Project: ETAP Page: 1

Location: 16.1.1C Date: 01-12-2018

Contract: SN: TATASTEEL6

Engineer: Revision: Base


Study Case: SC
Filename: TCC SLD 120118 Config.: Normal

Short-Circuit Summary Report

3-Phase Fault Currents

Device Capacity (kA)


Bus Device Making Short-Circuit Current (kA)
ID kV ID Type Peak Ib sym Ib asym Idc I"k ip Ib sym Ib asym Idc Ik
Bus1 6.600 Bus1 Bus 43.057 109.292 40.000

6.600 B/C CB 100.000 40.000 43.787 17.812 41.696 106.267 * 40.830 * 44.514 * 17.733

6.600 CB9 CB 100.000 40.000 43.787 17.812 43.057 109.292 * 41.448 * 45.113 * 17.810

6.600 CB27 CB 100.000 40.000 43.787 17.812 43.057 109.292 * 41.448 * 45.113 * 17.810

6.600 Fuse2 Fuse 80.000 106.462 42.830 108.793 42.459 63.653 47.423

6.600 Fuse6 Fuse 80.000 106.462 42.606 108.274 42.243 63.364 47.229

6.600 Fuse5 Fuse 80.000 106.462 42.698 108.488 42.334 63.485 47.309

6.600 Fuse7 Fuse 80.000 106.462 42.913 108.981 42.533 63.754 47.492

6.600 Fuse13 Fuse 80.000 106.462 42.877 108.899 42.502 63.711 47.463

ip is calculated using method C


Ib does not include decay of non-terminal faulted induction motors
Ik is the maximum steady state fault current
Idc is based on X/R from Method C and Ib as specified above

LV CB duty determined based on service rating.


Maximum through current is used for device duty.
* Indicates a device with calculated duty exceeding the device capability.
# Indicates a device with calculated duty exceeding the device marginal limit. ( 95 % times device capability)
Project: ETAP Page: 2

Location: 16.1.1C Date: 01-12-2018

Contract: SN: TATASTEEL6

Engineer: Revision: Base


Study Case: SC
Filename: TCC SLD 120118 Config.: Normal

Short-Circuit Summary Report

Device Capacity 3-Phase Short-Circuit Duty Results


Rated Thermal Thermal
Bus ID Device ID Ithr (kA) Tkr (sec.) Energy (MJ) Ith (kA) Tkr (sec.) Energy (MJ)

Bus1 B/C 40.000 3.00 4800.00 40.915 3.00 5022.23 *

Bus1 CB9 40.000 3.00 4800.00 40.915 3.00 5022.23 *

Bus1 CB27 40.000 3.00 4800.00 40.915 3.00 5022.23 *

Ithr = Rated short-time withstand current (Icw for low voltage circuit breaker)
Tkr = Rated short-time
Ith = Thermal equivalent short-time current

* Indicates a device with calculated duty exceeding the device capability.


# Indicates a device with calculated duty exceeding the device marginal limit. ( 95 % times device capability)