SWITC H G EAR
C O M P L E X
INTRODUCTION FIG. 1
Crompton Greaves Ltd. have manufactur ed and
1
supplied thousands of quality electrical products for
the past six decades which have excelled in various
2
test and service environments around the world.
Nearly 2000 Inductive Voltage Transformers, type 3 12
DESIGN
Voltage Transformers (VTs) are used to transform
high system voltages (kV) to low measurable values
(Volts).
6
quality kraft paper is used to wind the bushings 6 PORCELAIN INSULATOR 15 RATING/SCHEMATIC.PLATE
using a Wide Band Bushing Winding machine. The 7 HOUSING 16 SECONDARY TERMINALS
paper insulation is dried under heat and vacuum and 8 PRIMARY WINDING 17 GLAND PLATE
CONSTRUCTION
MAX.
The VT head is equipped with the primary terminal.
MIN.
The head accomodates an oil communicating type
stainless steel bellow to compensate for changes in
oil volume due to changes in the ambient temperature.
The bellow renders the VT truly hermetically sealed
and, at the same time, removes any chances of
abnormal internal pressure variation. A window is
provided at the top to indicate the bellow level and
thus the oil level in the VT.
The porcelains are cemented to aluminium alloy
ARCING DISTANCE
flanges on both sides with portland cement to provide
optimum mechanical strength. Brown glazed porcelain
of shed profile as per IEC 815 is used. Grey porcelains
or variant shed profiles can also be supplied against spe-
H
cific customer requirement.
The bottom tank is made of high quality sheet steel H1
TRANSPORT
All IVTs are transported in horizontal position except
W
for 72.5 kV IVT which is transported vertically.
BOTTOM VIEW
MAINTENANCE
The product is self contained, maintenance free and
doesnot require any spares throughout its service
life. For regular and periodic checks, please refer
the instruction manual.
1. TYPE DESIGNATION : UNITS IVT VEOT VEOT IVT VEOT
: IEC 44-2, 1997 (FORMERLY IEC 186, 1987)
2. APPLICABLE STANDARD
IS 3156, 1992
3. HIGHEST SYSTEM VOLTAGE : kV 72.5 123 145 170 245
4. ONE MIN POWER FREQUENCY
: kV 140 230 275 325 460
WITHSTAND VOLTAGE
5. 1.2/50 µ s IMPULSE WITHSTAND VOLTAGE : kVp 325 550 650 750 1050
6. RATED FREQUENCY : Hz 50/60
7. AMBIENT TEMPERATURE : °C -25 TO 50
8. SEISMIC ACCELERATION : g 0.3/0.5
9. RATED VOLTAGE FACTOR : - 1.2 (CONT) / 1.5 (30 SEC)
10. 1 MIN POWER FREQUENCY WITHSTAND
: kV 3
VOLTAGE ON SECONDARY WINDINGS
11. SECONDARY VOLTAGE : V 100, 100/√3, 110, 110/√3 , 120 , 120/√3
12. TOTAL CREEPAGE DISTANCE : mm 1810 3075 3625 4250 6125
13. ARCING DISTANCE : mm 700 1100 1300 1400 2080
14. TOTAL SIMULTANEOUS
: - 300 VA / CL 0.5 500 VA / CL 0.5 500 VA / CL 0.5 500 VA / CL 0.5 500VA / CL 0.5
BURDEN / ACCURACY
15. TOTAL THERMAL BURDEN : VA 500 VA 750 VA 750 VA 1000 VA 1000 VA
16. CANTILEVER LOAD : kG 125 200 200 200 250
17. TOTAL HEIGHT (WITHOUT SUPPORT
: mm 1810 2725 2725 3080 3830
STRUCTURE) (H)
18. TOTAL HEIGHT UPTO HV TERMINAL (H 1) : mm 1810 2375 2375 2670 3370
19. MAXIMUM WIDTH (A) : mm 700 790 790 930 980
20. MOUNTING DIMENSIONS (W) : mm 375 X 375 450 X 450 450 X 450 600 X 600 600 X 600
21. TOTAL WEIGHT : kG 230 400 400 575 650
22. QTY OF INSULATING OIL : kG 50 50 50 100 110
23. PROVISION FOR COMPENSATION
- STAINLESS STEEL BELLOW
OF OIL VOLUME EXPANSION
24. TYPE OF SECONDARY TERMINAL BLOCKS : - CLIP ON STUD TYPE
OPTIONALS
TYPE DESIGNATION : UNITS IVT VEOT VEOT IVT VEOT
1. HIGHEST SYSTEM VOLTAGE : kV 72.5 123 145 170 245
2. VOLTAGE FACTOR : - 1.9 FOR 30 SEC —
3. CREEPAGE DISTANCE : mm/kV 31/35/40
4. TOTAL SIMULTANEOUS
: - 100 VA / CL 0.2 200 VA / CL 0.2
BURDEN / ACCURACY
Power Systems
A Business Unit of Crompton Greaves Ltd.
Quality through care. Care through quality.
Inst. Trans. & Bushing Divn.
Switchgear Complex
A-3, MIDC, Ambad, Nashik : 422 010, India,
Tel: +91-253-382271 to 75,
Fax: +91-253-381247 The Thapar Group
Regd. Office : 6th Floor, CG House, Dr. Annie Besant Road, Prabhadevi, Mumbai - 400 025, India. CG-S&C/EXP/Cat. No. IT 111/4/99/3000