CALUCLATIONS
STATIC PRESSURE
ESP in standard
Coil Filters ESP In Straight Ducts
equipment
Volume
Flexible Fire Sound
Elbow Collar Reducer control
Duct dampers attenuators
damper
CALCULATE EXTERNAL STATIC PRESSURE FOR
DUCT NETWORK
E.S.P FOR STRAIGHT DUCTS
SECTION CFM FRICTION LENGTH OF DUCT STATIC PRESSURE
(F) (L) F*L/100
WG/ ’ (FEET) WG
Table - 1
SECTION : A
Table - 2
SECTION : B
Table - 3
SECTION : C
Table - 4
SECTION : D
Table - 5
SECTION : E
SECTION CFM FRICTION LENGTH OF STATIC
(F) DUCT PRESSURE
WG/ ’ (L) FXL/100
(FEET) WG
Table - 7
FRICTIONAL LOSS CALCULATION FOR VCD
∆P = CO *(V/4005)2
∆P = . *(800/4005)2
∆P = . Inches of WG
Table - 7
PRESSURE DROP IN VCD
Table - 8
Tee 0.37
Table - 9
REDUCER
ELBOW
VELOCITY
SECTION Duct name DUCT SIZE
(FPM) CO ∆P=CO * V/4005)2
Table - 10
PRESSURE DROP IN COLLAR
COLLER
COLLER
COLLER
Table - 12
4 3 2 1
PRESSURE DROP IN FITTINGS AND STANDARD EQUIPMENTS
SECTION : A
Table - 12
Static
Section Item Name Duct Size pressure(In.WG/100ft)
A VCD 22 X 20 0.03
S.A 22 X 20 0.02
FLEXIBLE DUCT Ø 6" 0.06
B VCD 14 X 12 0.04
COLLAR 14 X 12 0.0054
ELBOW 14 X 12 0.005
FLEXIBLE DUCT Ø 6" 0.06
C REDUCER 16 X16 0.0069
D VCD 14 X 12 0.05
Table - 16
SECTION E
Static
Section Item Name Duct Size pressure(In.WG/100ft)
A VCD 22 X 20 0.03
S.A 22 X 20 0.02
FLEXIBLE DUCT Ø 6" 0.06
B VCD 14 X 12 0.04
COLLAR 14 X 12 0.0054
ELBOW 14 X 12 0.005
FLEXIBLE DUCT Ø 6" 0.06
C REDUCER 16 X16 0.0069
D VCD 14 X 12 0.05
COLLER 14 X 12 0.005
FLEXIBLE DUCT Ø 6" 0.06
E VCD 12 X 12 0.05
COLLER 12X 12 0.0048
FLEXIBLE DUCT Ø 6" 0.06
Table - 17
TOTAL STATIC PRESSURE IN FITTINGS &STANDARD EQUIPMENT
Static
Section Item Name Duct Size pressure(In.WG/100ft)
A VCD 22 X 20 0.03
S.A 22 X 20 0.02
FLEXIBLE DUCT Ø 6" 0.06
B VCD 14 X 12 0.04
COLLAR 14 X 12 0.0054
ELBOW 14 X 12 0.005
FLEXIBLE DUCT Ø 6" 0.06
C REDUCER 16 X16 0.0069
D VCD 14 X 12 0.05
COLLER 14 X 12 0.005
FLEXIBLE DUCT Ø 6" 0.06
E VCD 12 X 12 0.05
COLLER 12X 12 0.0048
FLEXIBLE DUCT Ø 6" 0.06
Table - 18
Total static pressure in fittings &standard equipment = 0.46Inch.wg
Total external static pressure = E.S.P In straight Duct + E.S.P in fittings and standard equipment
Method-1
To place the order for Air handling unit we need to provide the
details like