Académique Documents
Professionnel Documents
Culture Documents
Introduction..................................................................................................................................................... v
Performance Objective ............................................................................................................................. v
PERFORMANCE OBJECTIVE
After completing this module, you will be able to discuss relevant communication technologies with your
customers and recommend communication technology strategies to your customers.
Output signal
Sensor
The sensor interacts with the process variable and converts it to an
electrical signal usable by a signal processor (i.e. transmitter). For
example, a pressure sensor might convert pressure into millivolts.
Signal Processor
Within a transmitter, a signal processor accepts the raw electrical signal
from a sensor, performs calculations on the signal according to preset
values (e.g., range, span), and sends out a new electrical signal suitable
for transmitter output.
Digital-to-Analog Converter
Prior to sending the output signal, the transmitter may convert a
digital value (used internally by the signal processor) to an analog 6. The job of an A/D converter is
value. Transmitters convert digital values to analog values because: to convert analog signals into
_____________ signals.
❑ Many process control devices—including control systems—can
only interpret analog signals
❑ Analog signals can convey process information much more 1. electrical
rapidly than digital signals 2. pneumatic
A digital-to-analog (D/A) converter changes a digital signal into an 3. digital
equivalent analog signal.
Analog
process
value
Sampled
digital 12. Which are the commonly used
values
digital communication protocols?
Select all options that apply.
Digital
process 1 4-20 mA
value 2 FOUNDATION fieldbus
3 HART
Figure 8.2: Digital Process Values 4 Profibus
Note: To answer the activity questions the Hand Tool (H) should be activated.
1 250 ohms
2 500 ohms
3 1000 ohms
4 1100 ohms
D/A converter
Output signal
A/D converter
Signal
processor
Digital information
(i.e, HART values)
Process Sensor
Variable
Analog
transducer
signal 1 Sampling rate
2 Sampling precision
3 Quality of the signal processor
Sampling
precision 4 Quality of the original A/D
(10 steps) conversion
Analog output
1 2 3
Time (seconds)
Burst Mode
Burst mode is a user-selectable HART option that enables the HART
device to continuously send data without the primary host requesting
the data. In normal mode, a HART device can typically complete two 6. The purpose of burst mode is to
message transactions per second; in burst mode, a HART device can enable the HART device to
complete three or more message transactions per second. __________ _____ data that is not
requested by the primary host.
The Model 333 Tri-Loop® also uses burst mode transmission to receive
data from multivariable transmitters. The Tri-Loop converts the burst
mode data into three analog signals that can be used by non-HART 1. continuously erase
control systems. 2. continuously send
3. intermittently send
MULTIPLE PROCESS VARIABLES
HART-capable transmitters send two output signals simultaneously: a
regular analog output signal and a digital HART signal overlayed on
the analog signal. Therefore, HART-capable transmitters can send two
(or more) process variables at the same time. The HART digital signal
alone is capable of sending up to four variables simultaneously to
support multivariable transmitters and more complex devices
(e.g., analyzers, valve positioners).
TRANSMITTER SELF-DIAGNOSTICS
The digital electronics in a HART-capable transmitter allow the
transmitter to periodically run its own self-test suite. If the transmitter
locates a problem, it can communicate the error condition in its digital
HART information.
8. What is the maximum
Transmitter self-diagnostics can significantly aid technicians with allowable number of
device maintenance by proactively reporting problems to a control transmitters that can coexist on
system. a multidrop network?
MULTIDROP NETWORKING
1 5
Analog-only transmitters must be individually wired to a control 2 10
system. By contrast, up to 15 HART-capable transmitters can share a 3 15
single analog loop in a networking configuration called multidrop. 4 20
Figure 8.7 shows a HART multidrop network. When on a multidrop
network, transmitters can only communicate using digital HART
signals; the analog signal for each device is fixed at 4 mA.
2 3 4 1
HART-capable transmitters
HART Communicators
The most common tool used to configure and test HART-capable Activities
transmitters is a HART communicator, such as the Rosemount
Model 275. HART communicators can engage in two-way 11. Where can a HART communicator
communication with any HART-capable transmitter on a loop. be connected in a control loop?
Note: To answer the activity questions the Hand Tool (H) should be activated.
User layer
.
e
Physical layer
FF network
Physical Layer
The physical layer handles the physical connections necessary to
enable FF communication. The wiring connections for power and
data exchange are part of the physical layer. The physical layer
converts signals between the FF network and the communications
stack.
The physical layer of an FF network segment can be either H1,
which operates at 31.25 Kbits/second, or FF HSE (high-speed
ethernet), which operates at 100 Mbits/second or faster. H1 and HSE
were specifically designed as complementary networks. H1 is
optimised for traditional process control applications using two-wire,
bus-powered devices. HSE is designed for use with field-powered
devices that have large amounts of data to transmit. HSE can also
provide interconnectivity for high-data/high-performance control
applications and plant information integration.
User Layer
1 It handles network
The user layer controls the transmitter-human interface elements, communication.
such as transmitter configuration and alarms. The user layer is 2 It controls the
represented as function blocks. Function blocks are programming transmitter-human interface
segments that can be logically linked together to produce transmitter elements.
functions. For example, two input blocks that hold the data from two 3 It regulates the flow of signals
temperature sensors can be linked into a mathematical block that to different Fieldbus blocks.
averages the two temperatures. 4 It programs segments that can
be logically linked together to
FOUNDATION FIELDBUS BLOCKS produce transmitter functions.
Transducer Block
The transducer block is the interface between a sensor and the
5. The transducer block provides
function blocks in the transmitter—function blocks can only interact
information about a device's status to
with sensor data through the transducer block. A transmitter usually
control systems. Is this statement true
has one transducer block for every sensor to which the transmitter
or false?
connects. However, some devices allow a single transducer block to
handle multiple sensor values.
Transducer blocks are used to define the sensor type, perform sensor
calibrations, configure LCD displays, support diagnostic functions,
and perform other tasks.
1 Function block
2 Resource block
3 Transducer block
PROTOCOL DESIGN
FF is the only all-digital device communication protocol specifically
designed for the process control industry. As such, it offers better
process control tools (i.e., function blocks) and more useful
communication, network, and safety options than other protocols.
Furthermore, FF is an open protocol—it is openly published and not
controlled by a single vendor. Therefore, users of FF technology can be
assured that the technology will remain stable and well supported by
their suppliers.
1 Redundancy
2 Reduced control costs
3 Greater control adaptability
4 Increased safety
5 Increased reliability
Spur
4 59 m (197 ft)
Terminator
Junction box
Tree
Daisy chain
Branch
Point-to-point
Note: To answer the activity questions the Hand Tool (H) should be activated.
Network master
device
Profibus- PLC
DP Power 1 Profibus-FMS
supply
Profibus- 2 Profibus-DP
PA 3 Profibus-PA
DP to PA
converter
Discrete
devices Control
valves and
transmitters
PROFIBUS-FMS
Profibus-FMS (Fieldbus Message Specification) is a high-level
protocol that is designed for communication between network master
devices (devices that control communication on network segments).
Profibus-FMS is a multimaster protocol—any or all of the devices on
the network can be masters. Profibus-FMS communicates using
high-speed signals like FF HSE.
Note: To answer the activity questions the Hand Tool (H) should be activated.
1. current
2. frequency
3. voltage
HART, FoxCom, and BRAIN use essentially the same frequency 1 Being an open protocol
shift keying method of overlaying digital information onto an analog 2 Being controlled by single
signal. All three protocols can be used via a communicator connected vendors
anywhere in the control loop. 3 Being widely adopted in the
industry
HART technology has two important benefits that FoxCom and
4 Communicator connected
BRAIN do not have. HART technology is:
anywhere in the loop
❑ An open protocol
❑ Widely adopted in the industry
Open Protocol
Both FoxCom and BRAIN are controlled by single vendors, which
threatens to lock customers into devices manufactured by that
vendor. HART technology is an open protocol that is not owned by a
single vendor, which frees customers to choose devices from any
manufacturer that supports the protocol. HART is supported by over 7. Customers view HART
140 companies, including Foxboro and YEW. technology as a stepping-stone to
__________ technology.
(1) Interprets sensor data and transfers the data to a control room.
(2) Rectifies sensor failures from the control room.
(3) Enables technicians to remotely configure transmitters.
(4) Reports transmitter problems to a control room.
2. How does “control in the field” change the way the process control industry uses
communication technology?
(1) Engineers can develop sophisticated control strategies that happen right at
the measurement device.
(2) Plants can rely much less on central control systems.
(3) Providing improved loop integrity reduces the need for redundant controllers
and redundant I/Os.
(4) Permits multiple devices to exchange process control information
simultaneously.
(5) Local loops are “safer” – modifying them (or failure of one loop) does not
have to affect the rest of the plant network.
(1) controller
(2) sensor
(3) transmitter
(1) 4 – 20 mA _____
(2) HART® _____
(3) FOUNDATIONTM Fieldbus _____
(4) 1–5V _____
(5) 3 – 15 psi _____
(1) Digital transmitters require less wiring, and are therefore cheaper to install.
(2) Digital transmitters are more accurate so money will be saved through
improved process control.
(3) Digital transmitters offer the advantage of self-calibration.
(4) Technicians can communicate with digital transmitters remotely.
(1) Requires a minimum 250 ohms resistance in the loop to establish HART
communication.
(2) The transmission rate is 2200 bits per second.
(3) Requires no loop resistance to establish HART communication.
(4) Uses two different frequencies to indicate 1 and 0.
1. If the sampling rate changes from 10 samples per second to 20 samples per second,
what will happen to the digital process value?
(1) The digital process value will have twice as many steps.
(2) The digital process value will decrease by half.
(3) The digital process value will be unaffected.
(4) The digital process value will decrease marginally.
2. If the analog signal changes to a flat line, the digital value will also become a flat line
that matches (or very nearly matches) the analog signal. Is this statement true or
false?
(1) True
(2) False
(1) frequently
(2) never
(3) rarely
4. What general statement can you make about data loss in A/D conversions based on
this illustration?
(1) A/D converters with high sampling rates and sampling precision will not loose
any data during the conversion process.
(2) A/D converters with high sampling rates and sampling precision can lose
some data during the conversion process.
(3) A/D converters with low sampling precision lose data during the conversion
process.
(4) A/D converters with low sampling rates lose data during the conversion
process.
(1) HART transmitters can be used with the existing equipment that uses the 4-
20 mA signaling standard.
(2) HART transmitter only deals with digital communication and since analog
signal is not required, wiring and control system costs are reduced.
(3) HART transmitters can be connected in multidropped networks, which can
save on wiring and control system costs.
(4) Unlimited mulitdropping of HART transmitter in a single loop.
(5) HART transmitters run their own self-diagnostics, thereby reducing expensive
downtime.
2. HART devices fulfill the role of digital devices and provide advanced functions like
“control in the field”. Is this statement true or false?
(1) True
(2) False
(1) sensors
(2) communicators
(3) transducers
3. HART communicators are quick and easy to upgrade with new device descriptions.
Is this statement true or false?
(1) True
(2) False
(1) X _____
(2) Y _____
(3) Z _____
(A) User layer – Contains function blocks that can be linked together to provide
process control features
(B) Physical layer – Defines the hardware connection of the transmitter to the
fieldbus network
(C) Communications stack – Handles transmitter communication on the fieldbus
network
(1) FOUNDATION Fieldbus devices offer complete remote control and require no
wiring, leading to a complete reduction of wiring costs.
(2) FOUNDATION Fieldbus devices require far less wiring than analog
transmitters, which can lead to substantial cost savings.
(3) FOUNDATION Fieldbus devices can run on the wiring of an already setup
analog system without terminators and power conditioners.
(4) FOUNDATION Fieldbus technology allows unlimited number field devices to
be multidropped in a single segment, which can lead to substantial cost
savings.
2. FOUNDATION Fieldbus devices, are interoperable by design. Any device from any
manufacturer can communicate with any other device. Is this statement true or false?
(1) True
(2) False
3. FOUNDATION Fieldbus devices __________ the need for large, central control
systems and their attendant network of wires. FOUNDATION Fieldbus devices can
handle many control responsibilities by__________.
(1) True
(2) False
(1) W _____
(2) X _____
(3) Y _____
(4) Z _____
(1) True
(2) False
(1) A safety barrier must be placed between the intrinsically safe and non-safe
segments.
(2) The intrinsically safe and non-safe segments must have separate wiring
properties.
(3) The number of devices on an I.S. segment is unlimited.
(4) The device must be certified as I.S.
4. The link active scheduler (LAS) need not necessarily be in the control room. The LAS
can be virtually anywhere on the network. Is this statement true or false?
(1) True
(2) False
(1) HART technology is an open protocol that allows the customer to obtain
devices from any manufacturer.
(2) HART transmitters require less network wiring as compared to FoxCom
Transmitters.
(3) HART technology is widely adopted in the industry and this ensures that the
technology will be supported in the future.
(4) FoxCom transmitters do not support analog signals as they handle only digital
communication.
How will you convince the customer that in comparison to Honeywell DE, HART
technology is a better stepping-stone to Fieldbus?
(1) HART technology allows the customer to keep his existing analog technology
while he introduces new digital technology. DE requires him to abandon his
analog technology immediately.
(2) HART devices can transmit multiple digital variables simultaneously. DE can
only send one.
(3) HART devices can be configured by technicians in the field or on the bench
with a communicator. DE devices are factory programmable and cannot be
configured in the field.
(4) HART technology is an open protocol, which will not lock the customer into a
single supplier. DE is proprietary and requires the customer to buy devices
from Honeywell.
(5) HART technology is widely adopted in the industry, ensuring broad support.
How will you convince the customer that FOUNDATION Fieldbus is the best solution
for his long-range plan for a fieldbus-only plant? (Select all options that apply)
1. 1, 3, 5
2. 1, 2, 3, 5
1. D, C, B, A
2. 2
3. 1, 4
1. 1, 2, 1
2. 1, 4
1. 1
2. 1
3. 1
4. 2
1. 1, 3, 5
2. 2
3. 2
1. 1, 2, 4
2. 2, 3
3. 1
1. A, C, B
2. C, A, E, D, B
3. D, A, B, C
1. 2
2. 1
3. 3, 2
4. 1
5. 1, 4
1. D, C, B, A
2. 2
3. 1, 3, 5
4. 1
1. 1, 3
2. 1, 2, 4, 5
3. 1, 2, 3, 5
1. True
2. 1,2,4
3. 1,3,4
4. 2
5. 2
6. 3
7. 1,4
8. 1
9. 1,2,4
10. 3
11. True
12. 2,3,4
13. 1,2,4
1. 3
2. 1
3. 1,2
4. 4
5. 1,2,3,5
6. 2
7. True
8. 3
9. 1,2,4
10. True
11. 4
12. 3
1. 1,3,4
2. False
3. 1
4. 2
5. False
6. 3
7. True
8. 2
9. True
10. 2,3,4
11. False
12. False
13. 1,2,3,5
14. 1
Profibus Protocol
1. 1,2,3
2. 3
3. 1,3
4. 1,2,4
5. False
6. 1
1. 1
2. True
3. 1
4. 2,3
5. True
6. 1,3
7. 3
8. 4
9. True
10. 1,3,4