Consultant :- Mitcon Consultancy & Engineering Services Ltd
EPC Contractor :- Enrich Energy Pvt Ltd
Project :- Proposed 20 MW Solar PV Project at Karnataka, India
End Customer :- Shri Keshav Cements & Infra Ltd
TECHNICAL SPECIFICATIONS Doc. No.: QMS/FOR/D&E/25
INVERTER DUTY TRANSFORMER Rev. No/ Date: 00/ 01.03.2017
Sr no Description Requirements
27 Cooling Equipments
a) Number of Banks As per GA Drg
b) No. of fans NA
28 Insulation level of bushings (As per IS3347 and IS 2099)
a) Lightning impulse withstand(KVP) HV-170KV (peak) LV-NA
b) Switching impulse withstand (KVP) NA AS per IS 2099
c) 1 Minute power frequency withstand voltage (KV rms) HV-70KV (rms) LV-3kV
d) Creepage distance (mm) 25mm/kV
** 29 Current Transformer details (HV1 & HV2 WTI)
a) Make As per make list
b) Type Ring Type , Tape wound
c) Ratio 48/3A
d) Burden 7.5VA
e) Accuracy Cl-3
30 Maximum no load loss (Iron loss) at rated voltage and at rated frequency in KW 5
31 Maximum load loss at rated current at rated frequency at 75 °C in KW 50
* 32 Terminal Arrangement
i) HV side Cable box with D.C
ii) LV side Cable box
33 Approx Weight
A.Core & winding in kg 6600
B.Tank & Fitting in kg 5200
C.Oil in kg 3100
D.Oil volume in ltr 3780
E. Total Weight in kg 14900
34 Approx. Overall Dimensions
A.Length 4620
B.Width 4300
C.Height 3200
35 Type of winding construction HV & LV Crossover & Spiral
36 Efficiency at Unity / 0.9(lag) / 0.8(lag) PF at 75 deg C
At 125 % 98.67 / 98.52 / 98.34
At 100 % 98.90 / 98.78 / 98.63
At 75 % 99.12 / 99.02 / 98.90
At 50 % 99.30 / 99.13 / 99.13
37 Maximum efficiency % & load 99.36 at 31.62%
38 Regulation at unity / 0.9 / 0.8 PF at 75 deg C % 1.2 / 3.84 / 4.75
39 Thickness of Tank (side/top/bottom) in mm 6/8/8
* 40 Shield between LV & HV winding ( dv/dt filter) Provided
* 41 Phase to Phase clearance in oil 18 mm
* 42 Magnetising current at 100% & 110% 1.5% & 4% (Approx)
*** 43 Winding material (HV & LV) Electrolytic Copper
*** 44 CRGO Grade & thickness Moh, 0.27
Note 1. Performance figures guaranted above are subject to tolerances as per IS 2016, Except losses
2. Efficiency and regulation values are calculated based on nominal values of NLL,LL & %Z.
3. Weights and dimensions are subject to +/- 10% tol
*4. Two CCA of 2.5 MVA each in one tank
Prd by - TP 2 of 2 Apprd by - SP
Date 01-11-2017
PCN ADA1720030 Rev 01
Rating 5000 KVA, 33/4 x 0.38KV 3 PHASE TRANSFORMER
Customer Enrich Energy Pvt Ltd
Make List
Sr no Fitting & assc Make
1 HV bushing (Porcelain) Genesis
*2 LV bushing (EPOXY) BARODA BUSHING
*3 Buchhloz relay VIAT/Atvus
4 Radiator Minar/Tarang/PE GURURAJ Radiatos Fresco Engg. CTR
5 Radiator valve Sarvodaya
6 Valves New Man Valve GEE CEE OSWAL GG VALVES
7 PRV T3 Sukrut VIAT/Atvus
8 MOG Sukrut VIAT/Atvus
9 OTI / WTI PECON Precimeasure
10 Breather Yogya Enterprises
11 NCT/WTI CT Starlite Electricals Bharati Electricals Trans Power Tech
12 OCTC Giriraj Electricals
* 13 Oil APAR Savita
14 Terminal in marshalling box Connectwell Elmax
15 Thermostat & Heater GIRISH(SAIEGO) POWER HEAT EGO
* 16 LV Busbar Raychem RPG
Prd by : TP 1 of 1 Apprd by : SP
COOLING AREA AND HEAT DISSIPATION CALCULATION
Page 1
PCN ADA1720030
Date 02.11.17
Rev 0
CALCULATION OF CROSS SECTIONAL AREA OF COPPER BUS BAR
AS PER IEC:60439(PART-1) 1999, ANNEX-B.
2
I t
SP =
κ
Where
2
Sp = Cross sectional area in mm
I = RMS value of a.c. fault current for a fault of negligible impedance = 40000 Amp -LV
25000 Amp -HV
2
Sp = 393.6 mm Required for LV Bus bars
2
Sp = 246.0 mm Required for HV Bus bars
2
Busbar Area provided for LV = 1200 mm
Page 1 of 1
Customer Enrich Energy Pvt LtdOFFERED TRANSFORMER 5000 kVA, 33 / 4 x 0.380 kV
Calculation Of Dynamic ability of transformer to withstand Short Circuit as per IEEMA guidelines:
Sheet 1 of 2
1) CALCULATION OF FIRST PEAK VALUE OF ASYMMETRICAL SHORT CIRCUIT CURRENT
2
E = 1.13 X 10^6 kg/cm for copper LV HV
Dmi = mean dia of inside winding in cm (LV/HV)= 30.9 42.4
bi = thickness of inside winding conductor= 0.34 0.218
Ns(HV)= 5.34
Ns(LV) = 2.95 Actual no. of supports provided = 12 + 12 dummy
Customer Enrich Energy Pvt LtdOFFERED TRANSFORMER 5000 kVA, 33 / 4 x 0.380 kV
Calculation Of Dynamic ability of transformer to withstand Short Circuit as per IEEMA guidelines:
Sheet 1 of 2
6) CALCUTATION OF INTERNAL AXIAL COMPRESSION FORCE : Sheet 2 of 2
Fc = ( - ) X 0.034 X Sn/( Zpu X hw ) in kg.
(- ve sign indicates that force is acting towards center)
Sn = Rated KVA 2500
Z p.u.= per unit impadance= 0.065
hw = winding height in cm = 82.1
Fc = 15.928 TONNES
FOR OUTER WINDING = 1/3*Fc = 5309.35 Kg
FOR INNER WINDING = 2/3*Fc = 10618.70 Kg
a = per unit turns out of circuit in winding = 0.1 (Per unit tapping)
N= NO. OF TURNS IN WINDING.=
Fa = 2715.61
2
Ai = Total supported area of inner radial spacer in cm = No of spacer x size of spacer= 93.6
2
Ao = Total supported area of outer radial spacer in cm = No of spacer x size of spacer= 220.8
278.48 MT