No Description Unit
A LT PANELS
Supply, Installation, Testing and Commissioning of Indoor type LT
1.00 Switchboards, Floor mounting type, 3b Design construction,
Bottom/Top entry. Refer enclosed SLD.
Refer standard : IS 13947, 8623(part-1)
Enclosure: Compartmentalized Single front CRCA
Doors:2mm Body:2mm Gland:3mm covers and partitions:1.6mm
IP class:IP52 for Indoor
Bus bars: Electrolytic grade conductivity as per standard IS 5082
Bubs bar Material: As per SLD 1(0.8A/Sqmm for Al & 1.4A/Sqmm for
Copper)
Bus bar supports: DMC/FRP/SMC
Bus bar joints: Shrouded/Tinned
Breakers: Microprocessor based above 250A/Thermal Magnetic up to
250A
Protection releases: As per SLD(Adjustable over current & short circuit
unless otherwise specified)
Ics=Icu for all breakers
Utilization category: All MCCB/ACB's shall be Cat: A except ACB's for
Ltg & raw power input distribution panel shall be with Cat: B .
Louvers: Busbar chamber shall have louvers with fine mesh inside
Shade: Epoxy powder coated RAL 7032
Design: Modular type
Cable entry: As per site condition
SPD should be B+C type
Note:1) All the breakers shall have spreaders/phase
separators/RHOM/Pad lock/Door lock/trip free 2)Breakers shall have
provision to add shunt trip 3) Shunt trip for the breakers to be
provided wherever shown 4) Insulated shrouding shall be provided for
live parts 5) FRLS PVC copper wires shall be used for control wiring 6)
CT's shall be provided with shorting terminals 7) MFM shall be BMS
Compatible with RS485 Port.
B) Busbar:
1 Set of 1000A, TPN Aluminium Busbar Chamber for the entire length
of the Panel as per specification
C) Outgoings :
1000Amps FP Variable Type MCCB with Manual Closing Mechanism of
36 kA Short Circuit Rating with Thermal O/L and Magnetic S/C
Protection - 1 No.
630Amps TPN Variable Type MCCB with Manual Closing Mechanism of
36 kA Short Circuit Rating with Thermal O/L and Magnetic S/C
Protection - 3 Nos.
D) Indications:-
LED ON/OFF/ TRIP indication for incomer controlled with control
MCB's
LED R,Y & B Phase indication for incomer controlled with control MCB's
E) Metering:-
3 phase, 4 wire, Digital flush type Class-I accuracy multifunction
meter with RS 485, 1000/5A, Class-I, 5VA burden moulded CT's. - 1
No
1 No 36KA SPD-B+C class for three phase
E) Metering:-
3 phase, 4 wire, Digital flush type Class-I accuracy multifunction
meter with RS 485, 630/5A, Class-I, 5VA burden moulded CT's. - 2
Nos.
1 No 25KA SPD-B+C class for three phase
B) Busbar:
1 Set of 800A, TPN Aluminium Busbar Chamber for the entire length of
the Panel as per specification
C) Outgoings :
630Amps TPN Variable Type MCCB with Manual Closing Mechanism of
36 kA Short Circuit Rating with Thermal O/L and Magnetic S/C
Protection - 2 Nos.
160Amps TPN Variable Type MCCB with Manual Closing Mechanism of
36 kA Short Circuit Rating with Thermal O/L and Magnetic S/C
Protection - 1 No.
63Amps TPN Variable Type MCCB with Manual Closing Mechanism of
36 kA Short Circuit Rating with Thermal O/L and Magnetic S/C
Protection - 1 No.
D) Indications:-
LED ON/OFF/ TRIP indication for incomer controlled with control
MCB's
LED R,Y & B Phase indication for incomer controlled with control MCB's
E) Metering:-
3 phase, 4 wire, Digital flush type Class-I accuracy multifunction
meter with RS 485, 800/5A, Class-I, 5VA burden moulded CT's. - 2
Nos.
1 No 36KA SPD-B+C class for three phase
E) Metering:-
3 phase, 4 wire, Digital flush type Class-I accuracy multifunction
meter with RS 485, 630/5A, Class-I, 5VA burden moulded CT's. - 1
No.
1 No 25KA SPD-B+C class for three phase
E) Metering:-
1
1
1
1
1