STATIC PRESSURE

CALUCLATIONS
STATIC PRESSURE

Static pressure is defined as pressure


applied to over come all frictional losses
in the system
Categories of Static Pressure
Static pressure is categorized in to two types
• External static pressure ( E.S.P )
• Internal static pressure ( I.S.P )

Total Static pressure = External static pressure +


Internal static pressure

T.S.P = I.S.P + E.S.P


• Internal Static Pressure
pressure required to gain frictional losses
inside the machine
• External Static Pressure
Pressure required to gain frictional losses out
side the machine i.e..inside the Duct Network
Static pressure

Internal static External static


pressure pressure

ESP in standard
Coil Filters ESP In Straight Ducts
equipment

Volume
Flexible Fire Sound
Elbow Collar Reducer control
Duct dampers attenuators
damper
CALCULATE EXTERNAL STATIC PRESSURE FOR
DUCT NETWORK
E.S.P FOR STRAIGHT DUCTS
SECTION CFM FRICTION LENGTH OF DUCT STATIC PRESSURE
(F) (L) F*L/100
WG/ ’ (FEET) WG

Table - 1
SECTION : A

SECTION CFM FRICTION LENGTH OF DUCT STATIC PRESSURE


(F) (L) F*L/100
WG/ ’ (FEET) WG

A 2201 0.04 5.33 0.0021

Table - 2
SECTION : B

SECTION CFM FRICTION LENGTH OF STATIC


(F) DUCT PRESSURE
WG/ ’ (L) F*L/100
(FEET) WG

A 2201 0.04 5.33 0.0021


B 660 0.04 10.61 0.0042

Table - 3
SECTION : C

SECTION CFM FRICTION LENGTH OF DUCT STATIC PRESSURE


(F) (L) F*L/100
WG/ ’ (FEET) WG

A 2201 0.04 5.33 0.0021


B 660 0.04 10.61 0.0042
C 1077 0.04 11.33 0.0045

Table - 4
SECTION : D

SECTION CFM FRICTION LENGTH OF DUCT STATIC PRESSURE


(F) (L) F*L/100
WG/ ’ (FEET) WG

A 2201 0.04 5.33 0.0021


B 660 0.04 10.61 0.0042
C 1077 0.04 11.33 0.0045
D 562 0.04 9.41 0.0037

Table - 5
SECTION : E
SECTION CFM FRICTION LENGTH OF STATIC
(F) DUCT PRESSURE
WG/ ’ (L) FXL/100
(FEET) WG

A 2201 0.04 5.33 0.0021


B 660 0.04 10.61 0.0042
C 1077 0.04 11.33 0.0045
D 562 0.04 9.41 0.0037
E 515 0.04 3.41 0.0013
Table - 6

E.“.P IN “TRAIGHT DUCT“ = . 8 WG


FINDING FRICTIONAL LOSS IN VCD

Table - 7
FRICTIONAL LOSS CALCULATION FOR VCD

∆P = CO *(V/4005)2

∆P = . *(800/4005)2
∆P = . Inches of WG

Table - 7
PRESSURE DROP IN VCD

SECTION DUCT SIZE VELOCITY (FPM) CO ∆P=CO * (V/4005)2

A 22X20 800 0.76 0.030324


B 16X16 593 1.1 0.024116
D 14X12 570 1.32 0.026737
E 12X 12 560 2.41 0.047118

Table - 8

Here the flow rate and head loss is taken from


Table no 3

Face velocity Fpm for


section B
PRESSURE DROP CALULATION FOR FITTINGS
PRESSURE DROP COEFFICIENTS FOR FITTINGS
(co)
Reducer 0.25
Elbow 0.27
wye 0.3

Tee 0.37
Table - 9
REDUCER
ELBOW

VELOCITY
SECTION Duct name DUCT SIZE
(FPM) CO ∆P=CO * V/4005)2

C reducer 16 X 16 670 0.25 0.00699656

B elbow 14 X 12 593 0.27 0.005919269

Table - 10
PRESSURE DROP IN COLLAR

COLLER
COLLER

COLLER

SECTION DUCT SIZE VELOCITY (FPM) CO ∆P=CO * (V/4005)2

B 14 X 12 593 0.25 0.005480805


D 14 X 12 570 0.25 0.005063895
E 12 X 12 560 0.25 0.004887773
Table - 11
PRESSURE DROP IN FLEXIBLE DUCTS
Pressure losses in Flexible Duct
Nominal Diameter Static Pressure Drop
Compression CFM
(inches) Inch.water/100ft
Fully stretch 90-430 0.08-1.98
Normal stretch 80-400 0.3-6.63
Compressed 90-390 0.72-12.36
Fully stretch 110-480 0.02-0.41
” Normal stretch 100-470 0.08-1.65
Compressed 110-470 0.16-2.46
Fully stretch 150-450 0.02-0.41
” Normal stretch 130-450 0.04-0.48
Compressed 130-460 0.07-0.78

Table - 12

Here we have 4 Diffuser


These 4 diffuser are connected
with four flexible ducts
4 * 6.63/100 = 0.26 Inch.wg

4 3 2 1
PRESSURE DROP IN FITTINGS AND STANDARD EQUIPMENTS
SECTION : A

Table - 12

Section Item Name Duct Size Static pressure(In.WG/100ft)


A VCD 22 X 20 0.03
S.A 22 X 20 0.02
FLEXIBLE DUCT Ø 6" 0.06
Table - 13
* For Sound attenuators the static pressure is taken from manufacture data
SECTION : B

Section Item Name Duct Size Static pressure(In.WG/100ft)


A VCD 22 X 20 0.03
S.A 22 X 20 0.02
FLEXIBLE DUCT Ø 6" 0.06
B VCD 14 X 12 0.04
COLLAR 14 X 12 0.0054
ELBOW 14 X 12 0.005
FLEXIBLE DUCT Ø 6" 0.06
Table - 14
SECTION:C

Section Item Name Duct Size Static pressure(In.WG/100ft)


A VCD 22 X 20 0.03
S.A 22 X 20 0.02
FLEXIBLE DUCT Ø 6" 0.06
B VCD 14 X 12 0.04
COLLAR 14 X 12 0.0054
ELBOW 14 X 12 0.005
FLEXIBLE DUCT Ø 6" 0.06
C REDUCER 16 X16 0.0069
Table - 15
SECTION :D

Static
Section Item Name Duct Size pressure(In.WG/100ft)
A VCD 22 X 20 0.03
S.A 22 X 20 0.02
FLEXIBLE DUCT Ø 6" 0.06
B VCD 14 X 12 0.04
COLLAR 14 X 12 0.0054
ELBOW 14 X 12 0.005
FLEXIBLE DUCT Ø 6" 0.06
C REDUCER 16 X16 0.0069
D VCD 14 X 12 0.05
Table - 16
SECTION E

Static
Section Item Name Duct Size pressure(In.WG/100ft)
A VCD 22 X 20 0.03
S.A 22 X 20 0.02
FLEXIBLE DUCT Ø 6" 0.06
B VCD 14 X 12 0.04
COLLAR 14 X 12 0.0054
ELBOW 14 X 12 0.005
FLEXIBLE DUCT Ø 6" 0.06
C REDUCER 16 X16 0.0069
D VCD 14 X 12 0.05
COLLER 14 X 12 0.005
FLEXIBLE DUCT Ø 6" 0.06
E VCD 12 X 12 0.05
COLLER 12X 12 0.0048
FLEXIBLE DUCT Ø 6" 0.06

Table - 17
TOTAL STATIC PRESSURE IN FITTINGS &STANDARD EQUIPMENT
Static
Section Item Name Duct Size pressure(In.WG/100ft)
A VCD 22 X 20 0.03
S.A 22 X 20 0.02
FLEXIBLE DUCT Ø 6" 0.06
B VCD 14 X 12 0.04
COLLAR 14 X 12 0.0054
ELBOW 14 X 12 0.005
FLEXIBLE DUCT Ø 6" 0.06
C REDUCER 16 X16 0.0069
D VCD 14 X 12 0.05
COLLER 14 X 12 0.005
FLEXIBLE DUCT Ø 6" 0.06
E VCD 12 X 12 0.05
COLLER 12X 12 0.0048
FLEXIBLE DUCT Ø 6" 0.06
Table - 18
Total static pressure in fittings &standard equipment = 0.46Inch.wg
Total external static pressure = E.S.P In straight Duct + E.S.P in fittings and standard equipment

Total external static pressure = 0.015 + 0.5 = 0.515Inch.wg


There are three methods to use this External static pressure

Method-1
To place the order for Air handling unit we need to provide the
details like

External Static pressure


Duct length
Duct Maximum size
Total CFM
Total TR
 AHU room size
Coin connection considerations
Filtration level
Internal Static pressure (I.S.P)
Pressure Drop for Filters
• Fine filters - 0.0981 Inch / wg
• Pre filters - 0.19 – 0.75 Inch / wg
• HEPA - 0.98 – 2.95 Inch / wg
Pressure drop for coil
• 2 Row coil - 0.11 Inch of wg - 8 fins/Inch
• 4 Row coil - 0.22Inch of wg – 8fins/Inch
Here we are using a fine filter and a 2 Row coil
There fore 0.98+0.11 = 1.09 Inch/Wg

Total Static pressure = External static pressure + Internal static pressure


= 0.46 +1.09
= 1.55 Inches of Wg
Method-2
CFM x total static pressure (ESP+ISP)
HP =
6356 x ɳ of motor x ɳ of blower

2202 CFM x 1.59 IN.WC


HP =
6356 x 0.8 x 0.75

Horse Power of Blower Motor = 0.91


Method-3

CFM = 6000 to 15000


ESP = up to . wg”
Example:
 CFM= 10000
 ESP = 0.8
Rpm = 600
HP= 4