was observed on the ribs of connectors at ultimate. Based on test results, the FRP
perfobond connectors showed relatively high shear capacity and could be applied to the FRP-concrete com-
posite deck. Then the simply supported FRP-concrete composite deck with FRP perfobond shear connectors
was tested under monotonic load. The load versus mid-span deflection response of composite deck behaved
linearly up to the ultimate load. Shear failure occurred on the webs of FRP deck near the upper flange, while
the FRP perfobond shear connectors remained intact without any damage. The measured maximum mid-span
deflection was 25.4 mm, corresponding to 1/63 of the simply supported span, which demonstrated the large
deformability of FRP-concrete composite deck.
Ribs
Figure 4. Shear failure on ribs of perfobond shear connectors
slip between the FRP deck and concrete slab. For 100
FRP deck
The measured load versus slip curves of push-out
specimens exhibit the elastic stage and plastic stage
under loading. As the applied loads were less than
20 0.2 time the ultimate loads, specimens showed an
hole
P almost linear-elastic responses, and the slip between
GFRP the FRP deck and concrete slab was small. Some
rebars
fine damage might begin to form at the FRP per-
fobond shear connectors when the applied loads
reached 0.2 time the ultimate loads, and the stiffness
of FRP perfobond shear connectors decreased as the
applied loads increased. The load versus slip curves
Foamed plastic are nonlinear after 0.2 time the ultimate loads. At ul-
timate, the relative slip developed rapidly with little
Figure 2. Details of push-out Figure 3. Test setup increase of applied loads.
specimen
2.2.3 Load versus strain curves
2.2 Test results and analysis Fig. 6 and Fig. 7 show the measured load versus
strain curves of specimens. Note ε1 and ε2 denote the
normal strain parallel to and perpendicular to the di-
2.2.1 Failure pattern rection of loading, respectively, and γ12 denotes the
Shear failure on the ribs of FRP perfobond shear converted shear strain. Seen from the figures:
connectors was observed in the push-out tests, as (1) The load versus strain curves are similar for
shown in Fig. 4. During test loading, no damage oc- the two specimens. The strains on ribs of FRP per-
curred on the surrounding concrete and the GFRP fobond connectors developed linearly up to 0.4 time
rebars installed through the holes. the ultimate loads. When shear failure occurred, the
shear strains on ribs of FRP perfobond connectors
are 8113 με and 7898 με, respectively.
(2) The normal strains measured at the same posi- distances of 200 mm from the center of the compos-
tion are much smaller than the shear strains, which ite deck.
indicates that the FRP perfobond connectors are
mainly subjected to the shear forces in the push-out
tests. P
East West
Neoprene pad
10mm Concrete slab
200 250
200
Neoprene pad
160 100
ε2 ε1 γ12 100 10mm
ε1
120 150 ε2 γ12
P /kN FRP deck
P /kN
80 100
40 50
Figure 8. Loading configuration
0 0
-2000 0 2000 4000 6000 8000 10000 -3000 0 3000 6000 9000
Strain/με Strain/με
Figure 6. Load versus strain Figure 7. Load versus strain 3.2 Overall response
curves of PS-1 curves of PS-2
The initial cracking was observed at the bottom of
concrete slab beneath the west load point when the
2.2.4 Shear capacity
applied load, P, increased to about 0.1 time the ulti-
The measured ultimate loads were 173.1 kN and
mate load, Pu. The formed cracks propagated up-
203.3 kN for specimen PS-1 and PS-2, respectively.
wards and several new cracks developed within the
Based on the test results, the shear failure on ribs of
constant moment region as the applied load in-
FRP perfobond shear connectors was observed. So
creased. Under the load of 0.7Pu, the relative slip be-
the load carrying capacity of push-out specimens
tween the FRP deck and concrete slab was 0.6mm
was mainly controlled by the shear capacity of FRP
and the sounds of fiber fracture from FRP deck
perfobond connectors, Ps, which can be calculated
could be heard sporadically. The relative slip be-
by:
tween the FRP deck and concrete slab was increased
Ps u Asn (1) to about 1.1 mm at ultimate, and the measured shear
stresses on FRP webs were 52.4 MPa, which ex-
where u = shear strength of ribs (MPa); Asn = total ceeded the shear strength of FRP deck obtained from
area of ribs with deducting the area of holes (mm2). the tests of mechanical properties. Fig. 9 shows the
The predicted shear capacity of FRP perfobond con- failure pattern of FRP-concrete composite deck.
nectors is 243.0 kN according to Eq. (1), which is Shear failure occurred on the webs of FRP deck near
higher than the measured ultimate loads. It may be the upper flange accompanied with a loud sound,
due to the fact that FRP perfobond connectors were while the FRP perfobond shear connectors remained
under the combined forces of shear and flexure in intact without any damage.
push-out test. Based on test results, the FRP per-
fobond connectors showed promising behaviors and
could be used to the FRP-concrete composite deck.
0.6Pu
P /kN
80 0.8Pu 80
60
40
1.0Pu
40
the normal strains developed linearly under the ap-
20
0
plied loads, while some nonlinear characteristics
0
-4000 -2000 0 2000 4000 6000
0 10 20 30 could be observed in the response of load versus
Strain/με Deflection /mm
shear strain. In addition, the shear strains are higher
than the normal strains at the position, which may be
Figure 10. Strain distributions Figure 11. Load versus
of mid-span section deflection curves caused by the fact that webs of FRP deck mainly re-
sist the shear forces. The shear strains developed in
3.3.2 Load versus deflection curves the web of FRP deck were 10691 με at ultimate load,
As illustrated in Fig. 11, the measured curves of load and the corresponding shear stresses were 52.4 MPa,
versus deflection at mid-span behave linearly up to which led to the shear failure on webs of FRP deck.
Pu. The initial concrete crack was observed at about
0.1Pu, while it seemed that the concrete cracking had 160
P /kN
80
160
4 CONCLUSION
160
120 120
s3 The following conclusions can be drawn from the
P /kN
s2
P /kN
s1 80
80
experimental studies:
40 40
(1) Shear failure on the ribs of FRP perfobond
0 0
0 0.3 0.6 0.9 1.2 0 1400 2800 4200 5600 shear connectors was observed in the push-out tests,
Slip /mm
Strain/με while no damage occurred on the surrounding con-
crete and the GFRP rebars installed through the
Figure 12. Load versus slip Figure 13. Strains developed
holes. The FRP perfobond connectors showed prom-
curves at the bottom of FRP deck
ising behaviors and could be used to the FRP-
3.3.4 Strains developed in FRP deck concrete composite deck.
As shown in Fig. 13, the longitudinal strains at the (2) For the FRP-concrete composite deck, shear
bottom of FRP deck in mid-span section are in- failure occurred on the webs of FRP deck near the
creased linearly up to the ultimate load. The meas- upper flange at ultimate, and the FRP perfobond
ured strains of FRP deck web at the distance of 330 shear connectors remained intact without any dam-
mm from the specimen center and at the distance of age. The strains approximately exhibit a linear dis-
15 mm from the FRP deck upper flange are shown in tribution along the height of section, and the average
Fig. 14, where ε1 and ε2 represent the normal strain relative slip reached 2.5 mm under the ultimate load.
The measured mid-span deflection was 25.4 mm at
ultimate, corresponding to 1/63 of the simply sup-
ported span, which demonstrates the large deform-
ability of FRP-concrete composite deck.
ACKNOWLEDGMENTS
REFERENCES