Process controller
Setpoint programmer
1/16 DIN - 48 x 48 mm
The specifications in this document may therefore be changed without notice Modbus® is a trademark of AEG Schneider Automation
ASCON spa
Via Falzarego, 9/11 - 20021 Baranzate - (Milano) Italy - Tel. +39 02 333 371 - Fax +39 02 350 4243
http://www.ascon.it e-mail info@ascon.it
BT-M5-ING 13-02-2006 15:33 Pagina 4
gammadue®
the right solution to your needs
Setpoint Tuning
Modbus RS485
Parameterisation One shot Adaptive
Supervision Auto tuning
(option)
Digital inputs (IL1, IL2) functions
2
BT-M5-ING 13-02-2006 15:33 Pagina 5
Technical data
Features Description Input type Scale range
at env. 25°C
-200…600 °C
Total The choices are: input type, operating mode, type of control, safety strategies, RTD -328…1112 °F
configurability alarm strategies Pt100Ω at 0°C -99.9…300.0 °C
Operating 1 loop with single/double output -99.9…572.0 °F
modes 1 loop as the latter with the addition of the Setpoint programmer RTD -50.0…50.0 °C
PID with overshoot control or ON-OFF 2xPt100Ω at 0°C for ∆T -58.0…122.0 °F
Algorithm
PID with valve algorithm, for controlling motorised valves T/C type L 0…600 °C
Proport. band (P) 0.1…999.9% Fe-Const. 32…1112 °F
Integral time (I) 1…9999 s User PID control T/C type J 0…600 °C
Derivative time (D) 0.1…999.9 s enabled/disabled Fe-Cu 45% Ni 32…1112 °F
Manual reset 0…100% output User enabl./disabled P and PD control T/C type T -200…400 °C
Cycle time 0.2…30.0 s Time prop. control Cu - CuNi -328…752 °F
Hysteresis 0.1…5.0% ON-OFF control
Control mode T/C type K 0…1200 °C
Dead band 0.0…5.0% Cromel Alumel 32…2192 °F
Cool Proport. band 0.1…999.9%
T/C type R 0…1600 °C
Cool Integral time 1…9999 s User Heat-Cool control Pt13%Rh-Pt 32…2912 °F
Cool Der. time 0.1…999.9 s enabled/disabled
T/C type S 0…1600 °C
Cool cycle time 0.2…30.0 s Pt10%Rh-Pt 32…2912 °F
Motor travel time 15…600 s
0/4…20 mA, 0…50 mV Configurable engineering units
Motor minim. step 0.1…5.0% Motorised valves
0/1…5 V, 0…10 V mA, mV, V, bar, psi, Rh, ph
Feedback potent. 100Ω…10kΩ
mV Custom scale On request
A/D converter with resolution of 160.000 points
Update measurement time: 50 ms Table 1 : PV input
Common
Sampling time (max. update time of the output adjustable):
characteristics
0.1…10.0 s configurable - Input shift : 60…+ 60 digit
Input filter with enable/disable: 0.1...999.9 s
Accuracy
0.25% ± 1 digits for temperature sensors Between 100…240V~
0.1% ± 1 digits (for mA and mV) the error is minimal
Resistance Pt100Ω a 0°C Max. wire res.: 20Ω
thermometer (IEC 751) 2 or 3 wires or (3 wires)
PV input (for ∆T: R1+R2 °C/°F 2 Pt100 for ∆T 0.1 °C/10°C Env. t.
(for signal must be <320Ω) selectable <0.1°C/10Ω Wire res.
ranges
see table 1) L,J,T,K,R,S Max. wire res:
(IEC 584) Internal cold junction 150Ω Sensitivity
Thermocouple
°C/°F compensation <2µV/°C Env. t.
selectable <5µV/10Ω Wire res.
0/4…20mA Engineering units
DC input (current)
Rj = 30Ω Decimal point conf. Input drift:
–
0…50 mV with or without √ <0.1% / 20°C
Rj = 10MΩ Initial Sc.: -999…9999 Env. temperature
DC input (voltage) Full Sc.: -999…9999 <5µ/10Ω Wire res.
1...5/0...5/0...10V
Rj = 10KΩ (minim. range 100 digits)
Current
0/4…20mA Bias in engineering units and ± range
Remote Setpoint Rj = 30Ω
Not isolated
accuracy 0.1% Voltage Ratio from -9.99…+99.99
1...5/ 0...5/ 0...10V
Auxiliary inputs Rj = 300KΩ Local + Remote Setpoint
(options)
max. span Display from 10 to 200 A
CT current
50 or 100 mA resolution of 1A with alarm threshold
transformer
hdw selectable (Heater break alarm)
100Ω…10KΩ Position feedback
Potentiometer
supply. 300mV measurement
The closure of Auto/Man mode change, Local/Remote
the external Setpoint mode change, Stored Setpoints
contact activation, keypad lock, measure hold and
Digital inputs 2 logic slopes inhibit.
produces any
of the following Start, stop, hold of a program
actions (only with Setpoint programmer)
Single or double channel, direct or reverse action
Control output
Minimum limit 0…100.0% (OP1 heat)
(analogue)
Maximum limit 0…100.0% (OP1 heat), -100.0…0% (OP2 cool)
3
BT-M5-ING 13-02-2006 15:33 Pagina 6
Technical data
Features Description Electrical wirings
at env. 25°C
Max. slope 0.01…99.99%/s up and down
Safety value -100…100%. User enabled/disabled
2 Relays SPST NO, 2A/250Vac resistive loads (4A/120Vac)
Time 2 Triacs 1A/250Vac resistive loads
proportioning 0…22Vdc, 20mA max. Galvanic isolation
SSR drive
Control output (for static switches) 500Vac/1min
Current 0/4…20mA max. 750Ω/10Vmax. 12 bit (0.025%)
Analogue Accuracy 0.1%
(optional) Voltage 0…1/5/10V 500Ω/20mA max. Short circuit protection
Motorised valve (3 states) Double action
Raise - Stop - Lower 2 poles NO, 2A/250Vac resistive load
SPST NO, 2A/250Vac resistive load - hysteresis 0.1…5.0% symmetrical
Active high Action Deviation threshold ± range
Band threshold 0…range
Active low type Absolute threshold Whole range
Alarms
Action Heater Break detection
Loop Break Alarm
Special
Activation inhibit (blocking)
functions
Acknowledge (latching)
Related to the program (optional) (OP3)
Galvanic isolation 500Vac/1min Current: 0/4…20mA
Analogue
Resolution: 12 bit (0.025%) 750Ω/10V max. Retransmission
output OP4
Accuracy: 0.1% Voltage: 1...5/0...5/0...10V of PV or SP
(optional)
Short circuit protected 500Ω/20mA max.
Ramp up and down, with Local plus 2 stored Setpoints
slope in digit/s, digit/minute Only Remote
or digit/hour between Local and Remote
Setpoint
0.0…10.0% Local with trim
of the range Remote with trim
High and low limits Time programmable (optional)
Programmable 1 program, 16 segments (1initial and 1 end)
Setpoint From 1 to 9999 cycles or continuous cycling (OFF)
(optional) Time values in seconds, minutes and hours
Start, stop, hold, etc. activated from the keypad, digital input and serial comm.s
One shot tune-step response method for calculating the PID terms parameters
Tuning Adaptive tune self-learnig, not intrusive, analysis of the process response to
disturbances and continuous calculation of the PID parameters (not available
with the Setpoint Programmer option) Dimensions
Auto/Manual Integrated in the controller, bumpless
station Operated from keypad, digital inputs and serial communications
Serial comm.s RS 485 isolated, Modbus/Jbus
(optional) 1,200, 2,400, 4,800, 9,600, 19,200 bit/s, 2 wires
Auxil. supply 18Vdc ±20%, 30mA max. for transmitters (2, 3, 4 wires)
Measure Detection of out of range, short circuit or sensor break with
input automatic activation of the safety strategies and alerts on display
Control output Safety value:-100…+100%, (user enabled/disabled)
Parameters and configuration data are stored in a non volatile
Operational memory for an unlimited time. They are organised in
safety Parameters
functionally homogeneous groups, as: visible and changeable,
visible and not changeable, not visible
Access Password to access the configuration data and the parameter
protection protection menu
100...240Vac (-15...+10%) 50/60Hz or 24Vac(-25...+12%), 50/60Hz
Power supply
and 24Vdc (-15...+25%). Power consumption 3W max .
Safety Compliance EN61010-1 (IEC 1010-1), inst. class 2 (2,5kV), poll. class II
Electromagnetic Compliance to the CE standards for industrial system and
compatibility equipment
General
UL and cUL
characteristics File E176452
Approval
Protection
IP65 front panel
EN60529 (IEC 529)
1
Dimensions /16 DIN - 48 x 48, depth 150 mm, weight 230 g approx.
4
BT-M5-ING 13-02-2006 15:33 Pagina 1
5
BT-M5-ING 13-02-2006 15:33 Pagina 2
Ordering codes
Line Basic model Accessories
Model: M5 A B C D – E F G 0
Power supply
Outputs
Serial comm.s/Options
The specifications in this document may therefore be changed without notice - Modbus® is a trademark of AEG Schneider Automation
Setpoint
Instr. handbook
Colour
Power supply A
100...240Vac (-15...+10%) 3
24Vac (-25...+12%) or 24Vdc (-15...+25%) 5
Setpoint Programmer E
Not fitted 0
Fitted (adaptive-tuning not available) 1
Instruction handbook F
Italian-English (std) 0
French-English 1
German-English 2
Spanish-English 3