Vous êtes sur la page 1sur 11

Electrical Power and Energy Systems 94 (2018) 276–286

Contents lists available at ScienceDirect

Electrical Power and Energy Systems


journal homepage: www.elsevier.com/locate/ijepes

An algorithm for longitudinal differential protection of transmission


lines
Tomislav Rajić ⇑, Zoran Stojanović
University of Belgrade-School of Electrical Engineering, Bulevar kralja Aleksandra 73, Belgrade 11000, Serbia

a r t i c l e i n f o a b s t r a c t

Article history: This paper describes a new algorithm for longitudinal differential protection of transmission lines. Classic
Received 9 March 2017 stabilization is an unreliable method for avoiding unnecessary relay tripping in case of current trans-
Received in revised form 27 June 2017 former saturation during faults outside the protected zone. There are various methods for detecting cur-
Accepted 5 July 2017
rent transformer saturation. The paper’s thesis is that rather than the stabilization current, the direction
Available online 29 July 2017
of the currents introduced into the relay should be monitored. The proposed algorithm has been com-
pared to the algorithms used by renowned relay producers. Different types of faults have been simulated,
Keywords:
both within and outside of the protected zone, and the paper demonstrates how the relay trips when the
Differential relay
Transmission line
algorithm in question is used. The results have proven that current transformer saturation does not affect
Power system protection protection operation, and that a prompt relay response is obtained for faults occurring within the pro-
tected zone.
Ó 2017 Elsevier Ltd. All rights reserved.

1. Introduction are various methods that can prevent such occurrences. The
leading relay protection manufacturers offer different solutions
Analogue longitudinal differential protection is used for shorter, [3,12–15].
single-circuit transmission lines in double-fed networks. If optical The study presented in this paper is based on the idea that a
ground wires (OPGW) are used, the length of the line ceases to be a current direction indicator should be used instead of the stabiliza-
limiting factor. The longitudinal differential protection principle is tion current. The direction indicator is defined by the phase com-
based on the comparison of the currents located at the beginning parison illustrated in [16–18], using the currents brought from
and at the end of the line, resulting in a quick, sensitive and simple either end of the line. The procedure described in the paper was
protection concept that ensures that the faulted line is discon- compared to the conventional solutions which have been imple-
nected from the network. The protected zone is defined by the mented in practice. An advantage of the proposed approach is a
position of the current transformers from which signals are prompter response with a minimum of mathematical operations.
brought into the differential relay [1–3]. What is more, the algorithm is insensitive to current transformer
There are two types of algorithms for differential protection: saturation.
those that use phasors [4–6] and those that use instantaneous val-
ues of electrical quantities [7]. In addition to the classic approach,
which uses current signals exclusively, there are solutions which 2. Classic approach
require voltage inputs [8–10] too.
The major problem related to differential protection operation Fig. 1 shows the longitudinal differential protection operating
is current transformer saturation [11]. Namely, during a fault principle and the tripping characteristic of the differential relay.
located outside the protected zone (external fault), high fault cur- If the fault occurs outside of the protected zone, the left and
rents can saturate current transformers. If the characteristics of the right-end currents have the same direction and approximate inten-
current transformers set at the opposite ends of the line are not sities, i.e. their difference is negligible and the protection does not
identical, a high differential current starts flowing through the trip. Should the fault occur within the protected zone (internal
relay. This current may cause unnecessary relay tripping. There fault), the right-end’s current changes its direction, establishing a
significant current through the differential relay M, causing its
tripping.
⇑ Corresponding author. The minimum tripping current (Imin) defines the minimum relay
E-mail address: rajic@etf.rs (T. Rajić). tripping threshold and is set to 20–50% of the rated transformer

http://dx.doi.org/10.1016/j.ijepes.2017.07.001
0142-0615/Ó 2017 Elsevier Ltd. All rights reserved.
T. Rajić, Z. Stojanović / Electrical Power and Energy Systems 94 (2018) 276–286 277

Fig. 1. Longitudinal differential protection of transmission lines. (a) Longitudinal differential protection operating principle. (b) Relay tripping characteristic.

current. This quantity is defined since in an actual system, in a non- point first moved into the additional stabilization zone, and after-
fault condition, there is always a difference between the currents wards reached the protection tripping zone. The relay block ceases
measured at the opposite line ends due to the current transform- after a set time delay (of several basic periods) or when the mea-
ers’ imperfection and the charging current [1–3]. sured differential current drops below the tripping current
The relay trips if the operating point, defined by the differential [3,12,13].
and stabilization currents’ RMS values, is located within the relay A problem may occur when current transformers are saturated
tripping area (Fig. 1b). with the alternating current component during a fault outside the
protected zone. This may be the cause of unnecessary relay trip-
3. Existing algorithms ping, since the relay block ceases after a set time delay, while the
relay remains active due to the saturation with the alternating
In a classic longitudinal differential protection algorithm, a component of the fault current.
problem may occur in case of current transformer saturation due
to a fault outside the protected zone. This phenomenon leads to 3.2. Negative sequence component principle
unnecessary relay protection tripping. The leading relay protection
manufacturers have different methods for tackling this problem. In order to prevent unnecessary relay tripping during faults out-
What follows is an overview of principles based on additional sta- side the protected zone, ABB’s relays use the negative sequence
bilization and the negative sequence current component. component principle as a supplement to the classic approach to
differential protection.
3.1. Additional stabilization principle The differential current is calculated according to Eq. (2), indi-
vidually for each phase, while the universal stabilization current
The Siemens corporation uses conventional differential protec- (the stabilization current for all phases) is taken to be the maxi-
tion logic, supplemented by the additional stabilization principle. mum value of all the phase currents which are brought into the
Eqs. (1) and (2) are used for calculating the stabilization and dif- relay from both ends of the line [14,15]:
ferential currents, for each phase individually [3,12]:
n o
Istab ¼ max ILA ; IRA ; IBL ; IBR ; ICL ; ICR ð3Þ
Istab ¼ jIL j þ jIR j ð1Þ
The negative sequence component principle presupposes that
Idiff ¼ jIL  IR j ð2Þ by the isolation of this component we may determine whether
the fault is located within or outside the protected zone.
with the following explanation: The relay simultaneously performs multiple checks. The first-
IL – basic harmonic phasor of the left-end phase current, line check is an instance of classic differential protection, operating
IR – basic harmonic phasor of the right-end phase current. according to the principle of calculating the differential and stabi-
lization currents. The second-line analysis is the isolation of the
Fig. 2 shows the typical operating points depending on fault second and fifth harmonics; however, this function is inactive in
position (either within or outside the protected zone). The operat- most cases. The third-line and the most important analysis in
ing point is defined by the RMS values of the differential and stabi- terms of unnecessary relay tripping is based on the negative
lization relay currents. Point A corresponds to the non-fault sequence component. The analysis is based on the comparison of
operating condition. Should the fault occur within the protected negative sequence currents obtained from both ends of the trans-
zone – in the middle of the line, for example – the differential mission line. If the phase difference between these two currents
and stabilization currents become virtually identical. The new is larger than 60°, it is assumed that the fault occurred within
operating point will be located on the line forming a 45° angle with the protected zone, and a signal for breaker activation is sent.
the abscissa axis. This line is represented as the dash-dot-dash line, Otherwise, the signal will not be sent. To secure a proper reaction,
whereas the new operating point is marked by the letter D. In such the modules of the negative sequence components need to exceed
a setting, the relay operates properly [3,12,13]. the minimum set value. Usually the minimum value equals 4% of
The dashed line in Fig. 2 illustrates the movement of the oper- the base value (Ibase). The secondary rate current of the current
ating point during a fault outside the protected zone, when current transformers is taken as the base value. If Istab exceeds 150% of
transformers are saturated. Soon after the fault occurs, the operat- the base value, the minimum value is the sum of 0.04  Ibase + 0.1 -
ing point moves to position B. Only then does the operating point  Istab. If at least one negative sequence component per module is
move to position C, located within the relay tripping area. The relay lower than the set component, the relay ignores the third-line
detects this trajectory and blocks if it registers that the operating analysis. The relay trips if the results of all the analyses indicate
278 T. Rajić, Z. Stojanović / Electrical Power and Energy Systems 94 (2018) 276–286

Fig. 2. Differential protection with additional stabilization tripping characteristic.

that the fault occurred within the protected zone, which may Using RMS and mean values instead of instantaneous values
sometimes cause the relay to trip after an additional delay of prevents false relay tripping due to interference, noise, transients
6 ms [14,15]. during the fault, etc. The relay trips when both conditions, repre-
Given the fact that the method is based on the negative sented by Eqs. (8) and (9), are met:
sequence component, unnecessary protection tripping can occur
during a three-phase short circuit outside the protected zone if Idiff > Imin ð8Þ
the current transformers are heavily saturated.
IND 6 0 ð9Þ

4. The proposed algorithm The condition represented by (8) means that the differential
current RMS value must exceed the current which defines the min-
The new approach to longitudinal differential protection uses imum relay tripping threshold. The minimum tripping current
two quantities: the RMS value of the differential current (Idiff) (Imin) depends on several factors. The most influential factor is
and the current direction indicator (IND). the capacitive charging current, which can be estimated on the
In every sampling instant, current signal samples are brought basis of operational capacitance [13]:
into the relay from both the left line-end (iL) and the right line- 2p
end (iR). The instantaneous value of the differential current (idiff) IC ¼ pffiffiffi  U n  f n  cd  L  106 ð10Þ
3
is calculated as the difference between these two samples, whereas
the instantaneous value of the direction indicator (ind) is their pro- where:
duct, as shown by Eqs. (4) and (5): Ic – capacitive charging current (A),
Un – rated network voltage (kV),
idiff ¼ iL  iR ð4Þ fn – rated frequency (Hz),
cd – longitudinal operational capacitance (nF/km),
ind ¼ iL  iR ð5Þ L – line length (km).
It is necessary to form six buffers for this algorithm, two per
each phase. One buffer holds samples of the differential current’s This accounts for prompter tripping, since the relay practically
instantaneous values, whereas the other buffer holds the current operates as an overcurrent protection with a defined tripping cur-
direction indicator’s values. The reading of a new sample leads to rent. Unnecessary tripping during a fault outside the protected
a shift in the buffers, so that the first element of the buffer (the old- zone is avoided due to the condition (9). This is explained by the
est sample) is deleted, while the new sample takes the last posi- fact that the currents brought into the relay from the opposite ends
tion. The buffer content is taken as the basis for calculating the of the line have the same direction in a non-fault condition or dur-
differential current RMS value and the mean value of the direction ing a fault outside the protected zone, while they have opposite
indicator. The calculation method for these quantities is repre- directions if the fault occurred within the protected zone. In the
sented by Eqs. (6) and (7): former case, IND has a positive value, while it has a negative value
sffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi in the latter case. In Eq. (9), the symbol  is used if the current
Pm 2 brought into the relay from one line-end equals zero, which means
n¼1 idiff ðnÞ
Idiff ¼ ð6Þ that the transmission line is operating in idle regime.
m
Pm 5. Results
n¼1 indðnÞ
IND ¼ ð7Þ
m
The 110 kV transmission line model used for testing the algo-
with the following explanation: rithm was formed using the Matlab/Simulink software package, as
idiff – the nth differential current sample, illustrated in Fig. 3a. The longitudinal line parameters are the fol-
ind – the nth current direction indicator sample, lowing: rd = 0.12 O/km, ld = 1.3 mH/km and cd = 8.9 nF/km, while
m – the number of samples in the basic T signal period, i.e. in the longitudinal zero-sequence line parameters are: ro = 0.32 O/
the data window (m = T/Tod = 20). km, lo = 4.1 mH/km and co = 5 nF/km. The length of the line is set
T. Rajić, Z. Stojanović / Electrical Power and Energy Systems 94 (2018) 276–286 279

Fig. 3. A model for testing longitudinal differential protection of transmission lines. (a) Transmission line with current transformers model. (b) Left-end (L) and right-end (R)
current transformer magnetizing characteristics.

Fig. 4. Transformers’ secondary currents in phase A and the quantities calculated by the Siemens’ algorithm during an external fault. (a) Left-end (iL) and right-end (iR)
secondary transformer currents in phase A. (b) Differential current (Idiff) and differential tripping current (Itrip). (c) Stabilization current (Istab) and differential current (Idiff).

to L = 60 km. Active networks are found at both line-ends, their Current transformer models were formed on both sides of the
three-phase short circuit power being 5000 MVA, whereas the protected line, bearing the following characteristics: transmission
reactance/resistance ratio is X/R = 10 [19,20]. ratio 100/1 A/A, apparent power 10 VA, complex error 10 and accu-
In this model, the relay was implemented using the Matlab func- racy limit factor 10 (10P10). For simplicity’s sake, a linear magne-
tion block. Current signals from all the phases and both line-ends tizing characteristic was implemented (Fig. 3b). The first part of the
are brought to the block input. The sampling period Ts is set to characteristic corresponds to a 10% error, made by the current
1 ms. When the conditions for tripping are met, the block triggers transformer in case of primary currents up to 10In. In case of a cur-
the control inputs of the circuit breakers and opens them. The rent exceeding 10In, the transformers become saturated and leave
same block was used for all three algorithms, allowing for a com- the defined class of accuracy. The second part of the characteristic
parative analysis. is not defined identically for the left-end and right-end current
280 T. Rajić, Z. Stojanović / Electrical Power and Energy Systems 94 (2018) 276–286

Fig. 5. Quantities calculated by ABB’s algorithm during an external fault. (a) Differential current (Idiff) and differential tripping current (Itrip). (b) Negative sequence component
modules at both ends (INegSeqL and INegSeqR) and minimum value (IMINNegSeq). (c) Angle difference between negative sequence component phasors (delta) and set boundary
(boundary).

Fig. 6. Quantities obtained by the new algorithm during an external fault. (a) Differential current (Idiff) and direction indicator (IND). (b) Differential current (Idiff) and
minimum tripping current (Imin), direction indicator (IND), and the signal sent to the circuit breaker (TRIP).

transformers. The second part of the left-end current transformer 5.1. Faults outside the protected zone
characteristic more or less corresponds to the horizontal semi-
straight line. The right-end current transformer characteristic devi- The presented network model was used for simulations.
ates from the continuation of the first part of the characteristic by It was observed how algorithms operate when a fault occurs
15°. outside the protected zone, with the simultaneous saturation of
A 10 X resistive load is found on the secondary side of all cur- current transformers at both line-ends. Being the most critical
rent transformers, which takes into account the relay impedance one, the three-phase short circuit located just after the right-end
and the secondary connections’ resistance. Such a load was chosen current transformers was observed, as it generates the highest
in order to simulate current transformer saturation with both the fault currents with a low negative sequence current component.
direct component of the fault current and its alternating compo- Fig. 4a illustrates the instantaneous values of the secondary trans-
nent once the direct component has been damped [11]. former currents that are brought to the relay. Due to the different
Due to the variation in the voltage and frequency values, as well core characteristics of the current transformers at opposite line
as the different magnetizing characteristics of the current trans- ends, the secondary current is more distorted at the left end.
formers, the set value should be approximately twice as large as
the calculated capacitive charging current Ic. In the observed over- 5.1.1. Additional stabilization principle
head transmission line (Un = 110 kV, L = 60 km), Ic is 10.6 A (sec- Fig. 4b and c shows the stabilization current (Istab), the differen-
ondary 0.106 A). Therefore, the relay tripping threshold of 0.2 A tial current (Idiff) and the differential tripping current (Itrip). The dif-
(20% of the rated secondary current, Irs = 1 A) meets the aforemen- ferential tripping current represents the relay tripping
tioned criterion. characteristic in Fig. 2. The relay reacts when the RMS value of
The formed model was used to simulate various faults. For clar- the differential current exceeds the RMS value of the differential
ity’s sake, all figures show only the currents and the relevant quan- tripping current.
tities of phase A. The fault instant in all the simulations is t = 0.04 s. From Fig. 4b it can be seen that in the instant t = 0.048 s the dif-
This instant enables the highest value of the DC fault current com- ferential current exceeds the differential tripping current, although
ponent in phase A. the fault occurred outside the protected zone, when the relay is not
T. Rajić, Z. Stojanović / Electrical Power and Energy Systems 94 (2018) 276–286 281

Table 1 expected to trip. However, Fig. 4c shows that when the stabiliza-
Fault types. tion current (Istab) becomes significantly high (over 7In), which
Fault number Fault type Fault position [%]a Faulted phases happens in the instant t = 0.043 s, the differential current remains
Fault 1 Two-phase-to-earth 20 A and B low for a while. This means that the relay blocking condition is ful-
Fault 2 Single phase 50 A filled whenever additional stabilization principle is used. This
Fault 3 Two-phase 80 A and C instant corresponds to the operating point B in Fig. 2. Even though
a
Line length percentage viewed from the left hand-side.
the differential current in the instant t = 0.067 s drops below the
differential tripping current, in 33 ms the differential current will
again exceed the differential tripping current and remain higher

Fig. 7. Relevant quantities in phase A during Fault 1 (Siemens and ABB). (a) Differential current (Idiff) and differential tripping current (Itrip)-Siemens. (b) Differential current
(Idiff) and differential tripping current (Itrip)-ABB. (c) Negative sequence component modules at both ends (INegSeqL and INegSeqR) and minimum value (IMINNegSeq)-ABB. (d) Angle
difference between negative sequence component phasors (delta) and set boundary (boundary)-ABB.

Fig. 8. Quantities obtained by the new algorithm during Fault 1. (a) Differential current (Idiff) and direction indicator (IND). (b) Differential current (Idiff) and minimum tripping
current (Imin), direction indicator (IND), and the signal sent to the circuit breaker (TRIP).
282 T. Rajić, Z. Stojanović / Electrical Power and Energy Systems 94 (2018) 276–286

Fig. 9. Relevant quantities in phase A during Fault 2 (Siemens and ABB). (a) Differential current (Idiff) and differential tripping current (Itrip)-Siemens. (b) Differential current
(Idiff) and differential tripping current (Itrip)-ABB. (c) Negative sequence component modules at both ends (INegSeqL and INegSeqR) and minimum value (IMINNegSeq)-ABB. (d) Angle
difference between negative sequence component phasors (delta) and set boundary (boundary)-ABB.

Fig. 10. Quantities obtained by the new algorithm during Fault 2. (a) Differential current (Idiff) and direction indicator (IND). (b) Differential current (Idiff) and minimum
tripping current (Imin), direction indicator (IND), and the signal sent to the circuit breaker (TRIP).

from then on. This is explained by the fact that the current trans- value (IMINNegSeq) during two time intervals: 0.043–0.052 s and
formers remain saturated even after the fault current’s direct com- 0.054–0.057 s (Fig. 5b). During other time intervals, at least one
ponent is absent. It can be concluded that a relay that uses of the two negative sequence components per module is lower
additional stabilization will remain active after the blocking time than IMINNegSeq, so there will be no phase angle comparison.
period, thus causing unnecessary tripping. Fig. 5c illustrates the temporal change of the phase shift (delta)
of the I NegSeqL and I NegSeqR . During the 0.48–0.54 s time interval,
5.1.2. Negative sequence current component principle the phase angle difference exceeds the set boundary of 60°. It
Fig. 5 presents simulation results when a negative sequence can be concluded that in the instant t = 0.48 s the negative
current component system is used. Fig. 5a shows that the differen- sequence component protection will generate a tripping signal
tial current value exceeds the differential tripping current in the and unnecessarily switch off the line, as the negative sequence
instant t = 0.048 s. The negative sequence components on the left components will exceed the minimum, and their phase shift will
(I NegSeqL ) and right (I NegSeqR ) sides of the line exceed the minimum be larger than 60°.
T. Rajić, Z. Stojanović / Electrical Power and Energy Systems 94 (2018) 276–286 283

Fig. 11. Relevant quantities in phase A during Fault 3 (Siemens and ABB). (a) Differential current (Idiff) and differential tripping current (Itrip)-Siemens. (b) Differential current
(Idiff) and differential tripping current (Itrip)-ABB. (c) Negative sequence component modules at both ends (INegSeqL and INegSeqR) and minimum value (IMINNegSeq)-ABB. (d) Angle
difference between negative sequence component phasors (delta) and set boundary (boundary)-ABB.

Fig. 12. Quantities obtained by the new algorithm during Fault 3. (a) Differential current (Idiff) and direction indicator (IND) and (b) Differential current (Idiff) and minimum
tripping current (Imin), direction indicator (IND), and the signal sent to the circuit breaker (TRIP).

5.1.3. The new approach


The changes in the differential current’s RMS value and in the
Table 2 direction indicator’s mean value are shown in Fig. 6. For clarity’s
Relay tripping times depending on the choice of algorithm [ms].
sake, in Fig. 6b these quantities are shown over a shorter time
Fault number SIEMENS ABB New algorithm interval. Fig. 6b also features the signal sent to the circuit breaker
Fault 1 4 4 1 (TRIP). It can be seen that the direction indicator is above 0 all the
Fault 2 5 4 2 time, thus blocking protection. Idiff exceeds Imin in the instant
Fault 3 6 7 1 0.045 s. However, protection is already blocked due to the
IND > 0 condition, and the line will not be switched off
unnecessarily.
284 T. Rajić, Z. Stojanović / Electrical Power and Energy Systems 94 (2018) 276–286

Table 3
Set values of fault resistance, line length, and source power.

Fault Fault Fault resistance Line length 3-Phase short-circuit power on the left side 3-Phase short-circuit power on the right side
number type [X] [km] [MVA] [MVA]
Fault 4 A-G 50 60 5000 5000
Fault 5 ABC 0 150 5000 5000
Fault 6 AC 0 60 5000 200
Fault 7 AB-G 50 150 5000 200

Fig. 13. Quantities obtained by the new algorithm during Fault 4. (a) Differential current (Idiff) and direction indicator (IND). (b) Differential current (Idiff) and minimum
tripping current (Imin), direction indicator (IND), and the signal sent to the circuit breaker (TRIP).

Fig. 14. Quantities obtained by the new algorithm during Fault 5. (a) Differential current (Idiff) and direction indicator (IND). (b) Differential current (Idiff) and minimum
tripping current (Imin), direction indicator (IND), and the signal sent to the circuit breaker (TRIP).

5.2. Faults within the protected zone the fault, it is detected that the fault is positioned within the pro-
tected zone (the negative sequence modules exceed the minimum
The aforementioned algorithms were tested for faults within value and the angle between them is larger than 60°). Therefore, it
the protected zone as well. Fault types are given in Table 1. The can be concluded that there is no blocking and that the relay trips
faults were simulated at points corresponding to 20%, 50% and 4 ms after the fault.
80% of the line’s length. Fig. 8 shows the quantities used by the new algorithm during
Fig. 7a presents quantities which the Siemens’s algorithm uses Fault 1. Soon after the fault occurs, the differential current exceeds
to test the need for tripping. A fault can be detected after just Imin, thus fulfilling the first condition for tripping. The direction
4 ms. Fig. 7b–d features the relevant quantities of the ABB’s algo- indicator becomes negative soon afterwards, and the second condi-
rithm. Based on the differential current (Fig. 7b), the first condition tion is met as well. It takes only 1 ms for the relay to trip.
for relay tripping is met 4 ms after the fault occurs. By analyzing Similar conditions can be seen in Figs. 9–12, relating to Fault 2
the negative sequence component (Fig. 7c and d) just 1 ms after and Fault 3 respectively.
T. Rajić, Z. Stojanović / Electrical Power and Energy Systems 94 (2018) 276–286 285

Fig. 15. Quantities obtained by the new algorithm during Fault 6. (a) Differential current (Idiff) and direction indicator (IND). (b) Differential current (Idiff) and minimum
tripping current (Imin), direction indicator (IND), and the signal sent to the circuit breaker (TRIP).

Fig. 16. Quantities obtained by the new algorithm during Fault 7. (a) Differential current (Idiff) and direction indicator (IND). (b) Differential current (Idiff) and minimum
tripping current (Imin), direction indicator (IND), and the signal sent to the circuit breaker (TRIP).

Table 2 offers a clear overview of relay tripping times during the When transmission lines are very long, there might be phase
aforementioned faults when different algorithms are implemented. unbalance between the currents that are compared due to the
excessive influence of the capacitive charging current. Conse-
quently, the direction indicator IND may be below zero in a non-
5.3. The influence of fault resistance, line length, and source power
fault condition. Although the protection does not issue a tripping
command in that case, as the condition (8) is not met as well, phase
The presented algorithm was tested under the following condi-
balance can be easily achieved by introducing sensitivity into the
tions: big fault resistance, a long overhead line, a strong source at
current buffers, as explained in [16,17].
one end of the line and a weak source at the opposite end. The
other simulation parameters were not altered. Table 3 shows the
set values of fault resistance, line length, and source power. 6. Conclusion
For a 150 km line, it is necessary to pre-set the minimal tripping
current (Imin). If Eq. (10) is applied, the capacitive charging current The paper presented an algorithm for longitudinal differential
is 26.6 A (secondary 0.266 A). Based on this value, the threshold protection of transmission lines. An electric power model was
was set to 0.4 A, which equals 40% of the rated secondary current. formed and various algorithms were tested. Fault positions and
All fault types were simulated: the single phase fault (Fault 4), fault types were varied during the testing. The proposed solution
the three-phase fault (Fault 5), the two-phase fault (Fault 6), and was compared to those used by renowned relay protection manu-
the two-phase-to-earth fault (Fault 7). Faults 4, 5, 6, and 7 were facturers. The results of the simulations have proven that the given
located at points corresponding to 20%, 50%, 80%, and 50% of the algorithm is completely insensitive to current transformer satura-
line length respectively. tion, which means that there is no unnecessary relay tripping during
The simulation results are shown in Figs. 13–16. an external fault. Compared to the commercial solutions, the new
As it can be inferred from the illustrations, the relay successfully algorithm is highly competitive in terms of how promptly it trips
detects the fault in such situations. The relay tripping times were during faults within the protected zone. Moreover, another advan-
5 ms, 2 ms, 2 ms, and 2 ms respectively. tage of the proposed algorithm when compared to the solutions
286 T. Rajić, Z. Stojanović / Electrical Power and Energy Systems 94 (2018) 276–286

presented in some recent studies is its prompt response with as few [8] Wen M, Chen D, Yin X. An energy differential relay for long transmission lines.
Int J Electr Power Energy Syst 2014;55:497–502.
mathematical operations as possible. The algorithm is simple and
[9] Kawady T, Talaab A, Ahmed E. Dynamic performance of the power differential
does not require complicated signal processing. The future research relay for transmission line protection. Int J Electr Power Energy Syst
will be aimed at the implementation of the given algorithm in the 2010;32:390–7.
protection of double transmission lines, transformers, and [10] Aziz MMA, Zobaa AF, Ibrahim DK, et al. Transmission lines differential
protection based on the energy conservation law. Electric Power Syst Res
generators. 2008;78:1865–72.
[11] Ajaei FB, Sanaye-Pasand M, Davarpanah M, et al. Compensation of the current-
Acknowledgments transformer saturation effects for digital relays. IEEE Trans Power Delivery
2011;26:2531–40.
[12] SIEMENS: Manual – SIPROTEC – differential protection 7UT6x. SIEMENS
The paper’s authors express their gratitude to the Serbian Min- Version 4.6; June 2012. p 105–8.
istry of Education, Science and Technological Development, under [13] SIEMENS: Manual – SIPROTEC – line differential protection with distance
protection 7SD52/53. SIEMENS Version 4.6. p 102–4.
whose auspices this research was conducted, as part of the Project [14] ABB: Application manual – line differential protection RED670 2.1 IEC. ABB,
III 42009 Intelligent Power Energy Networks. Product version 2.1; August 2016. p. 142–8.
[15] ABB: Technical manual – line differential protection RED670 2.0 IEC. ABB,
Product version 2.0; July 2016. p. 150–8.
References [16] Stojanovic Z, Djuric M. An algorithm for directional earth-fault relay with no
voltage inputs. Electric Power Syst Res 2013;96:144–9.
[1] Ðurić M, Stojanović Z. Relay protection. Belgrade: KIZ ‘CENTER’; 2014. [17] Stojanovic Z, Djuric M. The algorithm for directional element without dead
[2] Ðurić M, Terzija V, Radojević Z, et al. Algorithms for digital relaying. Belgrade: tripping zone based on digital phase comparator. Electric Power Syst Res
ETA; 2012. 2011;81(2):377–83.
[3] Ziegler G. Numerical differential protection: principles and applications. [18] Forcan M, Stojanović Z. An algorithm for sensitive directional transverse
second ed. Wiley; 2012. pp. 66–69 and 202–233. differential protection with no voltage inputs. Electric Power Syst Res
[4] Krishnanand K, Dash P, Naeem M. Detection, classification, and location of 2016;137:86–95.
faults in power transmission lines. Int J Electr Power Energy Syst [19] Rajić T, Stojanović Z. Longitudinal differential protection of lines with
2015;67:76–86. automatic reclosing. Jahorina, Bosnia and Herzegovina: INFOTEH; 2015. p.
[5] Hosny A, Sood VK. Transformer differential protection with phase angle 180–5.
difference based inrush restraint. Electric Power Syst Res 2014;115:57–64. [20] Rajić T, Stojanović Z. Influence of stabilization current on longitudinal
[6] Dambhare S, Soman SA, Chandorkar MC. Adaptive current differential differential protection of transmission lines. Jahorina, Bosnia and
protection schemes for transmission-line protection. IEEE Trans Power Herzegovina: INFOTEH; 2016. p. 78–83.
Delivery 2009;24:1756–62.
[7] Deng X, Yuan R, Li T, et al. Digital differential protection technique of
transmission line using instantaneous active current: theory, simulation and
experiment. IET Gener Transm Distrib 2015;9:996–1005.

Vous aimerez peut-être aussi