Vous êtes sur la page 1sur 2

QUIET-TEST™

H-100 Control Panel

DESCRIPTION
• Digital controls for all safety shutdowns

• Isochronous governor control built in

• Sealed Digital Circuit Board

• 2 Amp static battery charger

• Mates with HTS transfer switch and


any 2-wire start ATS

STANDARD FEATURES
The Quiet-Test™ H-100 Control Panel is a digital microprocessor In addition, the generator set parameters can be
electronic controller that integrates all engine and transfer switch manipulated and monitored without standing in front
functions into a single control system. of the control panel with GenLink® software. The Generac
• Two 4 line x 20 displays H-100 control also monitors and controls transfer switch
functions when used with the HTS Transfer Switch.
• Full system status
• Monitors utility voltage
• 3 phase sensing voltage regulator
• Monitors generator voltage
• Remote ports
• Timer for line interrupt delay
- RS232
• Timer for engine warmup
- RS485
• Timer for minimum engine run time
- Canbus
• Timer for return to utility position
• Water proof connections
• Timer for engine cooldown
• All engine sensors are 4-20 ma for minimal interference
• Built in exerciser timer (7 day)
• Built in PLC
• Additional 2 wire start controls for any 2 wire
transfer switch.
FEATURES QUIET-TEST™ H-100 Controller

• Full range stand-by operation • Shutdowns


• Full system status - Overvoltage
- 3 phase AC volts - Overspeed
- 3 phase amps - Low oil pressure
- kW - High coolant temperature
- Power factor - Low coolant level
- Reactive power • Remote communication
- Oil pressure - RS232
- Water temperature - Optional modem
- Water level - Canbus
- Oil temperature (optional) • Complies with NFPA Level 2
- Fuel pressure • Programmable auto crank
- Engine speed • Emergency Stop
- Battery voltage • On Off Manual Switch
- Alternator frequency • Not in Auto flashing light
- Time • Audible alarm for fault condition
- Date • Transfer switch logic communicates with HTS transfer switch
- Transfer switch status • Weekly exerciser (programmable)
- Run hours • Selectable Low speed exercise
- Service reminders • Digital voltage regulator with 3 phase sensing (3 phase units)
- Trending • Isochronous governor
- Fault history (alarm log) • Waterproof electrical connectors
- I2t function for full generator protection • Temperature Range -40° to 70° C
- Built in PLC for special applications

TYPICAL CONTROL CONNECTION

HTS
QUIET-TEST™ H-100 Controller Transfer
on Generator RS485 - 2 wire Switch
with ground
connection
for control

GENERAC® POWER SYSTEMS, INC. • P.O. BOX 8 • WAUKESHA, WI 53187


262/544-4811 • FA X 262/544-4851
Bulletin 0171340SBY / Printed in USA 03.05 © 2005 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.