FIRE PREVENTION DEPARTMENT,GENERAL DIRECTORATE OF

PROJECT DESCRIPTION FIRE SAFETY NOTES/PROVISIONS GENERAL NOTES: CIVIL DEFENCE, MINISTRY OF THE INTERIOR, STATE OF QATAR

GENERAL: FIRE FIGHTING SYSTEM THE MAIN CONTRACTOR WILL FOLLOW THE FOLLOWING NOTES:
PROP. MODIFICATION (BASEMENT FLR., GROUND FLR.& MEZZANINE FLR.) PREVIOUSLY AUTOMATIC SPRINKLER SYSTEM
APPROVED B+G+M+2+PCOMM./ RESIDENTIAL BLDG. PREVIOUS PSNO. N/2014/0002873 COVERAGE: THROUGHOUT
LOCATED IN AL KHOR AREA PARTIAL PROTECTION: SPECIFY AREAS PROTECTED:---------------------------------------
MANUAL FIRE FIGHTING SYSTEM
NUMBER OF STOREYS: B+G+M+2+P FIRE HOSE REELS 1 in (25mm)
TOTAL NO. OF STOREYS = 5 STOREYS ABOVE GROUND LEVEL PORTABLE FIRE EXTINGUISHERS:

DESCRIPTION OF LEVEL: LANDING VALVE ( CLASS 1)


YES
BASEMENT LEVEL. - CAR PARKING AREA,UNDERGROUND FIRE PUMP ROOM / NOT APPLICABLE
FIRE WATER TANK & GENERATOR ROOM FIRE WATER TANK
GROUND FLOOR - SHOPS/ LOBBY,CAR PARKING REINFORCED CONCRETE
STEEL
MEZZANINE FLOOR - SHOPS / RESIDENTIAL FLATS OTHER,SPECIFY (NON-COMBUSTIBLE):---------------------------------
BREECHING INLET ( FIRE DEPARTMENT CONNECTION)
TYPICAL (1ST-2ND) FLOOR - RESIDENTIAL FLATS ( EXISTING )
YES (INDICATE LOCATION ON PLAN)
PENTHOUSE FLOOR LEVEL - RESIDENTIAL FLAT & ROOF STAIRCASES ( EXISTING ) NOT APPLICABLE
BUILDING HEIGHT: OTHER AUTOMATIC SUPPRESSION SYSTEM
THE BUILDING HAS AN HABITABLE HEIGHT OF 14.95 METERS AT PENTHOUSE FLOOR TYPE APPLICATION/AREAS PROTECTED
LEVEL. WATER SPRAY SYSTEM ------------------------------------------------------
WATER MIST SYSTEM ------------------------------------------------------
BUILDING DATA CLEAN AGENT SUPPRESSION SYSTEM
FOAM SYSTEM
------------------------------------------------------
------------------------------------------------------
I'KAMAL ABDELFATTAH A MECHANICAL ENGINEER WITH UPDA REGISTRATION NO.1705 AS GRADE A,

BEING THE CONSULTANT HEREBY CERTIFY THAT THE FIRE SAFETY WORKS SHOWN ON THESE

BUILDING NAME : DRY CHEMICAL SYSTEM ------------------------------------------------------ PLANS HAS BEEN DESIGNED IN ACCORDANCE WITH THE PROVISIONS OF (NFPA 10 ),

WET CHEMICAL SYSTEM ------------------------------------------------------ (NFPA 13 ),(NFPA 14 ), (NFPA 20 )(NFPA 22,101,170 AND 5000)

KITCHEN/RANGE HOOD EXTINGUISHING SYSTEM ( AS PER NFPA 96 )


------------------------------------------------------ (NFPA 25 ) AND LOCAL FIRE SAFETY CODES OR STANDARDS

OTHER, SPECIFY:------------------------------------------------------- BEING IMPOSED BY QCD.


( CHECK PROVISIONS & SPECIFY LOCATION PROTECTED) FURTHER, I CERTIFY THAT I AM FULLY AWARE AND COMMIT MYSELF RESPONSIBLE TO THIS
PROJECT AND ALL THE CONDITIONS PRESCRIBED UNDER THE EXISTING LAW NO. 19 OF 2005,
FIRE ALARM SYSTEM
THE LAW REGULATING THE PRACTICE OF ENGINEERING PROFESSION IN THE STATE OF QATAR.
AUTOMATIC DETECTION AND ALARM
AFFIXED IS MY SIGNATURE TO ATTEST WITH ABOVE UNDERTAKING.
HAZARD CLASSIFICATION: ORDINARY HAZARD MANUAL
SMOKE ALARMS
NEW CONSTRUCTION: YES-------- NO-------- BATTERY OPERATED
KAMAL ABDEL FATTAH
QATARI HOME DESIGN & ENGINEERING CONSULTANTS
REPAIR OF EXITING: YES-------- NO-------- OTHER ---------------------- P.O. BOX. 7825
EMERGENCY COMMUNICATION SYSTEM
TEL. +974 44438800 FAX. +974 44352260
RENOVATION OF EXISTING: YES-------- NO-------- MAIN PANEL SUB - PANEL
MODIFICATION OF EXISTING: YES-------- NO-------- LOCATION: SPECIFY LOCATION
COMMAND CENTER
RECONSTRUCTION OF EXISTING: YES-------- NO-------- GUARD/SECURITY ROOM
CHANGE OF OCCUPANCY: YES-------- NO-------- OTHER, SPECIFY: RECEPTION LOBBY AT GROUND FLOOR LEVEL
CHANGE OF USE: YES-------- NO-------- EMERGENCY LIGHTING
LOCATION: ILLUMINATION REQUIREMENT
ADDITION OF EXISTING: YES-------- NO--------
MULTIPLE OCCUPANCY YES-------- NO-------- EXIT 108 LUX
EXIT ACCESS 108 LUX
-SEPARATED OCCUPANCY YES-------- NO-------- - IN NORMAL CASE :
EXIT DISCHARGE 108 LUX
-MIXED OCCUPANCY YES-------- NO-------- AIR CONDITIONING VENTILATION & SMOKE CONTROL SYSTEM
INCIDENTAL OF USE: YES-------- NO-------- POSITIVE PRESSURE VENTILATION SYSTEM LEGENDS & SYMBOLS : QATARI HOME
SPECIFY: STAIRWELL DESIGN & ENGINEERING CONSULTANTS
D:\ASMY DRAWING\JPEG - Print\member_logo_blk.jpg

SPECIAL STRUCTURE: YES-------- NO-------- SMOKE - STOP- LOBBY E-mail: qatarihome@qatarihome.com


FIRE FIGHTING LOBBY : qatarihome4438800@yahoo.com
HISTORICAL BUILDING: YES-------- NO--------
FIRE LIFT SHAFT - IN CASE OF FIRE MODE : 44438800, 44352260, P.O. BOX. 7825, DOHA-QATAR.
OTHERS: ( SPECIFY OTHER SCOPE OF WORK) ESCAPE CORRIDOR ESCAPE CORRIDOR
OTHERS,SPECIFY -------------- OTHERS,SPECIFY --------------
NOTE: EXISTING REFERS TO BUILDING WITH PREVIOUS QCD APPROVAL
SMOKE AND HEAT EXHAUST VENTILATION SYSTEM ( SHEVS)

AREA STATEMENT MECHANICAL


APPLICATION:
NATURAL
APPLICATION:
AREA STATEMENT BASEMENT CAR PARK BASEMENT CAR PARK
PLOT AREA - 807.00 sqm WAREHOUSE AND / OR STORAGE WAREHOUSE AND / OR STORAGE
FACTORY FACTORY
BASEMENT FLOOR AREA - 669.70 sqm ATRIUM FIRE PUMP ROOM
GROUND FLOOR AREA - 573.60 sqm MODIFICATION FIRE PUMP ROOM
MEZZANINE FLOOR AREA - 498.90 sqm OTHERS, SPECIFY-----------------------------
KITCHEN/OVEN/ ( NFPA 96 / NFPA 86)
FIRST FLOOR AREA - 556.70 sqm OTHERS, SPECIFY PUMP ROOM ( SHALL BE APPROVED BY MECHANICAL VENTILATION
SECOND FLOOR AREA - 556.70 sqm
OTHER MODE OF VENTILATION COMPLIANT TO NFPA 20 )
PENTHOUSE FLOOR AREA - 148.30 sqm
NATURAL THRU AIR/ SMOKE SHAFTS
TOTAL BUILT UP AREA - 3003.90 sqm NATURAL THRU EXTERIOR WALL OPENINGS SPECIFY- STAIRWELL
COVERED AREA - 573.60 sqm OTHERS, SPECIFY --------------------------------------
PERCENTAGE COVERED AREA - 71.07 % EMERGENCY POWER SUPPLY SYSTEM
NO.OF FLATS DIESEL - ENGINE GENERATOR SET
OTHERS, SPECIFY --------------------------------------
MEZZANINE FLOOR - 2 UNITS GAS INSTALLATION ( SPECIFY TYPE)---------------------------
TYPICAL FLOOR ( 4 UNITS X 2 FLR. ) - 8 UNITS COVERAGE TANK LOCATION:
MOHAMMED AHMED A A ALMOHANADI
PENTHOUSE FLOOR - 1 UNITS CENTRALIZED ABOVE GROUND
TOTAL NO.OF FLATS - 11 UNITS LOCAL UNDERGROUND
NO.OF PARKING TANK CAPACITY: MOUNDED
--------------------------------- OTHER : ( SPECIFY) ---------------------
BASEMENT LEVEL. - 10 UNITS
TANK TYPE AND MAKE
GROUND LEVEL - 6 UNITS
CYLINDER
TOTAL NO.OF PARKING - 16 UNITS CONTAINER
OTHERS, SPECIFY --------------------------------------
FIRE PROTECTION ( LPG INSTALLATION )
ACTIVE PASSIVE
PROP. MODIFICATION (BASEMENT FLR.,
BUILDING / TYPE OF CONSTRUCTION AUTOMATIC SUPPRESSION SYSTEM
NO ACTIVE FIRE PROTECTION
( PROVIDE DETAILS OF MINIMUM CONSTRUCTION
AND INSTALLATION REQUIREMENTS-AFE GROUND FLR.& MEZZANINE FLR.)
A. BUILDING / TYPE OF CONSTRUCTION ( PROVIDE WITH FIRE SAFETY ANALYSIS) DISTANCE, RATED ENCLOSURES, ETC.) PREVIOUSLY APPROVED B+G+M+2+P
OTHER FIRE SAFETY PROVISIONS COMM./ RESIDENTIAL BLDG. PREVIOUS PS
1. MANUAL FIRE ALARM BOXES SHAL BE PROVIDED ON ALL NATURAL EXITS, ACCESS PATHS NEAR REQUIRED EXIT
AREA & SHALL COMPLY WITH NFPA 72 & QATAR CIVIL DEFENSE. NO. N/2014/0002873
2. SURFACE MOUNTED FIRE ALARM BELLS SHALL BE LOCATED DIRECTLY ABOVE THE MANUAL FIRE ALARM BOXES
B. TYPE OF BUILDING MATERIALS AND FIRE RESISTANCE RATING OF BUILDING ELEMENTS AND SHALL BE SPACED IN ACCORDANCE WITH NFPA 72 & PROVISIONS OF QATAR CIVIL DEFENSE. - CANCELLATION OF ELECTRICAL SUBSTATION
3. A COMPLETE FIRE ALARM NOTIFICATION AUDIBLE & VISIBLE SIGNAL & AUTOMATIC SMOKE DETECTION SYSTEM,
CONSTRUCTION ELEMENT FIRE RATING SHALL BE PROVIDED ON THE ENTIRE BLDG. & SHALL COMPLY WITH NFPA 72 & QCD. - NEW LAYOUT OF PARKING AREA / RAMP
EXTERIOR BEARING WALLS 2 HOURS
4. FIRE STAIR DOORS & DOORS THAT OPEN INTO EXIT ACCESS CORRIDORS SHALL BE SELF CLOSING & SELF LATCHING.
- ADDT'L SHOP AT GROUND FLOOR
5. ALL CORRIDOR WALLS SHALL BE EXTENDED FROM FLOOR TO REACH SLAB SOFFIT AND SHALL HAVE A FIRE
INTERIOR BEARING WALLS RESISTANCE RATING OF MINIMUM 1-HOUR.
2 HOURS
6. ALL FIRE RESISTIVE SYSTEM SHALL BE FIRE BLOCKED & ALL PENETRATIONS IN FIRE RATED SYSTEM SHALL BE VENTILATION SYSTEM
COLUMNS 2 HOURS FILLED WITH FIRE STOPPING MATERIAL IN ACCORDANCE WITH NFPA CODE REQUIREMENTS.
BEAMS,GIRDERS,TRUSSES & ARCHES 2 HOURS 7.
8. THE BUILDING PLAN SHALL COMPLY WITH THE MINIMUM STANDARDS & REQUIREMENTS FOR FIRE SAFETY SET
FLOOR/CEILING ASSEMBLIES 2 HOURS BY THE FIRE PREVENTION DEPT. GENERAL DIRECTORATE OF CIVIL DEFENCE, MOI,QATAR.
ROOF/CEILING ASSEMBLIES 1 HOURS
INTERIOR NONBEARING WALLS 0 HOURS
EXTERIOR NONBEARING WALLS 0 HOURS 11. FIRE DAMPERS WITH FUSIBLE LINKS SHALL BE FIXED IN ALL DUCTS AT ALL FLOOR CROSSINGS, WALL CROSSING OF PANTRIES

C.FINISHING MATERIALS EXTERIOR WALLS/CLADDING- NAT. STONE,PLASTER & PAINT


& CROSSING OF FIRE RATED WALLS.FIRE STOPS SHALL BE APPLIED ON ALL PENETRATION OF FIRE RATED WALL & FLOOR
ASSEMBLIES & GLASS-SLAB CLADDING INTERSECTION AS PER NFPA 251. COVER PAGE
12. ELEVATORS SHALL BE ACCORDANCE SECTION 9.4 NFPA 101.
INTERIOR FINISHING EXIT CORRIDOR/LOBBY OTHER SPACES
OTHER FIRE SAFETY PROVISIONS
I I I I I I
I I I I I I
I I I I I I
I I I I I I

WALLS CLASS A OR B I , II CLASS A , B , I , II A , B OR C


FLOORS CLASS A OR B I , II CLASS A , B , I , II A , B OR C FIRE FIGHTING (FF)
FIRE ALARM (FA) 1641/14
CEILING CLASS A OR B I , II CLASS A , B , I , II A , B OR C
AIR CONDITIONING, VENTILATION AND SMOKE CONTROL SYSTEM CONTROL DIAGRAM MV-00