Designing of Compressor

Data:

QFreezingTank , Tons of Refrigeration = 456.43 TR

QIceStorage , Tons of Refrigeration = 312.98 TR

Refrigerant = R717 - Ammonia

Ice Evaporating Temperature = 5℉

Condenser Temperature = 104℉

Storage Evaporating Temperature = -10℉

Storage Condensing Temperature = 40℉

For Freezing Tank:

From the Table of R717-Ammonia:

h1 = hg @ 5℉ = 613.135 Btu/lb

h3= hf @ 104℉= 159.8151 Btu/lb

v1 = vg at 5℉= 8.1483 ft3/lb

From Mollier Diagram of R717-Ammonia:

h2 = h at 1168.6 kPa and s2 equal to s1 = 681 Btu/lb

Work of Compressor in the Freezing Tank:

To solve for the mass flow rate of the refrigerant

Qe = m (h1-h3)
𝑄𝑒
m=
ℎ1 −ℎ3
𝐵𝑡𝑢/𝑚𝑖𝑛
200
𝑘𝑔
456.43 𝑇𝑅 𝑥
1 𝑇𝑅
m= 𝐵𝑡𝑢 𝐵𝑡𝑢
613.135 −159.8151
𝑙𝑏 𝑙𝑏

𝑙𝑏 1 𝑚𝑖𝑛
m = 201.3721 x
𝑚𝑖𝑛 60 𝑠

𝑙𝑏
m = 3.3562
𝑠

V1 = m (v1)
𝑙𝑏
V1 = 3.3562 (8.1483 ft3/lb)
𝑠

V1 = 27.3473 ft3/s

Solving for the Compressor Work

Wc1 = m (h2 – h1)

𝑙𝑏
Wc1 = 3.3562 (681 Btu/lb – 613.135 Btu/lb)
𝑠

Wc1 = 227.7685 Btu/s

Solving for the Bore & Stroke


For Ice Storage

From the Table of R717-Ammonia:

h1 = hg @ -10℉ = 608.257 Btu/lb

h3= hf @ 40℉ = 86.6765 Btu/lb

v1 = vg at -10℉ = 11.502 ft3/lb

From Mollier Diagram of R717-Ammonia:

h2 = h at 1168.6 kPa and s2 equal to s1 = 682 Btu/lb

Work of Compressor in the Ice Storage:

To solve for the mass flow rate of the refrigerant

Qe = m (h1-h3)
𝑄𝑒
m=
ℎ1 −ℎ3

𝐵𝑡𝑢/𝑚𝑖𝑛
200
𝑘𝑔
312.98 𝑇𝑅 𝑥
1 𝑇𝑅
m= 𝐵𝑡𝑢 𝐵𝑡𝑢
608.257 − 86.6765
𝑙𝑏 𝑙𝑏

𝑙𝑏 1 𝑚𝑖𝑛
m = 120.0122 x
𝑚𝑖𝑛 60 𝑠

𝑙𝑏
m = 2.0
𝑠

V1 = m (v1)

𝑙𝑏
V1 = 2.0 (11.502 ft3/lb)
𝑠

V1 = 23.004 ft3/s

Solving for the Compressor Work

Wc2 = m (h2 – h1)


𝑙𝑏
Wc2 = 2.0 (682 Btu/lb – 608.257 Btu/lb)
𝑠

Wc2 = 147.486 Btu/s