Multilin F650

Feeder Protection & Bay Controller


The Multilin™ F650 has been designed for the protection, control and automation of feeders or related
applications. The Multilin F650 provides high speed protection and control for feeder management and
Protection & Control
bay control applications, and comes with a large LCD and single line diagrams that can be built for • Time, instantaneous & directional phase, neutral,
bay monitoring and control for various feeder arrangements including ring-bus, double breaker or for ground and sensitive ground overcurrent
breaker and half. • Manual close with cold load pick up control,
forward power and directional power units
Designed with advanced communications options and detailed monitoring capabilities, the Multilin F650
provides advanced functionality, including high-performance protection, extensive control functions • Load encroachment supervision
and flexible configuration capabilities. The Multilin F650 can also be used for a variety of applications • Wattmetric ground fault detection
other than feeder protection and control.
• Positive and negative sequence based over/
under voltage elements
Key Benefits • Four-shot autorecloser with synchronism check
• Comprehensive and flexible protection and control device for feeder applications • Trip circuit supervision, breaker control and
• Increased system uptime and improved system stability with load shedding and transfer schemes breaker failure

• Advanced automation capabilities for customized protection and control solutions • Frequency protection (rate of change, under
and over frequency)
• Human Machine Interface (HMI) with graphical LCD, programmable buttons, and easy keys for
selecting setting menus, and submenus • Broken conductor and locked rotor

• Reduced replacement time with modular draw-out construction • Programmable digital inputs and outputs

• Reduced troubleshooting time and maintenance costs with IEEE 1588 (PTP), IRIG-B and SNTP time
®

synchronization, event reports, waveform capture, and data logger


Monitoring & Metering
• Simplified system integration with communications supporting serial and Ethernet interfaces as well
• Fault locator, fault and event recorder
as multiple protocols
• Comprehensive breaker monitoring
• Embedded IEC® 61850 protocol (and support for edition 2), IEC 60870-5-103, IEC 62439/PRP/HSR,
IEEE 802.1D/RSTP • High resolution oscillography and data logger
with programmable sampling rate

Applications • Metering: V, I, Hz, W, VA, PF

• Primary or back-up protection and control for feeders on solidly grounded, high impedance grounded • Demand: Ia, Ib, Ic, Ig, Isg, I2, MW, MVA
or resonant (Peterson Coil) grounded systems
• Bus blocking/interlocking schemes EnerVista Software
• High-speed fault detection for arc flash • Simplified setup, configuration and
• Throw over schemes (bus transfer scheme applications) commissioning
• Load shedding schemes based on voltage and frequency elements • Strong document archive and
• Back-up protection of various high voltage applications management system

• Distributed Generation (DG) interconnect protection, including active and passive anti-islanding • Simplified full featured monitoring and
data recording
• Seamless integration toolkit
F650 Feeder Protection & Bay Controller

Protection and Control Directional supervision is available for phase, Over/Under Frequency Protection
neutral, ground and sensitive ground currents.
The F650 provides high speed protection and The F650 offers overfrequency and
The neutral/ground directional elements
control for feeder management and bay control underfrequency elements to improve network
can be programmed to work under zero-
applications, including: (grid) stability using voltage or frequency based
sequence voltage, ground sensitive current or
loadshedding techniques. It also allows to
dual polarization.
Overcurrent Protection provide back up protection and trip breakers
directly when protecting feeders and other
Instantaneous and time over­current functions Over/Under Voltage Protection
frequency sensitive power equipment.
are available for phase, neutral, ground/sensitive
The F650 includes the following voltage elements:
ground and negative sequence currents. A
• Phase undervoltage/overvoltage elements
Frequency Rate of Change Protection
variety of time curves are provided including
IEEE/ANSI®, IEC A/B/C/long time inverse/short (each element has three individual phase Frequency rate of change (df/dt) elements
time inverse, GE IAC, I2t, definite time, rectifier undervoltage/overvoltage components) included in the F650 provide protection against
curve and four user-programmable curves. • Auxiliary undervoltage/overvoltageelement system disturbances through load shedding.

• Neutral overvoltage element


Directional Elements Wattmetric Zero-sequence Directional
Following are some of the key applications
Applications include ground fault protection
where voltage elements can be used:
in solidly grounded transmission networks,
• Source transfer schemes grounded/ungrounded/resistor-grounded/
• Load shedding schemes resonant-grounded distribution networks. The
wattmetric zero-sequence directional element
• Back up capacitor bank protection and
responds to power derived from zero-sequence
control
voltage and current in a direction specified by
• Backup motor protection to prevent the element characteristic angle. The angle
Flexible load encroachment characteristic in automatic restart can be set within all four quadrants and the
F650 can be set by adjusting the load angle and power can be active or reactive. Therefore, the
the reach.

Functional Block Diagram

1
52

79
1 CLOSE TRIP 27X
3
Monitoring
3 59X
BROKEN 3
50BF 49 50PH 50PL 46 48 32FP 32 32N CONDUCTOR 51PH/V 51PL/V 67P
R R 50N 51N 67N
1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
25
1

1 2 2
50G 51G 67G
3 3 3
1
50SG 51SG 50IG 67SG METERING
3 3 3 3
3V_0
3

47 27 59 VTFF 81U 81O 81R


3 3 3 1 3 3 3
59NH
3

59NL
F650 Feeder Protection Relay and Bay Controller 3

EN F650 BLOCK F.CDR

ANSI Device Numbers & Functions


25 Synchrocheck 50N Neutral Instantaneous Overcurrent 67P Phase Directional Overcurrent
27/27X Bus/Line Undervoltage 50G Ground Instantaneous Overcurrent 67N Neutral Directional Overcurrent
32 Sensitive Directional Power 50SG Sensitive Ground Instantaneous Overcurrent 67G Ground Directional Overcurrent
32FP Forward Power 50IG Isolated Ground Instantaneous Overcurrent 67SG Sensitive Ground Directional Overcurrent
32N Wattmetric zero-sequence directional 51N Neutral Time Overcurrent 79 Autorecloser
46 Negative Sequence Time Overcurrent 51G Ground Time Overcurrent 81 U/O Under/Over Frequency Broken Conductor
47 Negative Sequence Voltage 51SG Sensitive Ground Time Overcurrent Detection
48 Blocked Rotor 51PH/V Voltage Restraint Phase Time Overcurrent 81R Frequency Rate of Change
49 Thermal Image - overload protection 51PL/V VTFF VT Fuse Failure Detection
50 BF Breaker Failure 59/59X Bus/Line Overvoltage Load Encroachment
50PH/PL Phase Instantaneous Overcurrent (High/Low) 59NH/NL Neutral Overvoltage - High/Low

2 GEDigitalEnergy.com
F650 Feeder Protection & Bay Controller

element may be used to sense either forward Autoreclosurer Advanced Automation


or reverse ground faults in either inductive,
This function is applicable to three-pole tripping The F650 incorporates advanced automation
capacitive or resistive networks. The inverse
schemes and single breaker applications. Four features including powerful programmable
time characteristic allows time coordination of
reclosing “shots“ are possible prior to locking logic, communication, and SCADA capabilities
elements across the network.
out, each with an independent time setting. that far surpass what is found in the average
Auto­reclosure outputs can be used to modify feeder relay. The F650 integrates seamlessly
Breaker Failure and Control
circuit protection settings between shots. with other Multilin relays for complete system
The breaker failure function determines if a
protection.
trip command sent to a breaker has not been Synchronism Check
executed within a selectable time delay. In the F650 Logic Configuration
One synchronism check element is available.
event of a breaker failure, the unit will issue an
The algorithm allows breaker close time F650 Logic Configuration is the powerful
additional signal to trip the breakers
compensation to optimize close conditions. programming logic engine that provides the
connected to the same busbar, potential
The element monitors maximum difference in ability of creating customized protection
sources of fault current.
voltage magnitudes and control schemes thereby minimizing the
The F650 incorporates 3 levels of current and need, and the associated costs, of auxiliary
( V), phase angles ( ), and frequencies
time, together with a trip without current components and wiring. Using F650 Logic
unit, and an internal arc detection unit. The ( f) as well as the dead source condition. Configuration, the F650 can be programmed
breaker failure unit has three levels: “Retrip” to provide required tripping logic along with
or “Supervision” used to generate a second Multiple Settings Groups
custom scheme logic for auto transfer schemes
trip signal to the corresponding breaker on Three separate groups of protection (Main-Tie-Main), load shedding based on
which the initial opening has been executed, settings may be stored in the F650 frequency, voltage and communication, loop
“High Level”, and “Low Level” used to executing non-volatile memory. The user can edit the restoration schemes, other remedial action
complex protection schemes. The function can active settings internally and externally via schemes and dynamic setting group changes.
be initiated/blocked via digital inputs as well as contact inputs and communications.
communications. Inputs and Outputs
Broken Conductor
The relay also provides for control of one or two A choice of 16 to 64 inputs and 0 to 16 outputs
breakers from faceplate pushbuttons, remote F650 incorporates a broken or fallen conductor are available. Digital inputs may be user defined
communications or contact inputs. A breaker detection function. The relay uses the ratio with a separate debounce and chatter time.
pole discrepancy is included in the breaker between the negative sequence current, I2, and Programmable “quasi“ analog input levels allow
control scheme. Breaker position is indicated by the positive sequence current I1. In normal and the use of different voltage levels in the same
LEDs on the faceplate. balanced load situations, this ratio is zero, while model via setting the requested thresholds.
in severe load fault conditions, an unbalance is EnerVista™ software allows easy configuration
Load Encroachment produced and this ratio increases. of all the interlocking and switching sequences.
A graphic HMI interface provides access to
Feeders may experience very heavy load In order to avoid trips or pickup with very weak
monitoring, metering and alarm panel screens.
increases due to various contingency situations. loads, there is a current level threshold (I2/I1) to
The Load Encroachment function in F650 inhibit the operation of the element when the
Virtual Inputs/Outputs
provides the capability to manage such load three phase currents are below a fixed level.
growth in feeders. The load encroachment Traditionally, protective relay logic has been
element can be set for the feeder’s expected Locked Rotor relatively limited. Use virtual inputs and outputs
maximum load, reducing the likelihood of false in conjunction with the programmable logic
F650 incorporates a locked rotor element .
tripping for load conditions while maintaining capabilities of the F650 for unusual applications
Protection element 48 produces a trip when
dependability to trip for legitimate faults. involving interlocks, blocking, or supervisory
current (primary values) exceeds the set value.
functions, to minimize the requirement for
The load encroachment supervision in F650 is This current setting value is the product of the
auxiliary components and wiring while making
based on positive-sequence voltage and current set Full Load Current by the pickup setting.
more complex schemes possible.
and applies a characteristic as shown in the
figure above. It allows the user to set the phase The virtual inputs and outputs are digital signals
overcurrent elements below peak load current associated with the F650 internal logic. Virtual
to see end-offline phase faults in heavily loaded inputs include signals generated remotely
feeder applications. via communications. The virtual outputs are
outputs of programmable logic equations used
to customize the device. Virtual outputs can also
serve as inputs to programmable logic equations.

GEDigitalEnergy.com 3
F650 Feeder Protection & Bay Controller

CAN BUS Remote I/O (CIO) controllers. The remote outputs interface Basic Metering
seamlessly to the remote inputs of other F650
The F650 can be ordered with up to two Metered values include:
devices via the IEC 61850 GSSE messaging. User
additional communication cards on the rear.
secure peer-to-peer communications to develop • Current: Ia, Ib, Ic, In, Ig, Isg
Besides two identical ports, COM1 and COM2,
complex schemes in distributed logic and I/Os. • Phase-to-phase and phase-to-ground
the cards may incorporate a port for CAN BUS
voltages for bus and line: Van, Vbn, Vcn, Vbb, Vab,
communications used to connect the Remote
Vbc, Vca
CAN BUS I/O module (CIO Module). Use the Monitoring and Metering
CIO Module to double the number of I/Os of • Active power (per-phase and total): Wa, Wb,
The F650 provides advanced monitoring and
the F650, when the maximum number of I/Os Wc, W
metering that includes:
available inside the relay (up to 64 inputs and • Reactive power (per-phase and total):
16 outputs) is not sufficient to meet the needs of VT Fuse Failure VAra, VArb, VArc, VAr
specific applications. • Total active and reactive energy: MWh, Mvarh
Use the VT Fuse Failure feature to issue an alarm
In addition to increasing the number of I/Os, and/or to block voltage driven protection functions • Power factor (per-phase and total)
the CIO Module allows the F650 to monitor that can operate incorrectly due to an abrupt • Frequency
signals located at a remote location with only partial or total voltage loss. This loss is caused
a connection between both devices, resulting in • Demand
by the voltage transformers secondary circuit
significant savings in installation costs. protection fuse failure. Different methods are used • Ia, Ib, Ic, Ig, Isg, Va, Vb, Vc and Vx signals are
to detect the different types of VT fuse failure. available locally and remotely and can be
Transducer Inputs stored in the oscillography record or data
dcmA inputs are available to monitor system Trip Circuit Monitoring logger.
parameters such as temperature, vibration, F650 can be used to monitor the integrity of
pressure, wind speed, and flow. both the breaker trip and closing coils and
circuits. The supervision inputs monitor both the
Remote I/O battery voltage level, while the outputs monitor
The remote I/O feature provides a means of the continuity of the trip and/or closing circuits,
sharing digital point state information between by applying a small current through the circuits.
F650s or other IEC 61850 compliant IEDs or

Double the Number of I/O’s of F650

Up to 32 inputs + 16 outputs embedded

F650
MV Switchgear

Up to 64 inputs + 16 outputs

CIO
Circuit Breaker

CAN BUS to connect to a remote CAN BUS I/O module (CIO module)

4 GEDigitalEnergy.com
F650 Feeder Protection & Bay Controller

Example of Redundant HSR and PRP Architecture • IEC 61850 (and support for edition 2)
• DNP 3.0
• Modbus RTU
Data AMDS
SCADA EMS DMS
Local HMI /
Single Line PowerOn PowerOn PowerOn
Historian
Proficy PowerOn • Modbus TCP/IP
Reliance Reliance Fusion Historian Advantage
• IEC 60870-5-104
• PRP & HSR (IEC 62439-3)
• RSTP (IEEE 802.1D)
• IEEE 1588 (PTP) for time synchronization
The F650 includes up to three communication
ports that operate simultaneously. Redundant
D400 D400 ports are also available for special applications.
F650 features an RS232 front port (COM2) and a
choice of rear RS485, plastic/glass fiber optics
(COM1 and COM2). Additionally, this module may
incorporate a port for CAN bus communications,
used for the connection to the remote CAN
BUS I/O module. F650 COM3 features 10/100
BaseTX and 100 Base FX single or redundant
Ethernet ports.

Security
Independent passwords for protection and
control allow restricting access via keypad and
display, or EnerVista software.
8 Series F650 350 UR F650 350
Multi-Language
PRP Network HSR Ring
The F650 supports multiple languages.
French, Chinese, Russian language options are
Redundancy protocols (PRP and HSR) can be used for various networking architectures including available on the local display, front panel, and
combined PRP/HSR topologies.
EnerVista setup software, as well as the product
instruction manual. Easily switch between
English and an additional user selectable
Event Recording and Oscillography The F650 provides optional Parallel Redundancy
language on the local display.
Protocol (PRP), High Availability Seamless Ring
The F650 is capable of storing 479 time-tagged
(HSR) (IEC 62439-3) and also Rapid Spanning Tree Interoperability With Embedded
events (1 ms tagging), to help with trouble­
Protocol (RSTP) (IEEE 802.1D) to increase network IEC 61850 Protocol
shooting. The trigger point, the channels, and
availability and reliability for critical applications.
sampling rate of the oscillography files are user IEC 61850 is the international standard for
programmable features. Up to five seconds at The basic concept of both protocols, PRP and HSR, information exchange and interoperability
maximum sample rate can be stored. is to send identical frames over different paths between intelligent devices within a substation.
and discard one of the copies in reception, at Use the F650 with IEC 61850 to lower the costs
Breaker Arcing Current (I2t) best. If an error occurs or one of the paths goes and simplify the engineering, commissioning,
The relay estimates the total interrupted down, the frame travelling through that path will operating, and maintenance associated with
current as an accumulation of the RMS current not reach its destination, but its copy remains substation protection and control applications.
measured during the time period taken to open intact and will reach the desired destination. This
The F650 provides integration with 61850
the breaker after a trip. It calculates the per- technology ensures high reliability and availability
standard edition 2. IEC 61850 allows for the
phase wear on the breaker contacts to establish of communication networks by providing
seamless connection of IEDs from multiple
a threshold. When the breaker maintenance redundancy and zero reconfiguration time in the
vendors. In addition to device interoperability,
threshold is exceeded the relay can be set to event of a failure. Failsafe communications systems
these protocols are designed to control the
trigger an alarm. are crucial for industries and utilities with critical
substation via a LAN instead of through discrete
applications where no recovery time is tolerated.
wiring to an RTU. Peer-to-peer communication
Communications
The F650 supports popular industry leading over Ethernet enables distributed control with
The F650 incorporates industry-leading standard protocols enabling easy, direct several IEDs and eliminates the need for an RTU
communication technologies making it one of integration into electrical SCADA and HMI systems. to remote SCADA master. High-speed message
the easiest and flexible feeder protection relay The protocols supported by the F650 include: transfer eliminates the need for large and costly
for use and integration into new and existing hard-wired interconnection.
infrastructures.

GEDigitalEnergy.com 5
F650 Feeder Protection & Bay Controller

EnerVista Software devices in real-time by communicating using Viewpoint Monitoring


serial, Ethernet, or modem connections, or offline
The EnerVista™ Suite is an industry-leading Viewpoint Monitoring is a simple-to-use and full-
by creating setting files to be sent to devices at
set of software programs that simplifies every featured monitoring and data recording software
a later time.
aspect of using the F65 relay. The EnerVista package for small systems. Viewpoint Monitoring
suite provides all the tools to monitor the status Included in Launchpad is a document archiving provides a complete HMI package with the
of your the protected asset, maintain the relay, and management system that ensures critical following functionality:
and integrate information measured by the documentation is up-to-date and available when
• Plug-&-Play Device Monitoring
F650 into DCS or SCADA monitoring systems. needed. Documents made available include:
Convenient COMTRADE and Sequence of Events • System Single-Line Monitoring & Control
• Manuals
viewers are an integral part of the 650 Setup • Annunciator Alarm Screens
• Application Notes
software included with every F650 relay, to carry • Trending Reports
out postmortem event analysis to ensure proper • Guideform Specifications
• Automatic Event Retrieval
protection system operation. • Brochures
• Automatic Waveform Retrieval
• Wiring Diagrams
EnerVista Launchpad
• FAQ’s
EnerVista Launchpad is a powerful software
package that provides users with all of the • Service Bulletins
setup and support tools needed for configuring
and maintaining Multilin products. The setup
software within Launchpad allows configuring

6 GEDigitalEnergy.com
F650 Feeder Protection & Bay Controller

User Interface

Display
Graphic 16x40 or text 4x20 LCD display
Fluorescent backlight to improve visibility

LEDs
Multicolor programmable LEDs with label panel
Local/Remote/Off pushbutton with LEDs

Keypad & Shuttle


Local/Remote/Off pushbutton withLEDs
Key control for easy navigation
Ergonomic programmable keys

Front Port
Electrically isolated front USB communication port

Dimensions
The F650 uses a “shuttle“ control for ease of use. A choice of text or graphic display, and up to five configurable keys are available for frequently performed
control functions. Up to 15 programmable LEDs are available. The F650 can incorporate (option “N” for the second position of the ordering code) a Graphical
display with IEC Symbols.

SIDE VIEW FRONT VIEW CUTOUT

210 ( 8,27 )

28 172,8 237 186 ( 7,32 )

19

4x 7 ( ,27 )
263 ( 10,36 )

190,5 ( 7,5 )
260,7

266,3

NOTE: All dimensions are shown in mm (inches)

GEDigitalEnergy.com 7
F650 Feeder Protection & Bay Controller

Dimensions

8 GEDigitalEnergy.com
F650 Feeder Protection & Bay Controller

Technical Specifications
PROTECTION PROTECTION Minimum voltage threshold:
PHASE/NEUTRAL AND GROUND TIMED OVERCURRENT ISOLATED GROUND INSTANTANEOUS OVERCURRENT (50IG) 3 to 300 in steps of 1V
(51PH/51PL/51N/51G) Logic: Any/two/all phases logic selectable by
Current: Fundamental Phasor (w/o harmonics) or RMS Current Input: Fundamental Phasor (without harmonics) setting
Rated current : For connection to 1 or 5 A CTs. Voltage Input: Fundamental Phasor (without harmonics) Supervised by breaker:
Pickup level : 0.05 to 160.00 A in steps of 0.01 A Current Pickup level: 0.005 to 0.400 A in steps of 0.001 A Selectable by setting
Reset Dropout level: 97% to 98% of the pickup level Voltage Pickup level: 2 to 70 V in steps of 1 V Timing accuracy: ±3.5% of operation time or 50 ms.
Accuracy: ±0.5% of the reading ±10 mA from 0.05 Dropout level : 97 to 98% of the pickup level (whichever is greater)
to10A Pickup level: for voltage 2 to 70 V in steps of 1 V
±1.5% of the reading for values higher Dropout Level: 97-98% of the pickup level PROTECTION
than 10A Level Accuracy: ±1.5% of the reading ± 1 mA from 0.005
OPERATION CURVES to 16 A AUXILIARY OVERVOLTAGE (59X)
IEEE extremely/very/moderately inverse Trip delay: 0.00 to 900.00 s. in steps of 0.01 s. Pickup level: 3 to 300 in steps of 1 V
IEC Curve A/B/C/Long-Time Time to instantaneous 0.00 to 900.00 s. in steps of 0.01 s. Reset dropout level: 97% to 98% of the pickup level
Inverse/ Short-Time Inverse Operate time: <50 ms at 3 x Pickup at 50 Hz, typically Accuracy: ±1% of the reading, from 10 to 208 V
ANSI extremely/very/normally/moderately Timing accuracy: at 0 ms time delay (no intentional Timing accuracy: ±3.5% of operation time or 50 ms
inverseI2t delay): 50ms at non-zero time delay: (whichever is greater)
IAC extremely / very / moderately inverse ±3% of operate time or 50 ms (which AUXILIARY UNDERVOLTAGE (27X)
Definite time ever is greater) Pickup level: 3 to 300 in steps of 1 V
Rectifier curve Snapshot Events: Selectable by setting Reset dropout level: 97% to 98% of the pickup level
User curve FlexCurve™ A/B/C/D PHASE DIRECTIONAL UNITS (67P) Accuracy: ±1% of the reading, from 10 to 208 V
Reset time type: Instantaneous or time delayed according Operation curves:
to IEEE Directionality: Forward and reverse selectable by setting Fixed time or inverse curve
Snapshot events: Selectable by setting Polarizing: Quadrature Voltage: Timing accuracy: ±3.5% of operation time or 50 ms
Timer accuracy: From 1.03 times the pickup, ±3% of ABC seq: Phase A (VBC), Phase B (VCA), (whichever is greater)
operation time or 50 ms. (whichever is Phase C (VAB)
greater) ACB seq: Phase A (VCB), Phase B (VAC), FREQUENCY (81U ,81O)
Voltage restraint: Selectable by setting Phase C (VBA) Pickup level: 20 to 65 Hz in steps of 0.01 Hz
Polarizing voltage threshold: 0 to 300 Vac in steps of 1 V Reset dropout level: 30 mHz higher/lower than the
NEGATIVE SEQUENCE (46) Current Sensitivity Threshold: 50 mA pickup level
Current: Fundamental phasor (without harmonics) Characteristic angle: -90º to +90º in steps of 1º Accuracy: 0.05 Hz
Pickup level: 0.05 to 160.00 A in steps of 0.01 A Block Logic: Permission or Block selectable by setting Operation time trip delay: 0.00 to 900.00 s. in steps
Reset level: 98% of the pickup level Angle accuracy: ±2º for I>0.1 A and V>5 Vac of 0.01 s
Accuracy: ±0.5% of the reading ±10 mA from 0.05 to Operate time: <30ms, typically Reset time delay: 0.00 to 900.00 s. in steps of 0.01 s
10A Timer accuracy: ±3.5% of operation time or 100 ms.
NEUTRAL AND GROUND DIRECTIONAL UNIT (67N/67G)
±1.5% of the reading for higher values (whichever is greater)
Operation curves: Directionality: Forward and reverse selectable by setting
Polarizing: Voltage, current, dual NEUTRAL OVERVOLTAGE (59NH/59NL)
IEEE extremely/very/moderately inverse
IEC Curve A/B/C/Long-Time Inverse/Short- Polarizing Voltage: VN (measured or calculated, selected Voltage: Fundamental phasor of the neutral
Time Inverse by setting) voltage
Ansi extremely/very/normally/moderately Polarizing Current: Isg (measured from 5th current Pickup level: 3 to 300 in steps of 1 V
inverse transformer) Reset level: 97% of the pickup level
I2t Operating Current: Ig (measured from 4th current Accuracy: ±1% of the reading, from 10 to 208 V
IAC extremely / very / moderately inverse transformer) Trip delay: 0.00 to 900.00 s. in steps of 0.01 s
Definite time Polarizing Voltage threshold: 0 to 300 Vac in steps of 1 V Reset time: 0.00 to 900.00 s. in steps of 0.01 s
Rectifier curve Polarizing Current threshold: 0.005 A Timing accuracy: ±3.5% of operation time or 50 ms.
User curve FlexCurve™ A/B/C/D Characteristic angle: -90º to +90º in steps of 1º (whichever is greater)
Reset time type: Instantaneous or time delayed according
to IEEE Block Logic: Permission or Block selectable by setting
NEGATIVE SEQUENCE OVERVOLTAGE (47)
Timing: Operate at > 1.03 times the pickup Angle accuracy: ±2º for I>0.1 A and V>5 Vac
Pickup level: 3 to 300 in steps of 1 V
±3% of operate time or 50 ms. (whichever Operate time: <30ms, typically
Reset dropout level: 97%to 98%of the pickup level
is greater) SENSITIVE GROUND DIRECTIONAL UNIT (67SG) Accuracy: ±1% of the reading, from 10 to 208 V
SENSITIVE GROUND TIMED OVERCURRENT (51SG) Polarization By: Voltage Trip delay: 0.00 to 900.00 s. in steps of 0.01 s
Current: Fundamental Phasor (w/o harmonics)or RMS Polarization Voltage: 0 to 300 Vac in steps of 1V Reset delay: 0.00 to 900.00 s. in steps of 0.01 s
Rated current : For connection to 1 or 5 A CTs Directionality: Forward and reverse selectable Timing accuracy: ±3.5% of operation time or 50 ms.
Pickup level: 0.005 to 16.00 A in steps of 0.001 A by setting (whichever is greater)
Reset dropout level: 97% to 98% of the pickup level Characteristic angle:-90º to +90º in steps of 1º FORWARD POWER (32FP)
Accuracy: ±1.5% of the reading ± 1 mA Angle accuracy: ±3º from 0.1 A and 5 Vac Current, Voltage: Fundamental phasor (primary values)
Response time: <30ms typically Pickup level (two steps)
from 0.005 to 16 A
THERMAL MODEL (49) 0-10000 MW (primary values) in steps
Operation curves:
IEEE extremely / very / moderately inverse Current: Fundamental phasor (without harmonics) of 0.01 MW
IEC A/B/C/long-time inverse/short time Rated current: Valid for connection to 1 or 5 A CTs Reset dropout level: 97%to 98% of the pickup level
inverse curve Pickup level: 0.05 to 160.00 A in steps of 0.01 A Accuracy for primary magnitudes
IAC extremely / very / normally / Dropout level: 97% to 98% of the pickup ±3% in the complete range.
moderately inverse Accuracy: ±0.5% of the reading ±10 mA from 0.05 to 10 A Reset type: Instantaneous
ANSI extremely / very / normally / ±1.5% of the reading for higher values Trip delay (two steps):
moderately inverse I2t Timer accuracy: ±3.5% of the operating time or 50 ms. 0.00 to 900.00 s in steps of 0.01 s
Definite time Timing accuracy: ±3.5% of operation time or 50 ms.
Rectifier curve (whichever is greater)
Heating constant: Between 3 and 600 minutes (whichever is greater)
FlexCurve™ A/B/C/D user curve
Reset time: Instantaneous or time delayed according Cooling constant :1 to 6 times the heating constant SENSITIVE DIRECTIONAL POWER (32)
to IEEE Current, Voltage: Fundamental phasor (primary values)
BREAKER FAILURE (50BF) Pickup level (two steps):
Timing accuracy: Operate at > 1.03 times the pickup ±3% Current: Fundamental phasor (without harmonics)
of operate time or 50 ms. (whichever is -10000.00 to 10000.00 MW (primary
greater) Rated current: Valid for connection to 1 or 5 A CTs values) in steps of 0.01
PHASE/NEUTRAL AND GROUND INSTANTANEOUS Pickup level for supervision: Characteristic angle (two steps):
0.05 to 160.00 A in steps of 0.01 A 0.00 to 359.99 in steps of 0.01º
OVERCURRENT (50PH/50PL/50N/50G) Pickup level high level: Accuracy for primary magnitudes:
Current: Fundamental Phasor (w/o harmonics) or RMS 0.05 to 160.00 A in steps of 0.01 A ±3% of complete range
Rated current : For connection to 1 or 5 A CTs. Pickup level low level: Trip delay (two steps):
Pickup level: 0.05 to 160.0 A in steps of 0.01 0.05 to 160.00 A in steps of 0.01 A 0.00 to 900.00s in steps of 0.01s
Reset dropuout level: 97% to 98% of the pickup level Pickup level internal arcing: Timing accuracy: ±3.5% of operation time or 50ms
0.05 to 160.00 A in steps of 0.01 A (whichever is greater)
Accuracy: ±0.5% of the reading ±10mA from 0.05 Reset dropout level: 97% to 98% of pickup level
to 10A Accuracy: ±0.5% of the reading ±10 mA from 0.05 to 10A BROKEN CONDUCTOR (I2/I1)
±1.5% of the reading for higher values ±1.5% of the reading for higher values Pickup level: 20.0-100.0% (I2/I1 ratio) in steps of 0.1%
Overreach < 2% Timer accuracy : ±3.5% of the operating time or 50 ms Reset dropout level: 97%to 98%of the pickup level
Trip Delay: 0.00 to 900.00 s. in steps of 0.01 s. (whichever is greater) Trip delay: 0.00 to 900.00 s in steps of 0.01 s
Operate time: <30 ms at 3 x Pickup at 50 Hz, typically Timing accuracy: ±3.5% of operation time or 30 ms.
PHASE OVERVOLTAGE (59P) (whichever is greater)
Reset time delay: 0.00 to 900.00 s. in steps of 0.01 s. Voltage: Fundamental phasor (without harmonics Minimum phase current threshold: I2/I1 current inhibi-
Timing accuracy: at 0ms time delay (no intentional delay): of phase-to phase voltages tion level: 0.000-1.000 in steps of 0.001
50 ms Pickup level: 3 to 300 in steps of 1 V
at non-zero time delay: ± 3% of operate Reset dropout level: 97% to 98% of the pickup level FREQUENCY RATE OF CHANGE
time or 50ms (whichever is greater) Accuracy: ±1% of the reading, from 10 to 208 V df/dt trend: Increasing, decreasing, bi-directional
Operate time : 0.00 to 900.00 s. in steps of 0.01s df/dt pickup level: 0.10 to 10.00 Hz/s in steps of 0.01
SENSITIVE GROUND INSTANTANEOUS Reset time: 0.00 to 900.00 s. in steps of 0.01s df/dt level accuracy: 80 mHz/s or 3.5%, whichever is
OVERCURRENT (50SG) Timer accuracy: ±3.5% of operation time or 50 ms greater
(whichever is greater) Overvoltage supervision: 0.00 to 110.00 % in steps
Current: Fundamental Phasor (w/o harmonics) or RMS of 0.0
Rated current: For connection to 1 or 5 A CTs. PHASE UNDERVOLTAGE (27P) 95% settling time for df/dt: < 24 cycles
Pickup level: 0.005 to 16.0 A in steps of 0.001 A. Voltage: Fundamental phasor of phase-to-ground
Reset dropout level: 97% to 98% of the pickup level Operate time:
or phase-to phase voltages (selectable by at 2 × pickup : 12 cycles
Accuracy: ±1.5% of the reading 1 mA from 0.005 to 16A setting)
Overreach: < 2% at 3 × pickup : 8 cycles
Pickup level: 3 to 300 in steps of 1 V at 5 × pickup : 6 cycles
Trip Delay: 0.00 to 900.00 s. in steps of 0.01 s.
Operate Time: < 30 ms at 3 x Pickup at 50 Hz Reset dropout level: 102% to 103% of the pickup level Frequency Rate min.: 20.00 to 80.00 Hz in steps of 0.01
Reset time: 0.00 to 900.00 s. in steps of 0.01 s. Accuracy: ±1% of the reading, from 10V to 208 V Frequency Rate max.: 20.00 to 80.00 Hz in steps of 0.01
Timing accuracy: at 0ms time delay (no intentional delay): Operation curves: Frequency Rate delay: 0.00 to 60.00 s in steps of 0.01
50 ms at non-zero time delay: ± 3% of Fixed time or inverse curve Snapshot Events: Selectable by setting
operate time or 50ms (whichever is greater) Reset type: Instantaneous

GEDigitalEnergy.com 9
F650 Feeder Protection & Bay Controller

Technical Specifications
PROTECTION SWITCHGEAR Metering Measurements: Each channel shows the
LOAD ENCROACHMENT Switchgear number: 1 to16 present and maximum measured
value, with date and time for the
Responds to: Positive-sequence quantities Switchgear: 1 to16 (configurable) maximum recorded value.
Minimum voltage: 0.00 to 300.00 V in steps of 0.01 MAXIMUM NUMBER OF STARTS: Samples: 5, 10, 15, 20, 30, 60 minutes.
Reach (sec. Ω ): 0.02 to 250.00 Ω in steps of 0.01 (depending on ordering code) Accuracy: ±1%

Impedance accuracy: ±3% Metering algorithm: Fundamental DATA LOGGER
Angle: 5 to 50° in steps of 1 Tripping Time ±250 ms or 5% whichever is Channels: 1 to 16
Angle accuracy: ±3° Accuracy: greater Parameters: Any of the analog Metering actual values
Pickup delay: 0 to 65.535 s in steps of 0.001 Samples: 1 second, 1, 5, 10, 15, 20, 30, 60
Full load Amps: 0.5 to 10.0 A in steps of 0.1 minutes.
Reset delay: 0 to 65.535 s in steps of 0.001 Breaker Supervision: Selectable by setting
Time accuracy: ±3.5% or ±60 ms, whichever is greater Capacity: Fixed, (32768 measures)
Operate time: < 60 ms at 50 Hz Min. Stop time: 0.0 to 900.0 s in steps of 0.1
Snapshot Events: Selectable by setting Number of starts: 0 to 10 in steps of 1 METERING
Time to restart: 0 to 100 minutes in steps of 1 CURRENT
CONTROL Reset Counter: Selectable by setting Accuracy: ±0.5% of the reading ± 10 mA
AUTORECLOSE (79) Snapshot Events: Selectable by Setting from 0.1 to 10 A (for phases and
Operate time: <45 ms at 50Hz, typically ground)
Schemes: Three-phase pole tripping schemes ±1.5% of the reading ± 1 mA from
DIGITAL COUNTERS: (depending on ordering code)
No. of reclosing shots: Up to 4 reclose attempts 0.005 to 5 A (for sensitive ground)
before lockout Number of Counters: 8
±1.5% of the reading for higher
Counting: Preset, Compare values
Dead time: Independent dead time setting before
each shot adjustable between 0 and 900 s Programmability: reset, up/down, set to pre-set,
VOLTAGE
in steps of 0.01 s freeze/reset, freeze/count Accuracy: ±1% reading, from 10 to 208 V
METERING
Reclaim time: 0.00 to 900.00 s in steps of 0.01 s MONITORING POWER
Condition permission: Selectable by setting TRIP/CLOSE COIL MONITORS Active: ±2,5% of the reading from power
Detect open trip and close circuits factor ±0.8 to 1
Hold time: 0.00 to 900.00 s in steps of 0.01 s Reactive: ±2,5% of the reading from power
Reset time: 0.00 to 900.00 s in steps of 0.01 s OSCILLOGRAPHY factor ±0.2 to 0
Snapshot Events: Selectable by setting Records: Up to 20 oscillography records. Apparent: ±2,5% of the reading
Possibility to modify protection settings after each shot Samples: Programmable to 4, 8, 16, 32 or 64
samples per cycle ENERGY
Trigger position: Watts- hour (positive and negative)
SYNCHRONISM CHECK (25) 5% to 95% of total length Accuracy: 2,5%
Dead/live levels for line and bus: Trigger: Programmable via programmable logic Range: ±0 to 2147 MWh
0.00 to 300.00 in steps of 0.01 V Data: 5 current channels and 4 voltage Parameters: three-phase
channels Updating Time: 100 ms
Maximum voltage difference: Var-hour (positive and negative)
2.00 to 300.00 V in steps of 0.01 V Up to 16 digital channels selectable
from the available internal states Accuracy: 2,5%
Maximum angle difference: programmable through PLC Range: ±0 to 2147 MVArh
2.0º to 80.0º in steps of 0.1º Storage: Permanent in non volatile memory Updating Time: 100 ms
Maximum frequency slip: (flash) without battery In non-volatile POWER FACTOR
10 to 5000 mHz in steps of 10 mHz memory (flash) without battery Accuracy: 0.02
Synchronism time: 0.01 to 600.00 s in steps of 0.01 s Format: International Standard COMTRADE FREQUENCY
ASCII - IEEE C37.111-1999. Accuracy: ±50 mHz
Angle accuracy: 3º
Accuracy angle: 2º
Dead Source function: None FAULT LOCATOR
(DL-DB) Dead Line - Dead Bus INPUTS
Method: Single-ended
(LL-DB) Live Line-Dead Bus Positive sequence module: CURRENT INPUTS
(DL-LB) Dead Line – Live Bus 0.01 to 250.00 Ohm in steps of 0.01 Rated current: Appropriate for 1 or 5 A
Ohms LoadRelay Burden: < 0.04 Ohm
Snapshot Events: Selectable by setting Overload: 20 A permanent
Positive sequence angle:
25 to 90º in steps of 1º 500 A during 1 second
FUSE FAILURE Zero sequence module: Current Withstand:
Activation by Algorithm based onpositive sequence of volt- 0.01 to 750.00 Ohms in steps of 0.01 Continuous at 20 A
age and current Ohm 1 second at 500 A for phases
Zero sequence angle: and ground
Activation by V2/V1 ratio 1 second at 50 A for sensitive
25 to 90º in steps of 1º
Line length: 0.0 to 2000.0 in steps of 0.1 (miles or ground
BREAKER FAILURE (50BF) km) VOLTAGE INPUTS
Current: Fundamental phasor (without harmonics) Display fault on HMI: VAC inputs do not need varistors, as the impulse test is
Rated current: Valid for connection to 1 or 5 A CTs Possibility to show the fault report on applied to 100% of the transformers
the display Metering range: From 2 to 275 Vac
Pickup level for supervision: Accuracy: 5% (typical) LoadRelay Burden: 0.05 VA at 120 Vac (50 or 60 Hz)
0.05 to 160.00 A in steps of 0.01 A Voltage withstand: 260 Vac permanent
Pickup level for high level: SNAPSHOT EVENTS Continuous at 275 V to neutral
0.05 to 160.00 A in steps of 0.01 A Capacity: 479 scrolling events 420 Vac during 1 min/hr at 420 to
Labeling time tag: 1 ms using an internal clock of 100 µs neutral
Pickup level for low level: Accuracy: 1 ms (using the IRIG-B synchronization
0.05 to 160.00 A in steps of 0.01 A input) DIGITAL INPUTS
Trigger: By pickup or dropout or operate of any Voltage Threshold: Programmable from 20 up to
Pickup level for internal arcing: 230Vdc in steps of 1 V
element
0.05 to 160.00 A in steps of 0.01 A By change of state in a Digital Impedance: > 100 kOhm
Reset level: 97% to 98% of pickup level input/output change of state Load for voltage
By virtual inputs and control events supervision inputs: 2 mA + V/100 kOhm
Accuracy: ±0.5% of the reading ± 10 mA from 0.05 Maximum error: ±10% setting or ± 5 V
to 10 A Storage: Permanent in non volatile memory
(flash) without battery Acknowledgement time: < 1 ms
±1.5% of the reading for higher values Debounce time: 1 to 50 ms in steps of 1 ms
Reset type: Instantaneous CONTROL EVENTS
Timing accuracy: ±3.5% of the operating time or 30 ms. Capacity: 128 events programmable through PLC REMOTE INPUTS
(whichever is greater) Labeling time tag: 1 ms using an internal clock of 100 µs No of input points: 32, configured from 64 incoming
Accuracy: 1 ms (using the IRIG-B synchronization bit pairs
input) No of remote devices: 16
BREAKER MAINTENANCE Trigger: By any digital signal programmable Default states on loss of comms: On, Off, Latest/on,
through PLC Latest/off
Kl2t BKR Ph A, B, C Cnt:
Alarm: Possibility to display the event as an
0.00 to 9999.99 in steps of 0.01 (KA)2s alarm on the alarms panel. Information ANALOG INPUTS (dcmA)
BKR Openings Cnt: 0 to 9999 in steps of 1 available always through Current inputs: 0 to -1; 0 to +1; -1 to +1; 0 to 5; 0
BKR Closings Cnt: 0 to 9999 in steps of 1 Communications for all models and to 10; 0 to 20, 4 to 20
BREAKER SETTINGS also in HMI for models with graphical Conversion range: -1 to 20 dcmA
display (M in ordering code). Accuracy: +/-0.2% of full scale
Switchgear number: 1 to16 Storage: Permanent in non volatile memory Type: Passive
Maximum KI2t: 0.00 to 9999.99 in steps of 0.01 (KA)2s (flash) without battery
KI2t integ. Time: 0.03 : 0.25 s in steps of 0.01s IRIG-B TIME SYNCHRONIZATION INPUT
Maximum openings: 0 to 9999 in steps of 1 DEMAND Type: Demodulated input (no carrier)
Maximum Openings in an hour: 1 to 60 in steps of 1 Channels: 9 Formats: B000(*) B001, B002 and B003(*)
Parameters: Ia(kA RMS), Ib(kA RMS), Ic(kA RMS), Level: TTL
Ig(kA RMS), Isg(kA RMS), I2 (KA), Load: 1.5 mA
P(MW), Q (MVAr) and S (MVA) (*) Signal combinations recognized in accordance with IRIG
Current and Power Method: Standard 200-95
Thermal Exponential, block
interval, Rolling demand REAL TIME CLOCK
Accuracy: Typical 20 ppm
Backup energy: More than 1 week

10 GEDigitalEnergy.com
F650 Feeder Protection & Bay Controller

Technical Specifications
POWER SUPPLY TYPE TESTS MECHANICAL CHARACTERISTICS
Options: REFERENCE Metallic package in 1/2 19" rack 6 units high
CATEGORY TEST TEST LEVEL
F range LO, LOR: DC: 24 to 48 V STANDARD Protection class IP52 (according to IEC 529)
H range HI, HIR: DC: 110 to 250 V Dielectric IEC60255-27 2 KV / 2.3 KV
AC: 120 to 230 V voltage CONTROL
Power: 25 VA nominal, maximum 45 VA withstand
Voltage loss hold-up time: SAFETY Impulse voltage IEC60255-27 5 KV Graphical display: English, Spanish, French and Chinese
High Range (HI): 200 ms typical, worst withstand Basic display: English, Spanish, French, Chinese and Cyrilic
case 100 ms without unit reset Insulation IEC60255-27 500 V (test
Low Range (LO): 24 Vdc 30ms; 48Vdc resistance level) PACKAGING
100ms Electrostatic IEC60255-26/ Level 4
Discharge IEC6100-4-2 Approximate weight:
Immunity Net: 11 lbs (5 kg)
OUTPUTS Ship: 13.2 lbs (6 kg)
Radiated RF IEC60255-26/ Level 3
TRIPPING CONTACTS/OUTPUT RELAYS Electromagnetic IEC6100-4-3
Permanent current Carry continous 16 A Field Immunity ENVIRONMENTAL
Closing current Make and Carry for 1 second 60 A
during 1 second Electrical Fast IEC60255-26/ Zone A Temperature:
Opening current 0.3 A with L/R = 40 ms at 125 Vdc Transient IEC6100-4-4 Storage: -40 to +80° C
Immunity Operation: -10 to +60° C
0.25 A with L/R = 40 ms at 250 Vdc
Surge Immunity IEC60255-26/ Zone A Humidity: Up to 95% without condensing
IEC6100-4-5
REMOTE OUTPUTS Conducted RF IEC60255-26/ Level 3
Standard output points 32 APPROVALS
Immunity IEC6100-4-6
User output points 32 Power magnetic IEC60255-26/ Level 5 CE: Conforms to EN/IEC 60255, 61010
Immunity IEC6100-4-8 UL: UL508 Certicfied under E234610
EMC Power IEC60255-26/ Zone A
COMMUNICATIONS Frequency IEC6100-4-16
Immunity
FRONT PORT (COM2):
Type: RS232 Damped IEC60255-26/ 2.5 KV *Specifications subject to change without notice.
Oscillatory IEC6100-4-18 Common
Baude Rate: 300, 600, 1200, 2400, 4800, 9600, Wave Immunity Mode
38400, 57600 and 115200 bauds 1 KV Diff.
Default baud rate: 19200 bauds Mode
Protocol: ModBus® RTU / DNP 3.0 Voltage Dips & IEC60255-26/ Levels
ASYNCHRONOUS REAR PORTS: Interruptions IEC61000-4-11/ based on
IEC61000-4-29 IEC61000-4-11
Two COM1, COM2 (rear COM2 multiplexed with front & IEC61000-
port) 4-29
Type: Depending on model Ripple on DC IEC60255-26/ 15% Rated
Two RS485 ports IEC61000-4-17 DC value
Two 1mm-plastic F.O. ports Radiated & IEC60255-26/ Class A
Two multimode glass F.O. ports Conducted CISPR11/
with ST connectors. Emissions CISPR22
PROTOCOLS: IEC 60870-5-103 on COM1 Sinusoidal IEC60255-21-1 Class 1
DNP on COM1 & COM2 Vibration
Serial Modbus on COM1 & COM2 Shock & Bump IEC60255-21-2 Class 1
MECHANICAL
Seismic IEC60255-21-3 Class 2
CAN PORT:
Enclosure IEC60255-26/ IP52
Type: Cable or Multimode glass F.O. port Protection IEC6100-4-2
with ST connectors
Fiber Wave length: 1300 nm Cold test IEC60068-2-1 -40˚C 16 hrs
(storage)
Isolation: 2kV
Cold test IEC60068-2-1 -20˚C 16 hrs
ETHERNET PORT: (operational)
Type: Dry heat test IEC60068-2-2 85˚C 16 hrs
Model B: 10/100BaseTX self-negotiable (storage)
Model C: 10/100BaseTX + 100Base FX with Dry heat test IEC60068-2-2 60˚C 16 hrs
ST connectors CLIMATIC (operational)
Model D: 10/100BaseTX + Double Change of IEC60068-2-14 5 cycles (3+3)
100BaseFX with ST connectors Temperature -20˚C/60˚C
(physical media redundancy)
Damp Heat IEC60068-2-30 6 cycles
Model E: Redundant 10/100BaseTX Humidity Cyclic (12+12) 55˚C
Model G: 1588, 10/100 Base TX* + 100 Base TX @ 93% R.H.
Model H: 1588, 10/100 Base TX* + 100 Base FX Damp Heat IEC60068-2-78 40˚C @ 93%
Model J: PRP, 1588, 10/100 Base TX* + steady state R.H.
Redundant 100 Base FX
Model K: PRP, HSR , RSTP, 1588, 10/100 Base TX*
+ Redundant 100 Base FX
Model L: PRP, 1588, 10/100 Base TX +
Redundant 100 Base TX
Model M: PRP, HSR , RSTP, 1588, 10/100 Base TX
+ Redundant 100 Base TX
PROTOCOLS: ModBus TCP/IP
DNP over TCP/IP and UDP/IP
IEC 60870-5-104
IEC 61850
IEEE1588 (PTP)
IEC 62439-3 Clause 4 (PRP)
IEC 62439-3 Clause 5 (HSR)
IEEE 802.1D (RSTP)
Http, ftp, tftp (allow the use of a
standard Internet browser)
NOTES:
In Models C and D, the 10/100BaseTX port is selected by an
internal switch. Two indicating LEDs for transmission and
reception are included.
Models B,C, D and E supports IEC 61850 Edition 1.
Models G, H, J, K, L and M supports IEC 61850 Edition 2.

GEDigitalEnergy.com 11
Ordering
F650 * * * F * G * * * * * * * * Description
DISPLAY B Basic Display (see note 2)
M Graphic Display with Standard Symbols (see note 2)
N Graphic Display with IEC Symbols (see note 2)
I Iberdrola Graphic Display with Standard Symbols (see note 2)
J Iberdrola Basic Display (see note 2)
REAR SERIAL
F None
COMMUNICATIONS BOARD 1
A Redundant RS485
P Redundant plastic fiber optic
G Redundant glass fiber optic
X Redundant RS485 + fiber remote CAN bus I/O
Y Redundant plastic fiber optic + fiber remote CAN bus I/O
Z Redundant glass fiber optic + fiber remote CAN bus I/O
C Cable remote CAN bus I/O
M RS485 + cable remote CAN bus I/O
REAR ETHERNET
B 10/100 Base TX
COMMUNICATIONS BOARD 2
C 10/100 Base TX + 100 Base FX
D 10/100 Base TX + Redundant 100 Base FX
E Redundant 10/100 Base TX
G 1588, 10/100 Base TX* + 100 Base TX
H 1588, 10/100 Base TX* + 100 Base FX
J PRP, 1588, 10/100 Base TX* + Redundant 100 Base FX (See note3)
K PRP, HSR , RSTP, 1588, 10/100 Base TX* + Redundant 100 Base FX (See note3)
L PRP, 1588, 10/100 Base TX + Redundant 100 Base TX (See note3)
M PRP, HSR , RSTP, 1588, 10/100 Base TX + Redundant 100 Base TX (See note3)
I/O BOARD IN SLOT F 1 16 Digital Inputs + 8 Outputs
2 8 Digital Inputs + 8 Outputs + 2 Trip / Close circuit supervision circuits
4 32 Digital Inputs
5 16 Digital Inputs + 8 Analog Inputs
I/O BOARD IN SLOT G 0 None
1 16 Inputs + 8 Outputs
2 8 Digital Inputs + 8 Outputs + 2 Trip / Close circuit supervision circuits
4 32 Digital Inputs (See Note 1)
5 16 Digital Inputs + 8 Analog Inputs (See Note 1)
AUXILIARY VOLTAGE LO 24-48 Vdc (range 19.2 – 57.6)
HI 110-250 Vdc (range 88 – 300),120-230 Vac (range 96 – 250)
LOR Redundant L
HIR Redundant H

English/English
LANGUAGE C Chinese/English (See Note 2)
F French/ English
P Russian/English (See Note 2)
S Spanish/ English
T Turkish/ English

Modbus® RTU, TCP/IP, DNP 3.0 Level 2, IEC 60870-5-104


PROTOCOL 3 IEC 60870-5-103, Modbus RTU, TCP/IP
5 Procome, Modbus RTU, TCP/IP,
6 IEC 61850 Edition 2, Modbus RTU & TCP/IP, DNP 3.0 Level 2, IEC 60870-5-104

ENVIRONMENTAL PROTECTION H Harsh (Chemical) Environment Conformal Coating

ENHANCED DISPLAY E Enhanced Display with Front USB port

(*) Notes:
1. The number selected for option G must be equal or higher than the number selected for option F
for models including boards 4 and 5.
2. Display options with language selection:
Graphic display (M & N): available for English, French, Spanish and Chinese languages. For chinese
only IEC symbols option is available (N in ordering code).
Basic display (B): available for English, French, Spanish, Russian, Turkish and Chinese languages
3. Advanced features require new CPU:
• G & H: IEEE 1588 Precision Time Protocol (PTP), 61850 Edition 2.0.
• J & L: Parallel Redundancy Port (PRP,) IEEE 1588 Precision Time Protocol (PTP), 61850 Edition 2.0. GE Digital Energy
• K & M: High-Availability Seamless Redundancy (HSR), Rapid Spanning Tree Protocol (RSTP), Parallel
Redundancy Port (PRP), IEEE 1588 Precision Time Protocol (PTP), 61850 Edition 2.0. Toll Free: +1 877-605-6777
Direct: +1 678-844-6777

Related Products / Accessories


GEDigitalEnergy.com
MultiSync 100 - GPS Clock MultiSync100-P
IEC is a registered trademark of Commission Electrotechnique Internationale. IEEE is a registered
trademark of the Institute of Electrical Electronics Engineers, Inc. Modbus is a registered trademark
of Schneider Automation. ANSI is a registered trademark of American National Standards Institute,
Incorporated.
GE, the GE monogram, Multilin, EnerVista and MultiSync are trademarks of General Electric Company.

GE reserves the right to make changes to specifications of products described at any time without notice
and without obligation to notify any person of such changes.
GEA-12818A(E)