Integra-TR is configured as DCE. DTE devices should be connected using a nine-conductor pin-to-pin straight cable (PN 697-
4008-408). Some RTUs or PLCs may require a special cable to route the signals correctly. Refer to your data equipment
documentation package.
DTE baud rates from 1200 to 19200 are supported. Integra-TR's are factory set for or 9600 b/s, 8 bits, no parity, and 1 stop
bit. Unless required by your operating protocol, we advise restricting port speed to be equal to or less than the RF network
speed.
5 4 3 2 1
9 8 7 6
Page | 8
For DTE that lack RTS control, Integra-TR can operate in DOX (Data Operated Transmit) mode with only Transmit Data,
Receive Data and Ground. This 3-wire interface is shown in Figure XX.
The Setup port uses a DE-9 female connector configured as DCE. Signals are described in Table 3.
The Setup port uses a proprietary communications protocol designed to work with the Integra-TR Field Programming
Software program. It is also designed to provide alpha numeric (ASCII) diagnostics information when connected to a PC
terminal emulator.
Page | 9