Académique Documents
Professionnel Documents
Culture Documents
-1-
iPASOLINK 400
SECTION III MAINTENANCE
CONTENTS
CONTENTS ............................................................................................................................- 1 -
1. General .......................................................................................................................... 1-1
2. Precaution .................................................................................................................... 2-1
2.1 Maintenance and Operation Manual ....................................................................................... 2-4
2.1.1 Wrist Strap Connection.................................................................................................... 2-4
2.1.2 Maintenance Mode Setting (for the LCT Operation) ........................................................ 2-4
2.1.3 Manual Switch Operation ................................................................................................ 2-9
3. Current Status .............................................................................................................. 3-1
3.1 Current Status......................................................................................................................... 3-1
4. Routine Maintenance ................................................................................................... 4-1
4.1 Meter Reading ........................................................................................................................ 4-1
4.2 Performance Monitoring ......................................................................................................... 4-3
4.2.1 PM Parameters ............................................................................................................... 4-3
4.2.1.1 PM Status Monitor Types ....................................................................................... 4-3
5. Corrective Maintenance .............................................................................................. 5-1
5.1 Alarm/Status ........................................................................................................................... 5-2
5.1.1 Alarm Management ......................................................................................................... 5-7
5.1.1.1 Alarm Class............................................................................................................ 5-7
5.1.2 Alarm and Status Indication Detail .................................................................................. 5-8
5.1.2.1 ODU Alarms & Status ............................................................................................ 5-8
5.1.2.2 MODEM-A/EA Alarms & Status ............................................................................. 5-9
5.1.2.3 STM1-A Option Card Alarms & Status ................................................................. 5-10
5.1.2.4 16E1-A Option Card Alarms & Status .................................................................. 5-12
5.1.2.5 AUX-A Option Card Alarms & Status ................................................................... 5-12
5.1.2.6 GbE-A Option Card Alarms & Status ................................................................... 5-13
5.1.2.7 MSE-A Option Card Alarms & Status................................................................... 5-13
5.1.2.8 PTP-A Option Card Alarms & Status ................................................................... 5-14
5.1.2.9 MC-A4 Alarms & Status ....................................................................................... 5-15
5.1.2.10 Radio Traffic Aggregation Link Alarm .................................................................. 5-17
5.1.2.11 ETH GRP Alarm ................................................................................................... 5-17
5.1.2.12 IEEE802.3ah Alarm ............................................................................................. 5-17
Maintenance NWD-115477-06E
September, 2013
Submission Prohibited
NEC Group Internal Use Only
-2-
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
-3-
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
-4-
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
-5-
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
-6-
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
-7-
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
- 8 -/END
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
General 1-1
1. GENERAL
This section provides information on routine and corrective maintenance for the
iPASOLINK used for 7 to 42 GHz PDH/SDH/Packet digital radio system.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
1-2/END General
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Precaution 2-1
2. PRECAUTION
The maintenance personnel should report arrival and departure from a station to the
relevant station. The following precaution must be carefully observed during
maintenance.
Warning
1. The -48V DC power is superimposed on the center conductor of the coaxial
cable between the IDU and the ODU. Connecting test equipment directly to
this terminal may damage it and touching the coaxial cable core may cause
electrical shock.
2. Persons performing maintenance must take necessary steps to avoid
Electrostatic Discharge (ESD) which may damage the cards on the IDU or
cause error. Wear a conductive wrist strap connected to the grounded (G)
jack on the front of the equipment shelf. This will minimize static build-up
during maintenance.
3. Turn off the "ODU PWR" switch on the IDU before connecting/disconnecting
the IF cable to avoid the equipment damaged.
4. After turning ON the equipment, wait at least 1 minute before turning it OFF
again. Repeatedly turning the power ON and OFF within a short interval may
cause the equipment damaged.
5. Do not allow open or short circuit ODU TX output with the TX power on
conditions. Perform the TX Mute control in the Maintenance mode or turn the
“ODU PWR” switch off at the IDU before disconnecting cable or feeder from
the ODU TX output.
Caution
1. In a system using the optical STM-1 INTFC, do not stare at the laser beam
or look at it directly with optical instruments. Otherwise, it may hurt your eyes
(Class 1 laser product).
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
2-2 Precaution
6. While the CPU is initialized by the CPU RESET switch, alarm(s) status is
reset to normal. After initialized, the alarm information is properly provided
through relay contacts.
7. Information on the maintenance and the control such as Mute, CW, LB, etc.
is released if the power is turned off.
8. If each setup item of NE SETUP or SYSTEM OPERATION is changed
during operation, traffic will be momentarily interrupted.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Precaution 2-3
Straight Type
Tighten the TNC-male connector of IF cable to the IDU with engage connector nut
only using fingers and holding the cable with another hand.
L-angle Type
Tighten the engage connector nut only for the L-angle connector also.
(Tightening Torque: 0.3 to 0.5 N-m (3 to 5 kg-cm))
If you rotate other parts of the L-angle connector as illustrated left, it may cause
connector damage.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
2-4 Precaution
Procedure 2-1
Procedure 2-2
2. Confirm that the MAINT on the top of the LCT window becomes yellow.
Maintenance Button
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Precaution 2-5
3. Confirm that the MAINT LED at the front of the equipment becomes yellow.
(1) MC-A4
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
2-6 Precaution
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Precaution 2-7
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
2-8 Precaution
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Precaution 2-9
ERP Control
Note: This item is supported when the configuration is set to 1+1 Hot Standby
mode only.
Ex: MODEM No.1 and No.2 are constructed as 1+1 Hot Standby mode
and MODEM No.1 acts as working side. MODEM No.2 acts as standby
side.
Procedure 2-3
1. Click the Maintenance button on the top of the LCT window to turn on the
maintenance mode.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
2-10 Precaution
5. The MODEM TX/RX Switch Control window appears. Click SW GRP No. in
the TX SW Manual Control field.
7. Click OK button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Precaution 2-11
10. The MODEM TX / RX Switch Control window appears again. Confirm the
parameters displayed.
11. Click the Maintenance button on the top of the LCT window to exit the
maintenance mode.
12. Confirm that the MAINT color changes from yellow to white.
Note: This item is supported when the configuration is set to 1+1 Twin
Path/Hot Standby mode only.
For example, MODEM No.1 and No.2 are constructed as 1+1 Twin Path
mode and MODEM No.1 acts as working side. MODEM No.2 acts as
standby side.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
2-12 Precaution
Procedure 2-4
1. Click the Maintenance button on the top of the LCT window to turn on
maintenance mode.
7. Click OK button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Precaution 2-13
10. The MODEM TX / RX Switch Control window appears again. Confirm the
parameters displayed.
11. Click the Maintenance button on the top of the LCT window to exit
maintenance mode.
12. Confirm that the MAINT color changes from yellow to white.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
2-14 Precaution
Procedure 2-5
1. Click the Maintenance button on the top of the LCT window to turn on
maintenance mode.
4. Select LAG Revert Control from the Protection Control sub menu.
5. The LAG Revert Control window appears. Click the desired LAG to
configure.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Precaution 2-15
9. The LAG Revert Control window appears again. Confirm the parameters
displayed.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
2-16 Precaution
10. Click the Maintenance button on the top of the LCT window to exit
maintenance mode.
11. Confirm that the MAINT color changes from yellow to white.
Procedure 2-6
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Precaution 2-17
5. The ERP Control (Loop Detection Restart) box appears. Select the Ring
ID to Restart. Click Execute button.
Procedure 2-7
1. Click the Maintenance button on the top of the LCT window to turn on
maintenance mode.
4. Select RSTP / MSTP Control from the Protection Control sub menu.
5. The RSTP / MSTP Control window appears. Click RSTP Clear button.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
2-18 Precaution
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Precaution 2-19
8. The RSTP / MSTP Control window appears again. Confirm the parameters
displayed.
9. After finishing RSTP Control, click the Maintenance button on the top of the
LCT window to exit maintenance mode.
10. Confirm that the MAINT color changes from yellow to white.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
2-20 Precaution
Procedure 2-8
1. Click the Maintenance button on the top of the LCT window to turn on
maintenance mode.
4. Select SNCP Switch Control from the Protection Control sub menu.
5. The SNCP Switch Control window appears. Click the desired number to
configure.
6. The SNCP Switch Control box appears. Select the parameter from the SNCP
Manual SW Control drop-down list.
7. Click OK button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Precaution 2-21
10. The SNCP Switch Control window appears again. Confirm the parameters
displayed.
11. Click Maintenance button on the top of the LCT window to exit maintenance
mode.
12. Confirm that the MAINT color changes from yellow to white.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
2-22 Precaution
Procedure 2-9
1. Click the Maintenance button on the top of the LCT window to turn on
maintenance mode.
4. Select APS Switch Group Control from the Protection Control sub menu.
5. The APS Switch Group Control window appears. Click the desired number
to configure.
7. Click OK button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Precaution 2-23
10. The SNCP Switch Control window appears again. Confirm the parameters
displayed.
11. Click the Maintenance button on the top of the LCT window to exit
maintenance mode.
12. Confirm that the MAINT color changes from yellow to white.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
2-24 Precaution
(8) Timing Source Switch Control (This mode available when the Lock
Out is Off only)
In case that Lock Out Status is set to On, follow the Procedure 2-8 to change the
setting to Off and then follow the Procedure 2-9 to configure Timing Source
Switching.
Procedure 2-10
1. Click the Maintenance button on the top of the LCT window to turn on
maintenance mode.
4. Select Timing Source Switch Control from the Protection Control sub
menu.
5. The Timing Source Switch Control window appears. Click desired Lock
Out to configure.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Precaution 2-25
6. The Timing Source Switch Control box appears. Click Off radio button
from Lock Out.
7. Click OK button.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
2-26 Precaution
10. The Timing Source Switch Control window appears again. Confirm the
displayed parameters.
11. After finishing Lock Out Setting, click the Maintenance button on the top of
the LCT window to exit maintenance mode.
12. Confirm that the MAINT color changes from yellow to white.
Procedure 2-11
1. Click the Maintenance button on the top of the LCT window to turn on
maintenance mode.
4. Select Timing Source Switch Control from the Protection Control sub
menu.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Precaution 2-27
5. The Timing Source Switch Control window appears. Click the desired
Timing Source SW Control to configure.
6. The Timing Source Switch Control box appears. Select switching mode
(Manual SW or Forced SW).
7. Click OK button.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
2-28 Precaution
10. The Timing Source Switch Control window appears again. Confirm the
displayed parameters.
11. Click the Maintenance button on the top of the LCT window to exit
maintenance mode.
12. Confirm that the MAINT color changes from yellow to white.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Precaution 2-29
(9) PTP Master Source Switch Control (available only when PTP Lock
Out is set to off)
If the PTP Lock Out Status is set to On, change its setting to Off by referring to
Procedure 2-12, then proceed to Procedure 2-13 to configure the PTP Timing
Source Switching.
Procedure 2-12
1. Click the Maintenance button on the top of the LCT window to turn on
maintenance mode.
3. Select PTP Domain Control from the Maintenance Control sub menu.
4. The PTP Domain Control window appears. Click desired Lock Out to
configure.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
2-30 Precaution
5. The PTP Lock out option window appears. Click the Off radio button, then
click the OK button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Precaution 2-31
7. The PTP Domain Control window updates the information. Confirm the
displayed parameters.
8. When completing the PTP Lock Out Setting, click the Maintenance button on
the top of the LCT window to exit the maintenance mode.
9. Confirm that the MAINT indication color changes from yellow to white.
Procedure 2-13
1. Click the Maintenance button on the top of the LCT window to turn on
maintenance mode.
3. Expand PTP Domain Control from the Maintenance Control sub menu.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
2-32 Precaution
4. The PTP Domain Control window appears. Click the desired PTP SW
Control to configure.
5. The PTP Switch Control option window appears. Select switching mode
(Normal or Forced SW).
6. Click OK button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Precaution 2-33
8. The PTP Domain Control window updates the information. Confirm the
displayed parameters.
9. Click the Maintenance button on the top of the LCT window to exit
maintenance mode.
10. Confirm that the MAINT color changes from yellow to white.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
2-34/END Precaution
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
3. CURRENT STATUS
But it is just for viewing system status only you can not make any changes of all
items displayed on this window. (Such as modify, adding, masking alarms or items)
The Active Alarm tab displays all current alarms detected on the equipment
side.
You can download the current alarm list to LCT PC by clicking the Save
button on the top left of the Active Alarm tab.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
The Event Log tab displays all alarms and status detected when there are
any changes on the line card and configuration on equipment.
You can download the Event Status list to the LCT PC by clicking the Save
button on the top left of the Event Log tab.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
3. The Save As window appears. Select the proper folder of the Local PC, and
then click Save button.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
4. After finishing the export of log file, the Download Complete window
appears. Click Close button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
The MODEM/ODU tab displays all alarm and status detected on MODEM
card and ODU.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
The IDU tab displays all alarms and status detected on IDU.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
(5) E1 Tab
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
(b) U-Slot**
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
The STM-1 tab displays all alarms and status detected on STM1-A.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
The GbE tab displays all alarms and status detected on GbE-A.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
4. ROUTINE MAINTENANCE
This chapter provides the routine (annually) maintenance procedures to ensure the
satisfactory operation of the equipment. During routine maintenance, carefully
observe the precautions given in Chapter 2.
Procedure 4-1
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
Notes
1. If an abnormal indication appears, check Alarm/Status, performance monitor
and perform loopback test to distinguish sections of normal and alarmed.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
4.2.1 PM Parameters
Performance Monitor Parameters can be measured from iPASOLINK.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
5. CORRECTIVE MAINTENANCE
Faults can be classified in to those that cause deterioration of the transmission quality
and those that interrupt the traffic due to a malfunction of the equipment. This
chapter explains the troubleshooting procedures for equipment faults and the
corresponding remedial methods. The purpose of troubleshooting malfunctioning
equipment is to restart the service by locating the faulty part and replacing it with a
spare.
The faults that cause deterioration quality are primarily originated by changes
occurred in the state of propagation. Therefore, if a decline in the transmission
quality or similar fakes place frequently, the link design will have to be reviewed.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
5.1 Alarm/Status
When an alarm event has occurred, at first, check alarm indication on the front of the
IDU. Continuously, connect the PC to the LOCAL jack on the LCT port mounted on
the IDU and check alarm/status indication.
A faulty part can be located by checking the alarm LED indications and LCT Alarm
indications.
Alarm Report
When an alarm is detected, alarm notification is made to the user by lighting
up the LEDs on the rack, and reporting the alarm to user interface. The alarm
notification is also made to the user by an Office alarm, such as the station
alarm bell and lamps.
(1) MC-A4
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
Web-LCT indication
The alarm LED indications and PNMT indication faulty part can be located
by checking the ALM LED indicators and Web-LCT Alarm indications.
Meter Reading
Loopback
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
The alarm severity of each failure is indicated by the following alarm level and alarm
class. Alarm classes can be modified. Modification is done by Alarm Severity
Setting.
Critical (CR) :
The Critical severity level indicates that a service affecting condition has occurred
and an immediate corrective action is required. Such a severity can be reported, for
example, when a managed object becomes totally out of service and its capability
must be restored.
Major (MJ):
The Major severity level indicates that a service affecting condition has developed
and an urgent corrective action is required. Such a severity can be reported, for
example, when there is a severe degradation in the capability of the managed object
and its full capability must be restored.
Minor (MN):
The Minor severity level indicates the existence of a non-service affecting fault
condition and that corrective action should be taken in order to prevent a more
serious (for example, service affecting) fault. Such a severity can be reported, for
example, when the detected alarm condition is not currently degrading the capacity
of the managed object.
Warning (WR):
The Warning severity level indicates the detection of a potential or impending
service affecting fault, before any significant effects have been felt. Action should be
taken to further diagnose (if necessary) and correct the problem in order to prevent it
from becoming a more serious service affecting fault.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
6. CONTROL ITEMS
Following control items are available when the maintenance mode is only set to on.
Be careful during the operation on these control items because there is possibility to
be traffic affected during operation.
Loopback Control
- IF Loopback Control
- L2 Loopback Control (Loopback1/Loopback2)
- TDM Loopback Control (E1 Loopback1/ Loopback2)
- TDM Loopback Control (STM-1 Loopback1/ Loopback2)
- Link OAM Loopback Control
Database Upload/Download
- HW Reset Control
- FW Reset Control
Radio Control
License Management
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
Following is the control items list that does not relate to traffic.
Inventory Information
Performance Monitor
Offline Maintenance
- Data Adjust
- RF Sub Band Select
6.1 Loopback
When there is an interruption of signals, use the SDH/SONET/PDH/packet analyzers
and isolate the faulty section by checking the traffic signal using loopback.
When executing the loopback control, set Maintenance Mode to ON and do not
release Maintenance Mode while controlling loopback.
6.1.1 IF Loopback
In the IF loopback, the incoming of traffic signal is looped back is toward the line
interface direction in the MODEM interface.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Notes
*1 The MOD ALM and TX INPUT ALM will be un-masked as soon as
releasing the IF Loopback operation.
*2 If the remote control connected at opposite side, the remote control will
be disconnected while the IF Loopback is executed and does not restore
in default. So, it is necessary to set the IF Loopback Release Time to
release IF Loopback automatically before executing the IF Loopback.
6.1.1.1 IF Loopback
Important:
To operate the Loopback Control, the system must be set into the
Maintenance mode; Do not cancel the Maintenance mode while operating
the Loopback Control.
Procedure 6-1
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Expand the Loopback Control from the Maintenance Control sub menu.
4. Select the MODEM Loopback Control from the Loopback Control sub
menu.
5. The MODEM Loopback Control window appears. Click Off at the specified
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
6. The MODEM Loopback Control box appears. Click On radio button of the
IF Loopback.
7. Click OK button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
10. The MODEM Loopback Control window appears again. Confirm that the
status of IF Loopback of specified MODEM indicates On.
11. After finishing loopback test, click Maintenance button on the top of the LCT
window to exit maintenance mode.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
12. Confirm that the MAINT color changes from orange to white.
Procedure 6-2
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Expand the Loopback Control from the Maintenance Control sub menu.
4. Select the MODEM Loopback Control from the Loopback Control sub
menu.
5. The MODEM Loopback Control window appears. Click Off at the specified
MODEM No. (or SW GRP) of IF Loopback field.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
6. The MODEM Loopback Control box appears. Click On radio button of the
IF Loopback.
7. Click OK button.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
11. The MODEM Loopback Control window appears again. Confirm that the
status of IF Loopback of specified MODEM indicates On.
12. When the loopback test ends, click Maintenance tool button on the WebLCT
tool bar to exit from the Maintenance Mode.
13. Confirm that the MAINT color changes from orange to white.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
6.1.2 L2 Loopback
This function is layer2 level loopback. Incoming Layer2 frames are looped to the
source direction with MAC Destination and Source Address swap. Two loopback
modes are supported. The Loopback1 mode loops frames to ETH interface direction.
The Loopback2 mode loops frames to ODU.
Procedure 6-3
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Expand the Loopback Control from the Maintenance Control sub menu.
4. Select the MODEM Loopback Control from the Loopback Control sub
menu.
5. The MODEM Loopback Control window appears. Click Off at the specified
MODEM No. (or SW GRP) of L2 Loopback field.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
7. Click OK button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
10. The MODEM Loopback Control window appears again. Confirm that the
status of L2 Loopback of specified MODEM indicates Loopback1( or 2).
11. After finishing loopback test, click Maintenance button on the top of the LCT
window to exit maintenance mode.
12. Confirm that the MAINT color changes from orange to white.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
Execute the TDM Loopback Control (E1 Loopback1) for checking the incoming of
E1 traffic signal inside E1 interfaces (The traffic signal from outside to E1 interfaces
direction).
Note: During executing Loopback, the AIS will be detected at down stream of
the specified channel (Loopback channel).
Important:
1. To operate the Loopback Control, the system must be set into the
Maintenance mode; Do not cancel the Maintenance mode while
operating the Loopback Control.
Procedure 6-4
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Expand the Loopback Control from the Maintenance Control sub menu.
4. Select the TDM Loopback Control (E1 Loopback1) from the Loopback
Control sub menu.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
5. The TDM Loopback Control (E1 Loopback1) window appears. Click Off
at the specified E1 Loopback1 channel from the MC-A4 field.
6. The TDM Loopback Control (E1 Loopback) box appears. Click On radio
button of the specified E1 Loopback CH**.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
7. Click OK button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
10. The TDM Loopback Control window appears again. Confirm that the status
of the specified CH indicates On.
11. After finishing loopback test, click Maintenance button on the top of the LCT
window to exit maintenance mode.
12. Confirm that the MAINT color changes from orange to white.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
Execute the TDM Loopback Control (E1 Loopback2) for checking the incoming of
E1 traffic signal through MODEM IF (The traffic signal from wireless to E1
interfaces direction).
Remote login to the opposite site NE and execute Loopback2 at opposite site NE.
Note: During executing Loopback, the AIS alarm will be detected at down
stream of the specified channel (Loopback channel).
Important:
To operate the Loopback Control, the system must be set into the
Maintenance mode; Do not cancel the Maintenance mode while
operating the Loopback Control..
Procedure 6-5
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Expand the Loopback Control from the Maintenance Control sub menu.
4. Select the TDM Loopback Control (E1 Loopback2) from the Loopback
Control sub menu.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
5. The TDM Loopback Control (E1 Loopback2) window appears. Click Off
at the specified E1 Loopback2 Channel from the MC-A4 field.
6. The TDM Loopback Control (E1 Loopback2) box appears. Click On radio
button of the specified E1 Loopback2 CH**.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
7. Click OK button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
10. The TDM Loopback Control window appears again. Confirm that the status
of the specified CH indicates On.
11. After finishing loopback test, click Maintenance button on the top of the LCT
window to exit maintenance mode.
12. Confirm that the MAINT color changes from orange to white.
Execute the TDM Loopback Control (STM-1 Loopback1) for checking the incoming
of TDM traffic signal inside STM-1 interfaces (The traffic signal from outside to
STM-1 interfaces direction).
Note: During executing Loopback, the AIS will be detected at down stream of
the specified channel (Loopback channel).
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
Important:
To operate the Loopback Control, the system must be set into the
Maintenance mode; Do not cancel the Maintenance mode while
operating the Loopback Control.
Procedure 6-6
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Expand the Loopback Control from the Maintenance Control sub menu.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
7. Click OK button.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
10. The TDM Loopback Control window appears again. Confirm that the status
of STM-1 Loopback1 Port** indicates On.
11. After finishing loopback test, click Maintenance button on the top of the LCT
window to exit maintenance mode.
12. Confirm that the MAINT color changes from orange to white.
Execute the TDM Loopback Control (STM-1 Loopback2) for checking the incoming
of TDM traffic signal through MODEM IF (The traffic signal from wireless to
STM-1 interfaces direction).
Remote login to the opposite site NE and execute STM-1 Loopback2 at opposite site
NE.
Note: During executing Loopback, the AIS will be detected at down stream of
the specified channel (Loopback channel).
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Important:
To operate the Loopback Control, the system must be set into the
Maintenance mode; Do not cancel the Maintenance mode while
operating the Loopback Control..
Procedure 6-7
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Expand the Loopback Control from the Maintenance Control sub menu.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
7. Click OK button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
10. The TDM Loopback Control window appears again. Confirm that the status
of STM-1 Loopback2 Port** indicates On.
11. After finishing loopback test, click Maintenance button on the top of the LCT
window to exit maintenance mode.
12. Confirm that the MAINT color changes from orange to white.
Before loopback test, setup Link OAM referring to Link OAM tab, ETH OAM
Setting in the Operation manual.
iPASOLINK400
iPASOLINK400
(IDU)
(IDU)
MODEM#2
MODEM#2
MODEM#1
MODEM#1
Main board
Main board
Ethernet Port
Ethernet Port
Loop
Loopback back
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
Procedure 6-8
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Expand the Loopback Control from the Maintenance Control sub menu.
4. Select the Link OAM Loopback Control from the Loopback Control sub
menu.
5. The Link OAM Loopback Control window appears. Click Off at the
Loopback Status field.
6. The Link OAM Loopback Control box appears. Click On radio button of the
specified Link OAM Loopback.
7. Click OK button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
10. The Link OAM Loopback Control window appears again. Confirm that the
status of Loopback Status indicates On.
11. After finishing loopback test, click Maintenance button on the top of the LCT
window to exit maintenance mode.
12. Confirm that the MAINT color changes from orange to white.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
Provisioning Clear
Use this function to clear Provisioning setting from Configuration Data.
Date/Time Setting
Use this function to set the NE date and time.
Procedure 6-9
2. Select the Export (NE->Storage) Utility from the Equipment Utility sub
menu.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
5. The Save As window appears. Select the specified directory on the specified
device (local PC/USB memory) and then click Save button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
7. After the upload process is finished, open the export destination (folder) on
specified device (local PC or USB memory) to confirm whether the data has
been uploaded correctly or not.
*1 Connect USB memory to the USB port at the front of iPASOLINK and the
operation is on LCT.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
This function is used for downloading F/Ws from local PC or USB memory to
the targets. (Main Board, ODU, PTP-A)
This function is used for downloading FPGA from local PC or USB memory to
the target cards.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
This function is used to update the MODEM parameter file on the MODEM
module.
Important:
1. Confirm that you have IDU Main Board / ODU / PTP-A Program File that is
provided from NEC.
2. Confirm the current version of IDU Main Board / ODU / PTP-A Program File
from the IDU tab of Equipment Inventory Information window.
3. Turn ON the Maintenance Mode before downloading IDU Main Board / ODU
/ PTP-A Program File. Do not release Maintenance Mode while
downloading.
Procedure 6-10
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Select the Update (Storage->NE) Utility from the Equipment Utility sub
menu.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
5. The Update (Storage->NE) Utility box appears. Select the Main Card /
PTP-A from drop-down list and then click Next button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
7. The file selection window appears. Select the Main Board / PTP-A firmware file
and then click Open (or OK) button.
Local PC
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
USB Memory
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
11. After the download is completed, the Update Complete! window appears.
Check the Program ROM Switching check box and then click OK button.
12. The Warning box appears. Click OK button. iPASOLINK will be restarted
automatically.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
13. The Information box appears. Click OK button. The WebLCT will shut down
automatically.
15. Select the Inventory (Equipment Inventory Information) from the LCT
menu.
16. The Equipment Inventory Information (IDU) window appears. Confirm the
Current version (new program running version) of Main Board / PTP-A.
17. After finishing Program File download, click Maintenance button on the top of
the LCT window to exit maintenance mode.
18. Confirm that the MAINT color changes from orange to white.
(b) ODU
Important:
1. Confirm that you have ODU Program File that is provided from NEC.
2. Confirm the current version of ODU Program File from the ODU tab of the
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Procedure 6-11
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Select the Update (Storage->NE) Utility from the Equipment Utility sub
menu.
5. The Update (Storage->NE) Utility box (1/2) appears. Select the ODU from
drop-down list and then click Next button.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
6. The Update (Storage->NE) Utility box (2/2) appears. Select the MODEM
from drop-down list and then click Next button.
8. The file selection window appears. Select the ODU firmware file and then click
Open (or OK) button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Local PC
USB Memory
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
12. After the download is completed, the Update Complete! window appears.
Check the Program ROM Switching check box and then click OK button.
13. The Warning box appears. Click OK button. iPASOLINK will be restarted
automatically.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
14. The Information box appears. Click OK button. The WebLCT will shut down
automatically.
16. Select the Inventory (Equipment Inventory Information) from the LCT
menu.
18. After finishing Program File download, click Maintenance button on the top of
the LCT window to exit maintenance mode.
19. Confirm that the MAINT color changes from orange to white.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Important:
1. Confirm that data file of FPGA has been already acquired from NEC.
2. Confirm the F/W versions on the IDU tab of the Equipment Inventory
Information window.
3. When executing the FPGA data download, set Maintenance Mode to ON
and do not release Maintenance Mode while controlling download.
Procedure 6-12
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Select the Update (Storage->NE) Utility from the Equipment Utility sub
menu.
4. The Update (Storage->NE) Utility window appears. Select the FPGA Data
radio button and then click Execute button.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
7. The file selection window appears. Select the FPGA Data file and then click
Open (or OK) button.
Local PC
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
USB Memory
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
11. After the download is completed, the Update Complete! window appears.
Then auto-revert should be executed by clicking the OK button.
12. The Information box appears. Click OK button. The WebLCT will shut down
automatically.
14. Select the Inventory (Equipment Inventory Information) from the LCT
menu.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
15. The Equipment Inventory (IDU) window appears. Confirm the new program
running on the Equipment Inventory Information (IDU) window.
16. After finishing FPGA Data download, click Maintenance button on the top of
the LCT window to exit maintenance mode.
17. Confirm that the MAINT colors changes from orange to white.
Important:
Upload existing Configuration Data File.
Note:
1. Do not use the same folder between Exist Configuration Data File and Data
for Download that allows comparison of each Data.
Procedure 6-13
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
3. Select the Update (Storage->NE) Utility from the Equipment Utility sub
menu.
4. The Update (Storage->NE) Utility window appears. Select the Config Data
radio button then click Execute button.
5. The source selection window appears. Select the specified Config Data Type
(Network Config, Equipment Config, Partial Equipment Config, User
Config).
6. Select destination storage (Local PC/USB Memory) from the Import File
field and then click File icon button.
7. The file selection window appears. Select the Config Data file and then click
Open (or OK) button.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
Local PC
USB Memory
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
8. The source selection window appears again. When selected source is other than
Partial Equipment Config, click OK button, and proceed to step 11.
10. Configuration item selection window appears. Select a target configuration and
then click OK button.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
13. After the download is completed, the Update Complete! window appears.
Then auto-revert should be executed by clicking OK button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
14. The Information box appears. Click OK button. The WebLCT will shut down
automatically.
16. Upload the Configuration Data File again and then acquire the Configuration
Data.
17. Confirm the latest Configuration Data running by comparing the newly acquired
Configuration Data to that acquired before download.
18. After finishing Configuration Data download, click Maintenance button on the
top of the LCT window to exit maintenance mode.
19. Confirm that the MAINT color changes from orange to white.
Important:
1. Confirm specified Parameter File for MODEM has already acquired from
NEC.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
Procedure 6-14
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Select the Update (Storage->NE) Utility from the Equipment Utility sub
menu.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
6. The source selection window appears. Select the destination storage (Local
PC/USB Memory) from the Import File field and then click File icon button.
7. The file selection window appears. Select the MODEM Parameter file and then
click Open (or OK) button.
Local PC
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
USB Memory
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
11. After the download is completed, the Update Complete! window appears.
Then auto-revert should be executed by clicking the OK button.
12. After restarting, open the window of specified MODEM and then confirm the
latest MODEM Parameter Data running by comparing the confirmed parameter
of specified MODEM.
14. Confirm that the MAINT color changes from orange to white.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
An SSL server certificate file that is supported in the iPASOLINK is a zip file.
This file must include public key and secret key as follows:
iPASOLINK-serverAAA.zip
|
+---- BBB.crt
+---- BBB.key
Procedure 6-15
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Select the Update (Storage->NE) Utility from the Equipment Utility sub
menu.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
5. The source selection window appears. Select the destination storage (Local
PC/USB Memory) from the Import File field and then click File icon button.
6. The file selection window appears. Select the SSL Server Certificate file and
then click Open (or OK) button.
Local PC
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
USB Memory
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
10. The Information window appears after downloading. Click OK button. The
WebLCT will shut down automatically.
12. After finishing SSL Server Certificate download, click Maintenance button on
the top of the LCT window to exit maintenance mode.
Important:
1. When executing the Program ROM Switching, set Maintenance Mode to ON
and do not release Maintenance Mode while controlling switching.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
Procedure 6-16
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Select the Program ROM Switching Utility from the Equipment Utility
sub menu.
4. The Program ROM Switching window appears. Click the Main Card in the
Item field.
6. The Warning dialog box appears. Click OK button. Then auto-revert should be
executed by clicking the OK button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
8. When iPASOLINK restarts, launch WebLCT and log in to the equipment again.
9. Select the Equipment Utility (Program ROM Switching) from the LCT
menu.
10. Confirm the Current version of the Main Board in the Program ROM
Switching window.
11. After finishing Program ROM Switching, click Maintenance button on the top
of the LCT window to exit maintenance mode.
12. Confirm that the MAINT colors changes from orange to white.
Important:
When executing the Program ROM Switching, set Maintenance Mode to ON and
do not release Maintenance Mode while controlling switching.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
Procedure 6-17
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Select the Program ROM Switching Utility from the Equipment Utility
sub menu.
4. The Program ROM Switching window appears. Click the ODU No. in the
Item field.
5. The Program ROM Switching (ODU) box appears. Confirm the information
then click OK button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
10. After finishing Program ROM Switching, click Maintenance button on the top
of the LCT window to exit maintenance mode.
11. Confirm that the MAINT color changes from orange to white.
Important:
When executing the Program ROM Switching, set Maintenance Mode to ON and
do not release Maintenance Mode while controlling switching.
Procedure 6-18
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
3. Select the Program ROM Switching Utility from the Equipment Utility
sub menu.
4. The Program ROM Switching window appears. Click the PTP-A U-Slot. in
the Item field.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
9. After finishing Program ROM Switching, click Maintenance button on the top
of the LCT window to exit maintenance mode.
10. Confirm that the MAINT color changes from orange to white.
Procedure 6-19
2. Select the USB Memory Utility from the Equipment Utility sub menu.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
3. The USB Memory Utility window appears. Click the Refresh button.
4. After refreshing, the USB Memory Utility window appears again. Confirm that
USB Memory Utility window is updated.
Procedure 6-20
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
3. Select the Log Clear Function from the Equipment Utility sub menu.
4. The Log Clear Function window appears. Select the radio button and then
click Execute button.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
Procedure 6-21
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
5. The Shipment box appears. Select the Provisioning Clear from the
drop-down list and then click OK button.
7. The Information box appears. Click OK button The WebLCT will shut down
automatically.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Procedure 6-22
2. Select the Date / Time Setting from the Equipment Utility sub menu.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
4. The Date / Time Setting box appears. Assign a proper value for each
parameter according to the table below.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
7. The Date / Time Setting window appears again. Confirm the modified date
and time of the information displayed.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
Reset control is available only when Maintenance Mode is set to ON. If Maintenance
Mode is set to OFF, Executing the reset control will result in the error response.
Card Reset
Available to control each option card individually. Main ETH signal will be
downed during the resetting. After Card Reset finished, option card need to be
reset the configuration information that retains by IDU. Card Reset replies NG
response and is not executed if option card has been not registered, not mounted,
or mounted different place.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Procedure 6-23
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Expand the H/W / F/W Reset Control from the Maintenance Control sub
menu.
4. Select the H/W Reset Control from the H/W / F/W Reset Control sub
menu.
5. The H/W Reset Control window appears. Click Option in the Item field.
6. The H/W Reset Control box appears. Confirm the information then click OK
button.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
10. Confirm the information displayed in the H/W Reset Control window.
11. After finishing Reset Control, click Maintenance button on the top of the LCT
window to exit maintenance mode.
12. Confirm that the MAINT color changes from orange to white.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Procedure 6-24
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Expand the H/W / F/W Reset Control from the Maintenance Control sub
menu.
4. Select the F/W Reset Control from the H/W / F/W Reset Control sub menu.
5. The F/W Reset Control window appears. Click Main Card in the Item field.
6. The F/W Reset Control box appears. Confirm the information then click OK
button.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
8. The Information box appears. Click OK button. The WebLCT window will
shut down automatically.
10. Confirm the information displayed in the F/W Reset Control window.
11. After finishing Reset Control, click Maintenance button on the top of the LCT
window to exit maintenance mode.
12. Confirm that the MAINT color changes from orange to white.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Procedure 6-25
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Expand the H/W / F/W Reset Control from the Maintenance Control sub
menu.
4. Select the F/W Reset Control from the H/W / F/W Reset Control sub
menu.
5. The F/W Reset Control window appears. Click specified ODU No. in the
Item field.
6. The F/W Reset Control box appears. Confirm the information then click OK
button.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
9. The CPU Reset (ODU) starts automatically. After restarting, confirm the
information displayed in the F/W Reset Control window.
10. After finishing Reset Control, click Maintenance button on the top of the LCT
window to exit maintenance mode.
11. Confirm that the MAINT color changes from orange to white.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
The function of each control is as follows (These windows are not available when
MAINT is in OFF. Switch to Maintenance mode first is displayed):
TX Mute Control
Despite the equipment configuration setting, forcing the “TX Mute Control” to
ON will stop the transmit power of the ODU.
Notes
1 If Mute Control is set to OFF and Mute OFF does not work due to
uncontrollable factors, Mute status will remain ON.
2. In case of 1+1 Hot Standby configuration, the Mute OFF control does not
mute both lines. Moreover, when force Mute is controlled in No.1/No.2,
Maintenance Mode cannot set to OFF.
4. TX Mute Release Time is set together with TX Mute Control by the item that
becomes effective only when TX Mute Control is done from a higher-level
device.
CW Control
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
after Mute OFF. At this time, when there is a factor that the CW control is not
turned ON it becomes CW control error.
In addition, in case of remote connection and operated Control CW, it may not
be able to recover again. CW Control will restore automatically according to
the TX Mute Release Time parameter.
The flat rate of the transmission modulation method of the control station in the
AMR mode is temporarily managed.
The modulation method can be set according to the target device regardless of
the AMR Range setting.
Under the 1+0 configuration, each Slot#/Slot# is individually controlled.
This control is done by exchanging request/answer of the control between
local/remote stations as well as LB2.
When the TX Modulation Manual Control setting is returned from Manual to
Auto, the fixed modulation method is returned to QPSK.
Performing this function (Manual Control) sets the Maintenance Mode to ON.
However, in case of Auto setting and if Maintenance Mode is set to OFF, it will
cancel the “auto setting”.
Procedure 6-26
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
5. The MODEM Maintenance Control box appears. Assign a proper value for
each parameter.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
10. After finishing ATPC Manual Control, click Maintenance button on the top of
the LCT window to exit maintenance mode.
11. Confirm that the MAINT color changes from orange to white.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Procedure 6-27
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
5. The MODEM Maintenance Control box appears. Assign a proper value for
each parameter.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
10. After finishing TX Mute Control, click Maintenance button on the top of the
LCT window to exit maintenance mode.
11. Confirm that the MAINT color changes from orange to white.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
Procedure 6-28
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
5. The MODEM Maintenance Control box appears. Assign a proper value for
each parameter.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
10. After finishing TX Mute Control, click Maintenance button on the top of the
LCT window to exit maintenance mode.
11. Confirm that the MAINT color changes from orange to white.
6.2.3.3 CW Control
Procedure 6-29
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
5. The MODEM Maintenance Control box appears. Assign a proper value for
each parameter.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
10. After finishing CW Control, click Maintenance button on the top of the LCT
window to exit maintenance mode.
11. Confirm that the MAINT color changes from orange to white.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Procedure 6-30
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
5. The MODEM Maintenance Control box appears. Assign a proper value for
each parameter.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
11. Confirm that the MAINT color changes from orange to white.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
The following Laser management items are available when executing from the LCT.
For SDH optical interface, the ALS (Automatic Laser Shutdown) control
performs the resumption of optical power for a definite period of time.
In addition, this function operates under ALS control execution (optical power
shutdown). If ALS is not activated, the control is not carried out.
Procedure 6-31
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Select the Laser Shutdown Control from the Maintenance Control sub
menu.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
4. The Laser Shutdown Control window appears. Select Off in the Forced
Laser Shutdown Control field.
5. The Laser Shutdown Control box appears. Select a proper value for the
Forced Laser Shutdown Control parameter.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
9. The Laser Shutdown Control window appears again. Confirm the parameters
displayed.
10. After finishing Laser Shutdown Control, click Maintenance button on the top
of the LCT window to exit maintenance mode.
11. Confirm that the MAINT color changes from orange to white.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Procedure 6-32
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
3. Select the Laser Shutdown Control from the Maintenance Control sub
menu.
4. The Laser Shutdown Control window appears. Select Control in the ALS
Restart field.
5. The Laser Shutdown Control box appears. Select a proper value for the ALS
Restart parameter.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
9. The Laser Shutdown Control window appears again. Confirm the parameters
displayed.
10. After finishing ALS Manual Switch Control, click Maintenance button on the
top of the LCT window to exit maintenance mode.
11. Confirm that the MAINT color changes from orange to white.
When House Keeping input at own station is detected, Cluster Alarm will transmit to
the opposite station by setting up the bit of Cluster ALM input (output toward to
wireless)
When any changes for Cluster ALM output (input toward to wireless) is detected
after Cluster Alarm signal was received by equipment in the opposite station, the
equipment in the opposite station will be set-up bit for House Keeping output control
then Relay output (RL) will be executing.
After receiving a Cluster Alarm signal from the opposite station and another Cluster
Alarm is input (output to the direction of the radio), a setup is performed, and Cluster
Alarm signal is sent out to an opposite office. It is possible to transmit the Cluster
Alarm signal.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
House Keeping external input port provides six port, four of six ports are
used by both Cluster Alarm and House Keeping and each port is required to
select Alarm function.
When 1 to 4 external input ports are selected as a Cluster Alarm input, F/W
executes to change the signal of HKIN1-4 into Cluster Alarm signal in
wireless frame then output the signal toward to opposite side of wireless. In
addition, any Modems are available to output the Cluster Alarm input signal.
House Keeping output port provides six port, four of six port are used by
both Cluster Alarm and House Keeping and each port (HK1-4) required to
set up individually from F/W to FPGA.
Set up to OK or not OK for each item (parallel alarm required to set up for
each alarm items), execute port output if over one alarm at specified item is
detected.
H/W control output port for other 2 port. (RL1, RL2 port will be fixed for
parallel alarm output by H/W.)
Cluster Alarm output 1 to 4 signals are selected after the incoming signals of
a MODEM under redundant system, and the arbitrary Cluster Alarm is
output to the radio port of CH unit.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Cluster Alarm input and output, and a Through function can be separately
controlled between different ports.
Procedure 6-33
3. Select Cluster Alarm Setting from the Relay-Alarm Mapping Setting sub
menu.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
8. The Cluster Alarm Setting window appears again. Confirm the parameters
displayed.
6.2.6 Inventory
Inventory will display information of H/W, in mounted MODEM, Network
information, and Software License Key information for the iPASOLINK.
Procedure 6-34
3. The Equipment Inventory Information window appears. Select the IDU tab.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
7. The Save As window appears. Select the proper folder of local PC and then
click Save button.
8. After finishing the export of inventory file, the Download Complete window
appears. Click Close button.
9. Confirm that the Inventory Information file is saved in the selected folder.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
When MC-A4 Card is replaced, the IDU Serial No. and the Manufactured Date
can be written in manually.
Procedure 6-35
1. Modify the IDU inventory by clicking the Modify IDU Information button, if
required.
3. Set the IDU Serial No. and Manufactured Date, and then click OK button.
Note: IDU Serial No. and Manufactured date is set with checking the IDU label.
Procedure 6-36
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
7. The Save As window appears. Select the proper folder of local PC and then
click Save button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
8. After finishing the export of inventory file, the Download Complete window
appears. Click Close button.
9. Confirm that the Inventory Information file is saved in the selected folder.
Procedure 6-37
2. Select the S/W License Information from the Inventory sub menu.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
6. The Save As window appears. Select the proper folder of local PC and then
click Save button.
7. After finishing the export of license information file, the Download Complete
window appears. Click Close button.
8. Confirm that the License Information file is saved in the selected folder.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
- E1 PMON Report
- PMON/RMON/FDB Clear
Procedure 6-38
2. Select the MODEM PMON Report from the PMON / RMON Report sub
menu.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
5. The MODEM PMON Report (1-day) window appears. Confirm the detail of
MODEM PMON Report.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
10. The Save As window appears. Select the proper folder of local PC and then
click Save button.
s’X’p’Y’:
’X’ means the slot number(MC-A4:1, others:U-slot+1)
’Y’ means the port number
11. After finishing the export of CSV file, the Download Complete window
appears. Click Close button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
12. Confirm that the MODEM PMON Report file is saved in the selected folder.
Procedure 6-39
2. Select the E1 PMON Report from the PMON / RMON Report sub menu.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
10. The Save As window appears. Select the proper folder of local PC and then
click Save button.
E1 1-day: 1day-E1-s1p1-YYYYMMDD.pmon
E1 15-min: 15min-E1-s1p1-YYYYMMDD.pmon
s’X’p1:
’X’ means the slot number.(MC-A4:1, others:U-slot+1)
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
11. After finishing the export of CSV file, the Download Complete window
appears. Click Close button.
12. Confirm that the E1 PMON Report file is saved in the selected folder.
(1) RS Tab
Procedure 6-40
2. Select the STM-1 PMON Report from the PMON / RMON Report sub menu.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
3. The STM-1 PMON Report window appears. Click RS tab and confirm the
Performance Monitor values that monitored for 15-minute and 1-day will be
displayed.
5. The STM-1 PMON Report (1-day) window appears. Confirm the detail of
STM-1 PMON Report.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
10. The Save As window appears. Select the proper folder of local PC and then
click Save button.
s’X’p’Y’:
’X’ means the slot number.(MC-A4:1, others:U-slot+1)
’Y’ means the port number.
11. After finishing the export of CSV file, the Download Complete window
appears. Click Close button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
12. Confirm that the STM-1 PMON Report file is saved in the selected folder.
(2) MS Tab
Procedure 6-41
2. Select the STM-1 PMON Report from the PMON / RMON Report sub menu.
3. The STM-1 PMON Report window appears. Click MS tab and confirm the
Performance Monitor values that monitored for 15-minute and 1-day will be
displayed.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
5. The STM-1 PMON Report (1-day) window appears. Confirm the detail of
STM-1 PMON Report.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
10. The Save As window appears. Select the proper folder of local PC and then
click Save button.
s’X’p’Y’:
’X’ means the slot number.(MC-A4:1, others:U-slot+1)
’Y’ means the port number.
11. After finishing the export of CSV file, the Download Complete window
appears. Click Close button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
12. Confirm that the STM-1 PMON Report file is saved in the selected folder.
Procedure 6-42
2. Select the ETH RMON Report from the PMON / RMON Report sub menu.
3. The ETH RMON Report window appears. Confirm the Remote Network
Monitoring values that monitored for 15-minute and 1-day will be displayed.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
5. The ETH RMON Report (1-day) window appears. Confirm the detail of
RMON Report.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
10. The Save As window appears. Select the proper folder of local PC and then
click Save button.
s’X’p’Y’:
’X’ means the slot number.(MC-A4:1, others:U-slot+1)
’Y’ means the port number.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
11. After finishing the export of CSV file, the Download Complete window
appears. Click Close button.
12. Confirm that the ETH RMON Report file is saved in the selected folder.
Procedure 6-43
2. Select the VLAN Counter Report from the PMON / RMON Report sub
menu.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
3. The VLAN Counter Report window appears. Confirm the VLAN Counter
Report values that monitored for 15-minute and 1-day will be displayed.
Procedure 6-44
5. Select the PMON / RMON / FDB Clear from the Maintenance Control sub
menu.
6. The PMON / RMON / FDB Clear window appears. Select the PMON/RMON
Clear radio button and then click Execute button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
10. Select the PMON or RMON Report sub menu from the PMON / RMON
Report of the LCT menu.
Procedure 6-45
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
3. Select the PMON / RMON / FDB Clear from the Maintenance Control sub
menu.
4. The PMON / RMON / FDB Clear window appears. Select the FDB Table
Clear radio button and then click Execute button.
5. The FDB Table Clear box appears. Select the All radio button. Click OK
button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
7. After finishing FDB Table Clear, the Information box appears. Click OK
button.
Procedure 6-46
2. Select the PMON / RMON / FDB Clear from the Maintenance Control sub
menu.
3. The PMON / RMON / FDB Clear window appears. Select the FDB Table
Clear radio button and then click Execute button.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
4. The FDB Table Clear box appears. Select the VLAN ID radio button and enter
the VLAN ID No., and then click OK button.
6. After finishing FDB Table Clear, the Information box appears. Click OK
button.
Procedure 6-47
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
2. Select the PMON / RMON / FDB Clear from the Maintenance Control sub
menu.
3. The PMON / RMON / FDB Clear window appears. Select the FDB Table
Clear radio button and then click Execute button.
4. The FDB Table Clear box appears. Select Port radio button and select card
name and Port No. from each drop-down list, and then click OK button.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
6. After finishing FDB Table Clear, the Information box appears. Click OK
button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Note: Following case is not recommended for the use of DADE Adjustment.
1. PTP functions are used on Modem path.
Procedure 6-48
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
5. The Offline Maintenance Control box appears. Select the specified status
from the DADE Adjust drop-down list, and then click OK button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
10. After finishing DADE Adjustment, click Maintenance button on the top of the
LCT window to exit maintenance mode.
11. Confirm that the MAINT color changes from orange to white.
This selection can set up each ODU individually, the available suffix Sub Band
which can be set up are the alphabet "A through H, J through N, P, R, and X".
Notes
1. Before changing the Sub Band setting, it is required to set TX Mute to ON,
and also prevent any rewriting data in the ODU Flash ROM.
2. When any ODU which does not support a Sub Band change and change
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
Procedure 6-49
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
5. The Offline Maintenance Control box appears. Select the specified value
from the RF Sub Band Select drop-down list, and then click OK button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
8. The Offline Maintenance Control window appears again. Confirm that the
status is modified as same as the selection in the DADE Adjust field.
9. After finishing RF Sub Band Selection, click Maintenance button on the top of
the LCT window to exit maintenance mode.
10. Confirm that the MAINT color changes from orange to white.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Procedure 6-50
1. Click Maintenance button on the top of the LCT window to enter maintenance
mode.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
8. After finishing Maintenance Test, the Result window appears. Confirm the
parameters displayed.
(a) LB Result
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
(b) LT Result
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
(d) LM Result
Click Export CSV File button on the top of the ETH OAM LB / LT / DM
/ LM Control window.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
Click Export CSV File button in the LB (LT, DM, or LM) Result
window.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
11. The Save As window appears. Select the proper folder of local PC and then
click Save button.
History Information:
HistoryInfoExport-YYYYMMDDhhmmss.csv
Test Result :
TestResultInfoExport-LB(LT, DM or LM)-YYYYMMDDhhmmss.csv
12. After finishing the export of CSV file, the Download Complete window
appears. Click Close button.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
13. Confirm that the CSV file is saved in the selected folder.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Procedure 6-51
2. Select the Import License key from the S/W License Setup sub menu.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
3. The Import License key window appears. Click the Setup button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
4. The Import License Key window appears then click File icon button.
5. Select the license key(s) to be applied in the Dialog box for file selection where
license key is located.
Procedure 6-52
2. Select the Radio Capacity Setting from the S/W License Setup sub menu.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
3. The Radio Capacity Setting window appears. Click the Setup button.
4. The Radio Capacity Setting box appears. Specify the Radio Capacity License
and then selected the desired MODEM (Slot**) from the New State drop-down
list.
5. Click OK button.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
7. The Radio Capacity Setting window appears again. Confirm the parameters
displayed.
Procedure 6-53
2. Select the SFP Port License Setting from the S/W License Setup sub
menu.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
3. The SFP Port License Setting window appears. Click the Setup button.
4. The SFP Port License Setting box appears. Specify the SFP Port Usage
License and then select the desired GbE (Slot**) from the New State
drop-down list.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
5. Click OK button.
7. The SFP Port License Setting window appears again. Confirm the
parameters displayed.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
7. TROUBLE SHOOTING
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
START
YES
Connect the LCT to the IDU and
Is ALM NO
check ALARM/STATUS menu.
indicator on the IDU
Check every items whether
solid red ?
indicated status is alarm or normal.
YES
Is ALM NO
indicator
The IF cable
on the MODEM Card Is TX Input NO
type, Cable length and
blinking red? indicated normal? cable loss are used
standard NO
YES YES
YES
Check the IF cable
connection and connectors Replace the Change the
whether the cable is open or ODU with IF cable to
short circuit. Is TX power of NO
a spare. standard.
the ODU indicated
normal?
YES
Is ODU
NO CPU/Cable Open ALM
indicated
normal?
YES
Reset CPU of the ODU.
YES YES
Is TX power NO
Is ODU
vary with ATPC manual
ALM indicated
control?
normal?
YES
YES
Replace the ODU END Check the RX Replace the ODU with Replace
with a spare. section of the ODU. a spare, if TX power alarm the ODU
continues when temperature with a spare.
is improved.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
START
YES
Connect the LCT to the IDU and
Is ALM NO check Current Status menu.
indicator on the IDU Check every items whether
solid red ? indicated status is Alarm or Normal.
YES
NO
Is ALM
indicator
on the MODEM Card
blinking red ? NO
Is RX Level
indicated Normal?
YES
YES
Check the IF cable connection
and connectors whether the Is RX LEVEL by
cable is open or short circuit. RSL monitor vary ath random
NO interval?
YES
NO Check fading or
Is ODUCPU
/Cable Open ALM indicated interference.
Reset CPU of the ODU.
Normal?
YES
YES NO YES
Replace the END Check the TX Replace the Check Antenna system
Set proper
ODU section of the ODU or Replace the ODU
frequency.
with a spare. ODU. with a spare. with a spare.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
START
NO Is PWR LED on
the IDU solid green?
YES
Replace Fuse
in the IDU Connect the LCT to the IDU
Is ALM and check Current Status
NO NO
indicator on the IDU menu. Check every items
solid red ? whether indicated status is
Alarm or Normal
YES
NO
Is ALM indicator
blinking red ?
YES
NO
Is AIS Generated
indicated Normal?
Check associated
YES
DTE.
Check associated
DTE at local site. YES
NO Is CH Usage
indicated Normal ?
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Is ODU indicated NO
Normal?
YES
Check the section
of the ODU.
NO Is Module ALM NO
Is IDU indicated
Normal? of Main Board Indicated
Normal?
YES YES
Replace the IDU
with a spare.
NO
Is Module ALM
of Option Card Indicated
Normal?
YES
Replace the Option Card
with a spare.
NO
Is RDI indicated
Normal?
YES
Check the opposite
Equipment.
Select IF Loopback from
MODEM Loopback Control menu in the
Maintenance Control menu on the LCT.
NO
Check the section
of the ODU.
Is Input LOS NO
indicated Normal?
YES
Check associated DTE
and cable connection.
Check associated DTE and cable
connection at opposite site.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
Check the name plate of the spare ODU. When the indicated items are coincided, the
ODU can be replaced.
Caution:
1. Do not remove/connect the IF cable with the IDU power ON. Turn the IDU
power OFF before connecting/disconnecting the IF cable, or equipment
may be damaged.
7 to 11 GHz 13 to 42 GHz
Caution: Be careful that the surface of the ODU is hot during operation.
The mounting and demounting the ODU from/to antenna, refer to Installation in
Section II.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Procedure 7-1
(1) Removing
2. Turn off the power switch on the MODEM which is connected to the ODU is to
be replaced.
6. Loosen the four screws fixing the ODU with a T type hexagonal driver.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
(2) Mounting
Procedure 7-2
1. When the ODU is used for vertical polarization, rotate the ODU so that the plate
marked V is on the top.
2. When the ODU is used for horizontal polarization, remove the guide pin fixed on
the plate marked V.
3. Insert the guide pin removed in step 2 behind of the plate marked H.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Note:
1. Be careful not to damage the flange and O-ring.
6. Mount the spare ODU onto the bracket and tighten the four screws on the ODU.
8. Wrap twice the IF IN/OUT connector with self-bonding tape for waterproofing.
10. Turn on the power switch on the MODEM which is connected to the ODU.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
Caution:
1. Persons performing maintenance must take necessary steps to avoid
electro-static discharge which may damage the cards or cause error. Wear
a conductive wrist strap connected to the grounded (G) jack on the front of
the equipment shelf. This will minimize static build-up during maintenance.
2. Do not remove/connect the IF cable with the IDU power ON. Turn the IDU
power OFF before connecting/disconnecting the IF cable, or equipment
may be damaged.
(a) Removing
Procedure 7-3
1. Disconnect power supply cable from power supply connector. Disconnect the IF
cable, signal cables and the power cable, etc. in the following order.
1-1. Disconnect power cables from connector.
1-2. Disconnect E1, STM-1, LAN, AUX. signal cables from connector.
1-3. Disconnect IF cable from IF IN/OUT connector.
1-4. Disconnect ground cable from the ground terminal.
(b) Mounting
Procedure 7-4
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
2. Mount the IDU into the original position of the mounting rack and tighten
screws.
3. Reconnect the IF cables, signal cables and the power cable to the original
position in the following order.
4. Form the wiring, and fix the cables using cable binder to the mounting rack.
Notes:
1. Do not cross the cables on front of indicators and power switch used for
maintenance.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Procedure 7-5
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
Procedure 7-6
2. Retrieve the current alarms and check if the ODU alarm is cleared. If the alarm is
not cleared, contact NEC for the appropriate maintenance support.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
7.3.3.2 TX Power
This message indicates that TX power level of the ODU is lower than 3 dB.
Procedure 7-7
7.3.3.3 TX Input
This message indicates that TX IF signal level is out of range from -29 dBm ± 5 dB.
Procedure 7-8
7.3.3.4 RX Level
This message indicates that RX level is lower than -72dBm ~ -94dBm level (Alarm
detection level depends on modulation schemes and bit rates).
Procedure 7-9
Procedure 7-10
7.3.3.6 LO REF
This message indicates that Loss of Ref LO signal of ODU is detected.
Procedure 7-11
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
2. If the LO REF ALM is detected yet, replace the ODU with a spare.
This step is the end of the procedure.
Procedure 7-12
1. Exchange the ODU with correct type or set correct modulation setting.
This step is the end of the procedure.
Procedure 7-13
7.3.4.1 Module
This message indicates that a failure of hardware is detected on the card. The
possible cause is broken hardware on the card.
Procedure 7-14
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Procedure 7-15
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
Procedure 7-16
1. Pull out the card, and reinsert the card into the slot.
2. Retrieve the current alarms, and check if the Unequipped alarm is cleared.
3. If the Unequipped alarm is detected yet, confirm that the card is located in the
specified slot, if not, move it to the right slot.
4. Retrieve the current alarms, and check if the Unequipped alarm is cleared.
6. Retrieve the current alarms, and check if the Unequipped alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
Procedure 7-17
3. If the Power Supply alarm is detected yet, remove the connector and the
FUSE, check the FUSE and replace it if broken.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
4. Reinsert the FUSE and the connector. Retrieve the current alarms, and check if
the alarm is cleared. If the alarm is not cleared, contact NEC for the appropriate
maintenance support.
Procedure 7-18
2. Retrieve the current alarms, and check if the FAN Fail alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
Procedure 7-19
2. Retrieve the current alarms, and check if the Unequipped alarm is cleared.
3. If the alarm is not cleared, contact NEC for the appropriate maintenance support.
Procedure 7-20
1. Pull out the MC-A4 card, and remount the CLK2M-C card on the MC-A4 card.
2. Retrieve the current alarms, and check if the Unequipped alarm is cleared.
4. Retrieve the current alarms, and check if the Unequipped alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
This message indicates that a failure has been detected in the card. The possible
cause is a card type error.
Procedure 7-21
2. Retrieve the current alarms, and check if the Type Mismatch alarm is cleared.
3. If the Type Mismatch alarm is detected yet, replace the MC-A4 card.
4. Retrieve the current alarms, and check if the Type Mismatch alarm is cleared. If
the alarm is not cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure has been detected in the IDU CPU. The possible
cause is broken hardware on the card.
Procedure 7-22
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure has been detected in the memory. The possible
cause is broken hardware on the card.
Procedure 7-23
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
This message indicates that a failure has been detected in the USB memory.
Procedure 7-24
1. Pull out the USB memory, and reinsert the USB memory into the slot.
2. Retrieve the current alarms, and check if the USB FAILalarm is cleared.
4. Retrieve the current alarms, and check if the Unequipped alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
7.3.4.12 Temperature
This message indicates that the temperature in the IDU is over the workable temperature.
This possible cause is that the room temperature is uncontrolled.
Procedure 7-25
1. Check if there is any problem in the air conditioner on the IDU room.
3. Retrieve the current alarms, and check if the Temperature alarm is cleared. If
the alarm is not cleared, contact NEC for the appropriate maintenance support.
4. (Wait 1 hour at least after the room temperature is fallen down under the
workable temperature.)
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Procedure 7-26
1. Check if there is any alarm in the indicated facility port/line or in the equipment
at another side.
3. Retrieve the current alarms, and check if the CLK FAIL alarm is cleared.
4. If the CLK FAIL alarm is detected yet, check whether any alarm of the indicated
port/line is cleared.
5. If the any alarm is reported on the indicated port/line, clear it by other procedure
according to the trouble shooting.
6. Retrieve the current alarms, and check if the CLK FAIL alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
Procedure 7-27
3. Retrieve the current alarms, and check if the CLK Drift alarm is cleared.
4. If the CLK Drift alarm is detected yet, check whether any alarm of the indicated
port/line is cleared.
5. If the any alarm is reported on the indicated port/line, clear it by other procedure
according to the trouble shooting.
6. Retrieve the current alarms, and check if the CLK Drift alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
7.3.4.15 LTI
This message indicated that the IDU does not synchronize with any reference clock
source. If this condition occurs, the problem is on the optical fiber/electrical cable or on
the far-end NE.
Procedure 7-28
3. Retrieve the current alarms, and check if the LTI alarm is cleared. If the alarm is
not cleared, contact NEC for the appropriate maintenance support.
Procedure 7-29
3. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
Procedure 7-30
3. Retrieve the current alarms, and check if the EXT CLK LOS alarm is cleared. If
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
the alarm is not cleared, contact NEC for the appropriate maintenance support.
Procedure 7-31
1. Check if an alarm occurs in the equipment at another side, and clear it to normal
state.
2. Retrieve the current alarms, and check if the EXT CLK AIS alarm is cleared. If
the alarm is not cleared, contact NEC for the appropriate maintenance support.
Procedure 7-32
3. Retrieve the current alarms, and check if the EXT CLK LOF alarm is cleared. If
the alarm is not cleared, contact NEC for the appropriate maintenance support.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
Procedure 7-33
1. If the EXT CLK Out signal and the EXT CLK In signal are completely separated
as frequency at the equipment connected the EXT CLK In/Out, ignore this alarm.
2. Change the reference clock source from EXT CLK In to other reference clock
source by the maintenance command.
3. Retrieve the current alarms, and check if the EXT CLK Loop alarm is cleared. If
the alarm is not cleared, contact NEC for the appropriate maintenance support.
4. If not use the EXT CLK In as system clock, delete it from the reference clock
source and clear the maintenance command.
7.3.4.21 E1 LOS
This message indicates that a failure of the E1 LOS (Loss Of Signal) is detected from
the incoming signal on the indicated facility. If this condition occurs, the problem is
on the cable connection or on the far-end NE.
Procedure 7-34
3. Retrieve the current alarms, and check if the LOS alarm is cleared. If the alarm is
not cleared, contact NEC for the appropriate maintenance support.
7.3.4.22 E1 AIS
This message indicates that a failure of the AIS (Alarm Indication Signal) is detected
from the incoming signal on the indicated facility. If this condition occurs, the
problem is on the indicated line in the far-end NE.
Procedure 7-35
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
2. Retrieve the current alarms, and check if the AIS alarm is cleared. If the alarm is
not cleared, contact NEC for the appropriate maintenance support.
This step is the end of the procedure.
This message indicates that a failure of the PPS-FAIL (E1 SNCP Path Protection
Switch failed) is detected from the incoming signal on the indicated facility. If this
condition occurs, the problem is on both receiving signals.
Procedure 7-36
1. Check if the secondary path is available and the cross connect configuration is
valid.
3. Retrieve the current alarms, and check if the PPS-FAIL alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
This step is the end of the procedure.
This message indicates that the E1 port, which is not enabled, received signal.
Procedure 7-37
3. Retrieve the current alarms, and check if the Usage Error alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure of the ETH LOS (Loss Of Signal) is detected
from the incoming signal on the indicated facility. If this condition occurs, the
problem is on the optical fiber or on the far-end NE.
Procedure 7-38
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
3. Retrieve the current alarms, and check if the LOS alarm is cleared. If the alarm is
not cleared, contact NEC for the appropriate maintenance support.
7.3.4.26 ETH TF
This message indicates that a failure has been detected in the installed SFP modules.
The possible cause is that SFP module failure.
Procedure 7-39
2. Retrieve the current alarms, and check if the TF alarm is cleared. If the alarm is
not cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure has been detected in the port. The possible cause
is SFP type error or the port configuration error in the LCT.
Procedure 7-40
1. For the Ethernet port and STM-1 port, confirm their port configurations in the
LCT.
3. Retrieve the current alarms, and check if the SFP Type Mismatch alarm is
cleared.
4. If the SFP Type Mismatch alarm is detected yet, check whether the SFP type of
these ports is correct.
6. Retrieve the current alarms, and check if the SFP Type Mismatch alarm is
cleared. If the alarm is not cleared, contact NEC for the appropriate maintenance
support.
7. For other port, check whether the SFP type of these ports is correct first.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
8. If not, replace the SFP type, and insert the correct SFP to specified port.
9. Retrieve the current alarms, and check if the SFP Type Mismatch alarm is
cleared. If the alarm is not cleared, contact NEC for the appropriate maintenance
support.
This message indicates that a failure has been detected in the registered port. The
possible cause is removed of the SFP module.
Procedure 7-41
1. Pull out the SFP module, and reinsert it into the port.
2. Retrieve the current alarms, and check if the SFP Unequipped alarm is cleared.
3. If the SFP Unequipped alarm is detected yet, confirm that the SFP module is
located in the specified port, if not, move it to the right port.
4. Retrieve the current alarms, and check if the SFP Unequipped alarm is cleared.
6. Retrieve the current alarms, and check if the SFP Unequipped alarm is cleared. If
the alarm is not cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure of Ethernet Link down is detected on the
indicated port. If this condition occurs, the problem is on the optical fiber or on the
far-end NE.
Procedure 7-42
3. Retrieve the current alarms, and check if the LAN LINK alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
Procedure 7-43
1. Check if an alarm occurs in the far-end NE that is associated with the indicated
MEP, and clear it to normal state.
2. Retrieve the current alarms, and check if the ETH-OAM LOC alarm is cleared.
3. If the alarm is not cleared, confirm their MEG/MEP configurations in the LCT.
5. Retrieve the current alarms, and check if the ETH-OAM LOC alarm is cleared.
6. If the ETH-OAM LOC alarm is detected yet, check whether the MEG/MEP
configuration on the far-end NE is correct.
8. Retrieve the current alarms, and check if the ETH-OAM LOC alarm is cleared. If
the alarm is not cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure of Mismerge is detected on the indicated MEP.
The possible cause is the receiving unexpected ETH-CC frames from far-end NE or
the MEG/MEP configuration error in the LCT.
Procedure 7-44
3. Retrieve the current alarms, and check if the ETH-OAM Mismerge alarm is
cleared.
4. If the ETH-OAM Mismerge alarm is detected yet, check whether the MEG/MEP
configuration on the far-end NE is correct.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
6. Retrieve the current alarms, and check if the ETH-OAM Mismerge alarm is
cleared. If the alarm is not cleared, contact NEC for the appropriate maintenance
support.
This message indicates that a mismatch of the ETH-CC transmit period is detected
on the indicated MEG. The possible cause is the mismatch of the MEG configuration
between the far-end NE and local NE in the LCT.
Procedure 7-45
3. Retrieve the current alarms, and check if the ETH-OAM Unexpected Period
alarm is cleared.
4. If the ETH-OAM Unexpected Period alarm is detected yet, check whether the
MEG/MEP configuration on the far-end NE is correct.
6. Retrieve the current alarms, and check if the ETH-OAM Unexpected Period
alarm is cleared. If the alarm is not cleared, contact NEC for the appropriate
maintenance support.
This message indicates that a failure of the ETH-OAM RDI (Remote Defect
Indicate) is detected from the incoming ETH-CC frame on the indicated MEP. If this
condition occurs, the problem is an alarm detected at the peer MEP.
Procedure 7-46
2. Clear conditions that cause the alarm in the MEG that belongs to a peer MEP.
3. Retrieve the current alarms, and check if the ETH-OAM RDI alarm is cleared. If
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
the alarm is not cleared, contact NEC for the appropriate maintenance support.
This message indicates that mismatch exists between IDU configuration and installed
software license key. The possible cause is removal of the software license key from
the IDU by the software key allocator system.
Procedure 7-47
7.3.5.1 Unequipped
This message indicates that a failure has been detected in the registered slot. The possible
cause is the card is not inserted to the slot correctly.
Procedure 7-48
1. Pull out the card, and reinsert the card into the slot.
2. Retrieve the current alarms, and check if the Unequipped alarm is cleared.
3. If the Unequipped alarm is detected yet, confirm that the card is located in the
specified slot, if not, move it to the right slot.
4. Retrieve the current alarms, and check if the Unequipped alarm is cleared.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
6. Retrieve the current alarms, and check if the Unequipped alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure has been detected in the card. The possible
cause is card type error or the card configuration error in the LCT.
Procedure 7-49
3. Retrieve the current alarms, and check if the Type Mismatch alarm is cleared.
4. If the Type Mismatch alarm is detected yet, check whether the card type is
correct.
Procedure 7-50
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
7.3.5.4 Module
This message indicates that a failure of hardware is detected on the card. The
possible cause is broken hardware on the card.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
Procedure 7-51
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure of equipment internal Tx Bus Error has been
detected in the card. The possible cause is broken hardware on the card.
Procedure 7-52
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure of equipment internal Rx Bus Error has been
detected in the card. The possible cause is broken hardware on the card.
Procedure 7-53
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
7.3.5.7 LOF
Procedure 7-54
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
2. If the RX LEV metering value is NOT correct, clear it according to "RX LEV
ALM" of the troubleshooting.
4. If the RX LEV metering value and MODEM configuration are correct, replace
the IDU with a spare.
7.3.5.8 Frame ID
Procedure 7-55
This message indicates “Radio signal degradation (High BER threshold detection)”.
Procedure 7-56
2. If the RX LEV metering value is NOT correct, clear it according to "RX LEV
ALM" of the troubleshooting.
3. If the RX LEV metering value is correct, replace the IDU with a spare.
This message indicates “Radio signal degradation (Low BER threshold detection)”.
Procedure 7-57
2. If the RX LEV metering value is correct, replace the IDU with a spare.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
3. If the RX LEV metering value is NOT correct, clear it according to "RX LEV
ALM" of the troubleshooting.
Procedure 7-58
2. If the RX LEV metering value is correct, replace the IDU with a spare.
3. If the RX LEV metering value is NOT correct, clear it according to "RX LEV
ALM" of the troubleshooting.
7.3.5.12 MOD
This massage indicates “the operating status of the MOD. When any failure occurs in
the modulator section, “Alarm” is issued.”
Procedure 7-59
This message indicates “IF cable between IDU - ODU is in short condition”.
Procedure 7-60
2. If IF CABLE SHORT alarm is cleared, a failure may occur on the IF cable side.
Confirm the IF cable.
3. If IF CABLE SHORT alarm is not cleared, replace the IDU with a spare.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
7.3.5.14 XIF
This message indicates that an XIF cable connection error between master XPIC and
slave MODEM cards.
Procedure 7-61
3. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
MODEM port”.
Procedure 7-62
2. If the RX LEV metering value is correct, replace the IDU with a spare.
3. If the RX LEV metering value is NOT correct, clear it according to "RX LEV
ALM" of the troubleshooting.
7.3.5.16 RDI
Procedure 7-63
3. Retrieve the current alarms, and check if the RDI alarm is cleared. If the alarm is
not cleared, contact NEC for the appropriate maintenance support.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
7.3.5.17 UAE
Procedure 7-64
1. Check the current alarms, and if there are any other alarms, clear these alarms at
first according to the troubleshooting.
2. After clearing every alarm, retrieve the current alarm, and check if the UAE is
not cleared with any alarms, contact NEC for the appropriate maintenance
support.
Procedure 7-65
Procedure 7-66
7.3.5.20 Unlocked
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Procedure 7-67
1. Check the equipment clock setting. Refer to operation manual for detail.
This message indicates that the power switch on the MODEM-A/EA Card is set to
off.
Procedure 7-68
This message indicates that the two opposing MODEMs are not configured to have
the same Header Compression Mode.
Procedure 7-69
1. Set the same Header Compression mode to the remote NE. Refer to Operation
manual for the details.
This message indicates that the registered configuration data and the actually
installed FPGA version do not match, or settings of the MODEMs on the local and
opposing site do not match.
Procedure 7-70
2. Retrieve the current alarms, and check if the condition is recovered. If not, check
those above for the associated NE on the opposing site.
3. Retrieve the current alarms, and check if the alarm is cleared. If not, contact
NEC for the appropriate maintenance support.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
7.3.6.1 Unequipped
This message indicates that a failure has been detected in the registered slot. The possible
cause is the card is not inserted to the slot correctly.
Procedure 7-71
1. Pull out the card, and reinsert the card into the slot.
2. Retrieve the current alarms, and check if the Unequipped alarm is cleared.
3. If the Unequipped alarm is detected yet, confirm that the card is located in the
specified slot, if not, move it to the right slot.
4. Retrieve the current alarms, and check if the Unequipped alarm is cleared.
6. Retrieve the current alarms, and check if the Unequipped alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure has been detected in the card. The possible
cause is card type error or the card configuration error in the LCT.
Procedure 7-72
3. Retrieve the current alarms, and check if the Type Mismatch alarm is cleared.
4. If the Type Mismatch alarm is detected yet, check whether the card type is
correct.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Procedure 7-73
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
7.3.6.4 Module
This message indicates that a failure of hardware is detected on the card. The
possible cause is broken hardware on the card.
Procedure 7-74
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure of equipment internal Tx Bus Error has been
detected in the card. The possible cause is broken hardware on the card.
Procedure 7-75
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure of equipment internal Rx Bus Error has been
detected in the card. The possible cause is broken hardware on the card.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
Procedure 7-76
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure has been detected in the port. The possible cause
is SFP type error or the port configuration error in the LCT.
Procedure 7-77
1. For the Ethernet port and STM-1 port, confirm their port configurations in the
LCT.
3. Retrieve the current alarms, and check if the SFP Type Mismatch alarm is
cleared.
4. If the SFP Type Mismatch alarm is detected yet, check whether the SFP type of
these ports is correct.
6. Retrieve the current alarms, and check if the SFP Type Mismatch alarm is
cleared. If the alarm is not cleared, contact NEC for the appropriate maintenance
support.
7. For other ports, check whether the SFP type of these ports is correct first.
8. If not, replace the SFP module, and insert the correct SFP to specified port.
9. Retrieve the current alarms, and check if the SFP Type Mismatch alarm is
cleared. If the alarm is not cleared, contact NEC for the appropriate maintenance
support.
This message indicates that a failure has been detected in the registered port. The
possible cause is removed of the SFP module.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Procedure 7-78
1. Pull out the SFP module, and reinsert it into the port.
2. Retrieve the current alarms, and check if the SFP Unequipped alarm is cleared.
3. If the SFP Unequipped alarm is detected yet, confirm that the SFP module is
located in the specified port, if not, move it to the right port.
4. Retrieve the current alarms, and check if the SFP Unequipped alarm is cleared.
6. Retrieve the current alarms, and check if the SFP Unequipped alarm is cleared. If
the alarm is not cleared, contact NEC for the appropriate maintenance support.
7.3.6.9 STM-1LOS
This message indicates that a failure of the LOS (Loss Of Signal) is detected from
the incoming signal on the indicated facility. If this condition occurs, the problem is
on the optical fiber or on the far-end NE.
Procedure 7-79
3. Retrieve the current alarms, and check if the LOS alarm is cleared. If the alarm is
not cleared, contact NEC for the appropriate maintenance support.
7.3.6.10 TF
This message indicates that a failure has been detected in the installed SFP modules.
The possible cause is SFP module failure.
Procedure 7-80
2. Retrieve the current alarms, and check if the TF alarm is cleared. If the alarm is
not cleared, contact NEC for the appropriate maintenance support.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
7.3.6.11 RS LOF
This message indicates that a failure of the LOF (Loss Of Frame) is detected from
the incoming signal on the indicated facility. If this condition occurs, the problem is
on the cable or on the far-end NE.
Procedure 7-81
3. Retrieve the current alarms, and check if the LOF alarm is cleared. If the alarm is
not cleared, contact NEC for the appropriate maintenance support.
7.3.6.12 RS TIM
This message indicates that a failure of the RS TIM (Trace Identifier Mismatch) is
detected from the incoming signal on the indicated facility. If this condition occurs,
the problem is on the J0 setting or at the far-end NE setting.
Procedure 7-82
2. Clear the condition if the receive byte is not same as expected value.
3. Retrieve the current alarms, and check if the RS TIM alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
7.3.6.13 RS EXC
This message indicates that a failure of the RS EXC (EXCessive) is detected from
the incoming signal on the indicated facility. If this condition occurs, the problem is
on the B1 setting or at the far-end NE setting.
Procedure 7-83
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
3. Retrieve the current alarms, and check if the RS EXC alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
7.3.6.14 RS DEG
This message indicates that a failure of the RS DEG (DEGraded) is detected from the
incoming signal on the indicated facility. If this condition occurs, the problem is on
the B1 setting or at the far-end NE setting.
Procedure 7-84
3. Retrieve the current alarms, and check if the RS EXC alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
7.3.6.15 MS AIS
This message indicates that a failure of the MS AIS (Alarm Indication Signal) is
detected from the incoming signal on the indicated facility. If this condition occurs,
the problem is at the far-end NE.
Procedure 7-85
3. Retrieve the current alarms, and check if the MS AIS alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
7.3.6.16 MS RDI
This message indicates that a failure of the MS RDI (Remote Defect Indicate) is
detected from the incoming signal on the indicated facility. If this condition occurs,
the problem is an alarm detected at the far-end NE.
Procedure 7-86
3. Retrieve the current alarms, and check if the MS RDI alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
7.3.6.17 AU AIS
This message indicates that a failure of the AU AIS (Alarm Indication Signal) is
detected from the incoming signal on the indicated facility. If this condition occurs,
the problem is on the MSA function in the far-end NE.
Procedure 7-87
2. Clear conditions that cause the alarm for the far-end NE.
3. Retrieve the current alarms, and check if the AU AIS alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
7.3.6.18 AU LOP
This message indicates that a failure of the AU LOP (Loss Of Pointer) is detected
from the incoming signal on the indicated facility. If this condition occurs, the
problem is on the MSA function in the far-end NE.
Procedure 7-88
2. Clear conditions that cause the alarm for the far-end NE.
3. Retrieve the current alarms, and check if the AU LOP alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
7.3.6.19 HP UNEQ
Procedure 7-89
3. Retrieve the current alarms, and check if the HP UNEQ alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
7.3.6.20 HP TIM
This message indicates that a failure of the HP TIM (Trace Identifier mismatch) is
detected from the incoming signal on the indicated facility. If this condition occurs,
the problem is on the J1 setting or on the far-end NE setting.
Procedure 7-90
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
2. Clear the condition if the receive byte is not same as expected value.
3. Retrieve the current alarms, and check if the HP TIM alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
7.3.6.21 HP PLM
This message indicates that a failure of the HP PLM (Payload Mismatch) is detected
from the incoming signal on the indicated facility. If this condition occurs, the
problem is on the configuration in the far-end NE.
Procedure 7-91
3. Retrieve the current alarms, and check if the HP PLM alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
7.3.6.22 HP RDI
This message indicates that a failure of the HP RDI (Remote Defect Indicate) is
detected from the incoming signal on the indicated facility. If this condition occurs,
the problem is an HP alarm detected in the far-end NE.
Procedure 7-92
3. Retrieve the current alarms, and check if the HP RDI alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
7.3.6.23 LOM
This message indicates that a failure of the LOM (Loss Of Multi frame) is detected
from the incoming signal on the indicated facility. If this condition occurs, the
problem is on the HPA function at the far-end NE.
Procedure 7-93
3. Retrieve the current alarms, and check if the LOM alarm is cleared. If the alarm
is not cleared, contact NEC for the appropriate maintenance support.
7.3.6.24 TU AIS
This message indicates that a failure of TU AIS (Alarm Indication Signal) is detected
from the incoming signal on the indicated facility. If this condition occurs, the
problem is on the LPA function in the far-end NE.
Procedure 7-94
3. Retrieve the current alarms, and check if the TU AIS alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
7.3.6.25 TU LOP
This message indicates that a failure of the TU LOP (Loss Of Pointer) is detected
from the incoming signal on the indicated facility. If this condition occurs, the
problem is on the HPA function at the far-end NE.
Procedure 7-95
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
3. Retrieve the current alarms, and check if the TU LOP alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
7.3.6.26 LP UNEQ
Procedure 7-96
3. Retrieve the current alarms, and check if the LP UNEQ alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
7.3.6.27 LP-RDI
This message indicates that a failure of the LP RDI (Remote Defect Indicate) is
detected from the incoming signal on the indicated facility. If this condition occurs,
the problem is an LP alarm detected at the far-end NE.
Procedure 7-97
3. Retrieve the current alarms, and check if the LP RDI alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
7.3.6.28 LP-PLM
This message indicates that a failure of the LP PLM (Payload Mismatch) is detected
from the incoming signal on the indicated facility. If this condition occurs, the
problem is on the configuration at the far-end NE.
Procedure 7-98
3. Retrieve the current alarms, and check if the LP PLM alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
7.3.7.1 Unequipped
This message indicates that a failure has been detected in the registered slot. The possible
cause is the card is not inserted to the slot correctly.
Procedure 7-99
1. Pull out the card, and reinsert the card into the slot.
2. Retrieve the current alarms, and check if the Unequipped alarm is cleared.
3. If the Unequipped alarm is detected yet, confirm that the card is located in the
specified slot, if not, move it to the right slot.
4. Retrieve the current alarms, and check if the Unequipped alarm is cleared.
6. Retrieve the current alarms, and check if the Unequipped alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
This message indicates that a failure has been detected in the card. The possible
cause is card type error or the card configuration error in the LCT.
Procedure 7-100
3. Retrieve the current alarms, and check if the Type Mismatch alarm is cleared.
4. If the Type Mismatch alarm is detected yet, check whether the card type is
correct.
Procedure 7-101
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
7.3.7.4 Module
This message indicates that a failure of hardware is detected on the card. The
possible cause is broken hardware on the card.
Procedure 7-102
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
This message indicates that a failure of equipment internal Tx Bus Error has been
detected in the card. The possible cause is broken hardware on the card.
Procedure 7-103
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure of equipment internal Rx Bus Error has been
detected in the card. The possible cause is broken hardware on the card.
Procedure 7-104
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
7.3.7.7 E1 LOS
This message indicates that a failure of the E1 LOS (Loss Of Signal) is detected from
the incoming signal on the indicated facility. If this condition occurs, the problem is
on the cable connection or on the far-end NE.
Procedure 7-105
3. Retrieve the current alarms, and check if the LOS alarm is cleared. If the alarm is
not cleared, contact NEC for the appropriate maintenance support.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
7.3.7.8 E1 AIS
This message indicates that a failure of the AIS (Alarm Indication Signal) is detected
from the incoming signal on the indicated facility. If this condition occurs, the
problem is on the indicated line in the far-end NE.
Procedure 7-106
2. Retrieve the current alarms, and check if the AIS alarm is cleared. If the alarm is
not cleared, contact NEC for the appropriate maintenance support.
This step is the end of the procedure.
This message indicates that the E1 port, which is not enabled, received signal.
Procedure 7-107
3. Retrieve the current alarms, and check if the Usage Error alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
7.3.8.1 Unequipped
This message indicates that a failure has been detected in the registered slot. The possible
cause is the card is not inserted to the slot correctly.
Procedure 7-108
1. Pull out the card, and reinsert the card into the slot.
2. Retrieve the current alarms, and check if the Unequipped alarm is cleared.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
3. If the Unequipped alarm is detected yet, confirm that the card is located in the
specified slot, if not, move it to the right slot.
4. Retrieve the current alarms, and check if the Unequipped alarm is cleared.
6. Retrieve the current alarms, and check if the Unequipped alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure has been detected in the card. The possible
cause is card type error or the card configuration error in the LCT.
Procedure 7-109
3. Retrieve the current alarms, and check if the Type Mismatch alarm is cleared.
4. If the Type Mismatch alarm is detected yet, check whether the card type is
correct.
Procedure 7-110
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
7.3.8.4 Module
This message indicates that a failure of hardware is detected on the card. The
possible cause is broken hardware on the card.
Procedure 7-111
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure of equipment internal Tx Bus Error has been
detected in the card. The possible cause is broken hardware on the card.
Procedure 7-112
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure of equipment internal Rx Bus Error has been
detected in the card. The possible cause is broken hardware on the card.
Procedure 7-113
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
7.3.9.1 Unequipped
This message indicates that a failure has been detected in the registered slot. The possible
cause is the card is not inserted to the slot correctly.
Procedure 7-114
1. Pull out the card, and reinsert the card into the slot.
2. Retrieve the current alarms, and check if the Unequipped alarm is cleared.
3. If the Unequipped alarm is detected yet, confirm that the card is located in the
specified slot, if not, move it to the right slot.
4. Retrieve the current alarms, and check if the Unequipped alarm is cleared.
6. Retrieve the current alarms, and check if the Unequipped alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure has been detected in the port. The possible cause
is card type error or the card configuration error in the LCT.
Procedure 7-115
3. Retrieve the current alarms, and check if the Type Mismatch alarm is cleared.
4. If the Type Mismatch alarm is detected yet, check whether the card type is
correct.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
Procedure 7-116
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
7.3.9.4 Module
This message indicates that a failure of hardware is detected on the card. The
possible cause is broken hardware on the card.
Procedure 7-117
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure of equipment internal Tx Bus Error has been
detected in the card. The possible cause is broken hardware on the card.
Procedure 7-118
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure of equipment internal Rx Bus Error has been
detected in the card. The possible cause is broken hardware on the card.
Procedure 7-119
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure of the ETH LOS (Loss Of Signal) is detected
from the incoming signal on the indicated facility. If this condition occurs, the
problem is on the optical fiber or on the far-end NE.
Procedure 7-120
3. Retrieve the current alarms, and check if the LOS alarm is cleared. If the alarm is
not cleared, contact NEC for the appropriate maintenance support.
7.3.9.8 ETH TF
This message indicates that a failure has been detected in the installed SFP modules.
The possible cause is that SFP module failure.
Procedure 7-121
2. Retrieve the current alarms, and check if the TF alarm is cleared. If the alarm is
not cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure has been detected in the port. The possible cause
is SFP type error or the port configuration error in the LCT.
Procedure 7-122
1. For the Ethernet port, confirm their port configurations in the LCT.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
3. Retrieve the current alarms, and check if the SFP Type Mismatch alarm is
cleared.
4. If the SFP Type Mismatch alarm is detected yet, check whether the SFP type of
these ports is correct.
6. Retrieve the current alarms, and check if the SFP Type Mismatch alarm is
cleared. If the alarm is not cleared, contact NEC for the appropriate maintenance
support.
7. For other ports, check whether the SFP type of these ports is correct first.
8. If not, replace the SFP type, and insert the correct SFP to specified port.
9. Retrieve the current alarms, and check if the SFP Type Mismatch alarm is
cleared. If the alarm is not cleared, contact NEC for the appropriate maintenance
support.
This message indicates that a failure has been detected in the registered port. The
possible cause is removed of the SFP module.
Procedure 7-123
1. Pull out the SFP module, and reinsert it into the port.
2. Retrieve the current alarms, and check if the SFP Unequipped alarm is cleared.
3. If the SFP Unequipped alarm is detected yet, confirm that the SFP module is
located in the specified port, if not, move it to the right port.
4. Retrieve the current alarms, and check if the SFP Unequipped alarm is cleared.
6. Retrieve the current alarms, and check if the SFP Unequipped alarm is cleared. If
the alarm is not cleared, contact NEC for the appropriate maintenance support.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
This message indicates that a failure of Ethernet Link down is detected on the
indicated port. If this condition occurs, the problem is on the optical fiber or on the
far-end NE.
Procedure 7-124
3. Retrieve the current alarms, and check if the LAN LINK alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
7.3.10.1 Unequipped
This message indicates that a failure has been detected in the registered slot. The possible
cause is the card is not inserted to the slot correctly.
Procedure 7-125
1. Pull out the card, and reinsert the card into the slot.
2. Retrieve the current alarms, and check if the Unequipped alarm is cleared.
3. If the Unequipped alarm is detected yet, confirm that the card is located in the
specified slot, if not, move it to the right slot.
4. Retrieve the current alarms, and check if the Unequipped alarm is cleared.
6. Retrieve the current alarms, and check if the Unequipped alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
This message indicates that a failure has been detected in the card. The possible
cause is card type error or the card configuration error in the LCT.
Procedure 7-126
3. Retrieve the current alarms, and check if the Type Mismatch alarm is cleared.
4. If the Type Mismatch alarm is detected yet, check whether the card type is
correct.
Procedure 7-127
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
7.3.10.4 Module
This message indicates that a failure of hardware is detected on the card. The
possible cause is broken hardware on the card.
Procedure 7-128
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
This message indicates that a failure of equipment internal Tx Bus Error has been
detected in the card. The possible cause is broken hardware on the card.
Procedure 7-129
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure of equipment internal Rx Bus Error has been
detected in the card. The possible cause is broken hardware on the card.
Procedure 7-130
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
This message indicates that packet to TDM jitter buffer underrun is detected on the
pseudo-wire connection. If this condition occurs, the problem is on the cable
connection or on the far-end NE, or caused by packet jitter in the network.
Procedure 7-131
3. Retrieve the current alarms, and check if the TDM Buffer Underrun alarm is
cleared. If the alarm is not cleared, contact NEC for the appropriate maintenance
support.
4. Increasing jitter buffer size may solve the issue if the alarm is caused by packet
jitter in the network. This step is the end of the procedure.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
7.3.11.1 Unequipped
This message indicates that a failure has been detected in the registered slot. The possible
cause is that the card is not properly inserted to the correct slot.
Procedure 7-132
2. Pull out the card, and reinsert the card securely into the correct slot.
3. Retrieve the current alarms, and check if the Unequipped alarm is cleared.
5. Retrieve the current alarms, and check if the Unequipped alarm is cleared. If the
alarm is not cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure has been detected in the card. The possible
cause is card type error or the card configuration error in the LCT.
Procedure 7-133
3. Retrieve the current alarms, and check if the Type Mismatch alarm is cleared.
4. If the Type Mismatch alarm is detected yet, check whether the card type is
correct.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Procedure 7-134
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
7.3.11.4 Module
This message indicates that a failure of hardware is detected on the card. The
possible cause is broken hardware on the card.
Procedure 7-135
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure of equipment internal Tx Bus Error has been
detected in the card. The possible cause is broken hardware on the card.
Procedure 7-136
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
This message indicates that a failure of equipment internal Rx Bus Error has been
detected in the card. The possible cause is broken hardware on the card.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
Procedure 7-137
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
This message indicates that a hardware failure is detected from the clock module.
1. Check the temperature of the equipment or around the equipment, and lower it if
it is out of the operational range.
3. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
This message indicates that the PTP Sync packets from the Master are lost.
Procedure 7-138
1. Check if any alarms or packet losses are detected in the network, and clear
it/them, if any.
2. Check if any alarms are issued to the PTP Master or Boundary clock facility, and
clear it/them, if any.
3. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
This message indicates that the PTP Announce packets from the Master are lost.
Procedure 7-139
1. Check if any alarms or packet losses are detected in the network, and clear
it/them, if any.
2. Check if any alarms are issued to the PTP Master or Boundary clock facility,
and clear it/them, if any.
3. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
7.3.11.10 Unusable
This message indicates that the received PTP packets are not available. This
condition is caused if:
PTP packets (Sync, Delay_req, DelayResp) from the Master have large PDV
(Packet Delay Variation).
Fixed latency difference of each direction to/from the Master within the
network has varied enormously.
Procedure 7-140
Fixed latency difference of each direction to/from the Master within the
network are the same.
If any alarms or packet losses are detected in the network, clear it/them.
If any alarms are issued to the PTP Master or Boundary clock facility, clear
it/them.
2. Retrieve the current alarms, and check if the alarm is cleared. If the alarm is not
cleared, contact NEC for the appropriate maintenance support.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
This message indicates that all of member ports belonged to the radio group are
down.
Procedure 7-141
This message indicates that mismatch exists between configuration and installed
FPGA Version or between two opposite MODEMs settings.
Procedure 7-142
1. Check the Radio Traffic Aggregation configuration and FPGA Version in the
IDU.
2. If there exists mismatch, set the correct configuration or download the correct
Version of FPGA.
3. Retrieve the current alarms, and check if the Radio Traffic Aggregation Setting
Mismatch alarm is cleared.
4. If the Radio Traffic Aggregation Mismatch alarm is detected yet, check if there
is any problem in Radio Traffic Aggregation configuration in the equipment at
another side.
This message indicates that all of member ports belonged to the ETH Link
Aggregation group are down.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Procedure 7-143
This message indicates that Link OAM keepalive protocol timeout is detected. The
possible cause is in the opposite NE via Ethernet link, equipment configuration of
link OAM or failure.
Procedure 7-144
3. Retrieve the current alarms, and check if the Link OAM Down alarm is cleared.
If the alarm is not cleared, contact NEC for the appropriate maintenance support.
This message indicates that the opposite NE via Ethernet link detects Ethernet link
fault in the receive side.
Procedure 7-145
3. Retrieve the current alarms, and check if the Remote Link Fault alarm is cleared.
If the alarm is not cleared, contact NEC for the appropriate maintenance support.
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
This message indicates that the opposite NE via Ethernet link is under reboot
condition.
Procedure 7-146
3. Retrieve the current alarms, and check if the Remote Dying Gasp alarm is
cleared. If the alarm is not cleared, contact NEC for the appropriate maintenance
support.
This message indicates that a failure of hardware is detected in the opposite NE via
Ethernet link.
Procedure 7-147
2. Retrieve the current alarms and check if the Remote Critical Event alarm is
cleared. If the alarm is not cleared, contact NEC for the appropriate maintenance
support.
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
Figure 7-15 Alarm Action Table for STM-1 Interface (Channelized Mode)
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
Figure 7-16 Alarm Action Table for STM-1 Interface (Through Mode)
NWD-115477-06E Maintenance
Submission Prohibited
NEC Group Internal Use Only
7.3.15.3 E1 Interface
Maintenance NWD-115477-06E
Submission Prohibited
NEC Group Internal Use Only
NWD-115477-06E Maintenance