Vous êtes sur la page 1sur 3

• The transformer is short-circuit

Requirements for
TECHNICAL
proof (both inherently and
non-inherently) and marked with
the following symbol:
extra-low voltage
(ELV) lighting
installations Electronic convertors used for ELV
lighting installations must comply
with BS EN 61347-2-2 and be
marked with the following symbol:
Extra-low voltage (ELV) lighting is commonly
used in domestic and commercial installations,
particularly in the form of recessed
downlighter luminaires (see Figure 1)
Enclosure of connections
No less than for LV connections,
all connections (terminations and

S
pecific requirements relating an ELV luminaire does not have joints) in (or to) an ELV lighting
to ELV lighting installations a provision for connection of a circuit must be enclosed in
were newly introduced in BS 7671: protective conductor, only a SELV accordance with Regulation 526.5
2008 in Regulation Group 559.11, system may be used to supply the to help prevent spread of possible
as summarised in this article. The luminaire (Regulation 559.11.2 refers). fire should a loose connection
article also includes information on Safety isolation transformers occur.
the requirements for the enclosure of used for ELV lighting installations Many ELV luminaires are provided
terminations and joints in ELV lighting must comply with BS EN 61558-2-6 complete with an enclosure for
installations and on methods to be and meet with at least one of the the connections between the
employed for minimising the spread following two requirements of ELV circuit conductors and the
of fire when installing downlighters. Regulation 559.11.3.1. luminaire terminals. Figure 2
• The transformer is protected shows an example of this where
Shock protection measures on the primary side by a the enclosure is separate from
and supplies fail-safe protective device the luminaire. Figure 3 shows an
ELV supplies used for lighting should that monitors the power example where the enclosure is
be taken from a system meeting demand of the luminaires and attached to the luminaire.
the requirements for the protective automatically disconnects the If a luminaire is provided without
measures of SELV or PELV. It is not supply in the event of one of a suitable enclosure for the ELV
permitted to use an FELV system a number of specified fault or connections, the installer must
for an ELV lighting installation failure conditions, as detailed in provide an appropriate enclosure
(Regulation 559.11.1 refers). Where Regulation 559.11.4.2. complying with Regulation 526.5.

1 A typical use of ELV lighting in commercial premises

56 Spring 2009 NICEIC Connections www.niceic.com


Extra-low voltage
luminaire terminals
Transformer
Low voltage
joint box

Secure cable clamps


required at junction box entries

Detail of low voltage junction box

2 Example of ELV luminaire with ELV connections in an enclosure separate from the luminaire

Extra-low voltage
luminaire terminals
Transformer
Low voltage
joint box

Secure cable clamps


required at junction box entries

Detail of luminaire ceiling entry

3 Example of an ELV luminaire with ELV connections in an enclosure attached to the luminaire
Table 1: Minimum permitted cross-sectional area for ELV lighting circuit
Wiring systems
conductors
Table 1, which is based on the
General 1.5 mm2 requirements of Regulation 559.11.5.2,
Flexible cables of a length not exceeding 3 m 1.0 mm2 gives the minimum permitted
Suspended flexible cables or insulated conductors 4.0 mm2 cross-sectional area for the
conductors of an ELV lighting circuit.
Composite cables consisting of braided tinned copper outer 4.0 mm2
Larger conductor sizes may be
sheath, having a material of high tensile strength inner core
required in some cases, as explained
Note: Larger conductor sizes may be required in some cases to meet the requirements of
in the note to the table.
Section 525 of BS 7671 for voltage drop (depending on the number of luminaires supplied and
the length of run from the transformer) and Regulation Group 433.1 for co-ordination between
It is not permitted to use metallic
conductor and overload protective device. structural parts of the building or its

www.niceic.com NICEIC Connections Spring 2009 57


TECHNICAL

4 Part of a typical suspended ELV lighting system 5 Example of a downligher with integral fire protection

event of one of a number of downlighters are exposed to a fire


specified fault or failure from below, they may provide far
conditions, as detailed in less fire protection to a ceiling and
Regulation 559.11.4.2. the structural elements within it
• The system complies with than the plasterboard that they
BS EN 60598-2-23 – Luminaires. are replacing. It is recommended
Particular requirements. that, wherever possible,
Extra-low voltage lighting systems downlighters having integral
for filament lamps. Such a system fire protection (see Figure 5) are
is constructed so that the selected for use in all ceilings where
temperature of the conductors in the lining to be penetrated is the
the output circuit does not rise sole means of keeping fire and heat
by more than 10 ºC under short- out of the cavity.
circuit conditions. Where integral fire protection is
6 Example of a fire hood, for use Where suspended bare conductors not available owing to the design
with a downlighter without integral are used, at least one conductor and or style of the luminaire, additional
fire protection its terminals must be insulated for fire protection may be fitted at
that part of the circuit between the the time of installation in the
services installations (such as transformer and any short-circuit form of a ‘fire hood’ (see Figure 6)
pipes) or furniture as live conductors protective device on the or an insulated fire-protective box
of an ELV lighting installation. secondary side of the transformer. or similar.
Regulation 559.11.5.1 refers. Regulation 559.11.5.3 refers. Insulated fire-protective boxes, fire
hoods and the like must be fit for the
Bare conductors Suspended systems purpose and not be easily dislodged
If the nominal voltage does not Where the ELV system is suspended after installation by subsequent
exceed 25 V a.c. or 60 V d.c., bare (see Figure 4), the suspension work. Guidance on selecting them is
conductors may be used for ELV device(s) must be capable of given in Annex E of the Best Practice
lighting, provided that supporting five times the weight Guide mentioned at the end of
• the installation is designed and of the luminaire and its lamp, and this article.
installed or enclosed to reduce to a not less than 5 kg. The suspended
minimum the risk of a short-circuit, system must be fixed to the walls by Further
• the conductors have a insulated cleats and be accessible information
cross-sectional area not less throughout its length. Termination relating to
than 4 mm2, and and connection methods must use the impact
• the conductors are not placed either screw terminals or screwless of electrical
directly on combustible material. clamping devices, complying with installations
(Regulation 559.11.5.3 refers) the appropriate standard. It is not on the fire
Where both live conductors permitted to use insulating piercing performance
are uninsulated, one of the connections and termination of buildings
following two requirements of wires relying on counterweights to can be
Regulation 559.11.4.1 must be met maintain the electrical connection. found in the
to reduce the risk of fire. Regulation 559.11.6 refers. Electrical
• The conductors are provided with Safety Council’s Best Practice Guide
a fail-safe protective device that Containing the spread of fire where No5 Electrical installations and their
monitors the power demand of recessed downlighters are used impact on fire performance of buildings,
the luminaires and automatically Unless suitable precautions which is available as a free download
disconnects the supply in the have been taken, when recessed at www.esc.org.uk

58 Spring 2009 NICEIC Connections www.niceic.com

Vous aimerez peut-être aussi