Vous êtes sur la page 1sur 2

053-049  

Typical Wiring Diagram ISSUE 6 DEEP SEA ELECTRONICS

9000 Battery Charger Installation Instructions

DANGER OF DEATH : LIVE PARTS exist within the DSE9000 enclosure.


The enclosure cover must not be removed.
BOOST not available on
DSE9150 12V 2A CF not available on
DSE9155 30V 2A x 12V 2A
DSE9150 Installation
NOTE : The DSE9000 series battery charger should only be used to charge
one battery bank at a time. It is not recommended to parallel batteries as the
tolerance of the batteries leads to imbalance in the charging of the batteries.

The DSE9000 battery charger is designed to be mounted within a control panel, on


the panel DIN rail utilising the integral mounts or on a chassis utilising the mounting
holes. For dimension and mounting details, see overleaf.
The DSE9000 battery charger is fit-and-forget. It can be permanently connected to the
supply and the load, with no requirement to disable the charger during times of heavy
load (such as engine cranking) or when in parallel with a charging alternator.

Battery suitability
The charger is factory set by DSE to suit Lead Acid batteries but can be adjusted at
the time of ordering to suit other battery types. Care should be taken to ensure the
batteries connected to the charger are of the correct ‘technology’ to suit the setting of
the charger.

Connection type Screw terminal, rising clamp, no internal spring


Indications
The DSE9000 Battery Charger features an Red LED indicator to show Status.
Min cable size 0.5mm² (AWG 20)
Max cable size 2.5mm² (AWG 14)
Function Action
Recommended AC fuse
Charger • Off when AC supply is not present.
DSE9130 12V 5A charger 2.0A anti-surge
DSE9140 12V 10A charger N/A (Internally fitted)
Status • Steady during normal operation with AC supply above minimum
DSE9150 12V 2A charger 1.5A anti-surge operating voltage.
DSE9155 30V 2A charger 2.5A anti-surge • Slow flashing when connected to an operating charging alternator.
DSE9250 24V 3.7A charger 2.5A anti-surge • Fast pulsing during overload conditions.
DSE9260 24V 10A charger N/A (Internally fitted)
DSE9255 24V 5A charger 3.5A anti-surge Boost Mode (Not applicable to DSE9150 12V 2A or DSE9155 30V 2A)
Recommended cable
Refer to operator manual DSE part number 057-085 CAUTION : Boost mode is intended for equalisation of the cells in lead
size
acid batteries and should not be operated when the battery charger is
Deep Sea Electronics Plc. Deep Sea Electronics inc. Deep Sea Electronics Plc. connected to other battery types or when the charger is used as a power
Tel:+44 (0)1723 890099 Phone: +1 (815) 316-8706 (Far East)
Fax: +44 (0)1723 893303 Fax: +1 (815) 316- 8708 Tel:+66 2 670 6228
supply only. If in doubt, consult your battery manufacturer.
LO CALL (from UK BT landlines) TOLL FREE (USA only) : Fax: +66 2 678 3028
Telephone 0845 260 8933
Email: support@deepseaplc.com
Tel: 1 866 636 9703
Email: support@deepseaplc.com
Boost mode is operated by connecting the BOOST terminals together (for instance
Email: dsesales@deepseausa.com
Web: www.deepseaplc.com Web: www.deepseausa.com
Web: www.deepseaplc.com with an external switch or timer circuit). This will raise the battery charger floating
voltage by 0.8V DC.
Dimensions and Mounting Dimensions and Mounting Dimensions and Mounting
DSE9130 12V 5A DSE9150 12V 2A DSE9140 12V 10A
DSE9155 30V 2A DSE9260 24V 10A
DSE9250 24V 3.7A
DSE9255 24V 5A

Overall size 136.48mm x 140.41mm x 63.40mm Overall size 108.03mm x 101.10mm x 48.6mm Overall size 152mm x 188mm x 2.44mm
(5.37” x 5.53” x 2.5”) (4.25” x 3.98” x 1.91”) (6” x 7.4”x 2.44”)
Weight 0.5kg Weight 0.16kg Weight
Mounting type DIN rail or chassis mounting Mounting type DIN rail or chassis mounting DSE9140 12V 10A 0.75kg
Din rail type EN 50022 35mm type only Din rail type EN 50022 35mm type only DSE9260 24V 10A 0.85kg
Mounting holes Suitable for M4 Mounting holes Suitable for M4 Mounting type DIN rail or chassis mounting
Mounting hole 119.36mm x 128.36mm (4.7” x 5.05”) Mounting hole 91mm x 89mm (4.25” x 3.51”) Din rail type EN 50022 35mm type only
centres centres Mounting holes Suitable for M4
Input voltage DSE9250-001 24V 3.7A 110V-240V Input voltage 110V-240V Mounting hole centres 142mm x 128mm
(nominal) DSE9250-002 24V 3.7A 110V-277V (nominal) (5.59” x 5.0”)
DSE9130 12V 5A 110V-277V Input voltage 90V-250V Input voltage (nominal) 110V-277V
DSE9255 24V 5A 110V-277V (absolute range) Input voltage 90V-305V
Input voltage DSE9250-001 24V 3.7A 90V-265V Charge failure relay 3A DC resistive, 30V maximum (absolute range)
(absolute range) DSE9250-002 24V 3.7A 90V-305V rating Charge failure relay rating 3A DC resistive
DSE9130 12V 5A 90V-305V Operating -30°C to 55°C 30V maximum
DSE9255 24V 5A 90V-305V Temperature (-22°F to 131°F) Operating Temperature -30°C to 55°C
Charge failure 3A DC resistive, 30V maximum (-22°F to 131°F)
relay rating
Operating -30°C to 55°C
Temperature (-22°F to 131°F) 6 in 2.44 in

7.4 in
Dimensions in mm unless stated

Dimensions in mm unless stated

Dimensions in mm unless stated

This document is intended as a ‘quick start’ guide only. For full operating instructions and specifications, refer to operator manual DSE part number 057-085