Académique Documents
Professionnel Documents
Culture Documents
Contact us
ABB SACE The data and illustrations are not binding. We reserve
www.abb.com
SACE Emax
Low voltage air circuit-breakers
1
Main characteristics
2
Ranges
3
Installations
4
Overcurrent releases and relative accessories
5
Accessories
6
Circuit-breakers applications
7
Overall dimensions
8
Electrical circuit diagrams
9
Ordering codes
The new trip units, which are amazingly versatile and simple
to use, offer important innovations, such as the brand-new
intuitive operator interface allowing complete control of the
system with just a few simple keystrokes. Furthermore, there
are new protections, new alarms and connection to handheld
and laptop PCs using Bluetooth technology.
The re-engineered hardware architecture allows flexible and
Construction characteristics
Structure of the circuit-breakers 1/4
Operating mechanism 1/5
Operating and signalling parts 1/6
Fixed parts of withdrawable circuit-breakers 1/7
Utilization category 1/8
E1 E2
Automatic circuit-breakers
1 E1B E1N E2B E2N E2S E2L
Poles [No.] 3-4 3-4
4p c.-b neutral current-carrying capacity [% Iu] 100 100
800-1000- 800-1000- 1600-2000 1000-1250- 800-1000- 1250-1600
Size (40 °C) [A] 1250-1600 1250-1600 1600-2000 1250-1600-
2000
Ue [V~] 690 690 690 690 690 690
Icu (220...415V) [kA] 42 50 42 66 85 130
Ics (220...415V) [kA] 42 50 42 65 85 130
42 50 42 55 65 10
1SDC200058F0001
E1 CS E2 CS
Sectionalizing truck
Size (40 °C) [A] 1250 2000
Earthing switch with E1 MTP E2 MTP
making capacity Size (40 °C) [A] 1250 2000
E1 MT E2 MT
Earthing truck
Size (40 °C) [A] 1250 2000
(*) The performance at 1000V is 50kA.
Standard version 4 4 4
100 100 100
4000 3200-4000 4000-5000-
6300
690 690 690
80 100 100
80 100 100
80 85 100
75 75 100
E3N/MS E3S/MS E3V/MS E4S/MS E4S/f/MS E4H/MS E4H/f/MS E6H/MS E6H/f/MS
3-4 3-4 3-4 3-4 4 3-4 4 3-4 3-4
2500-3200 1000-1250-1600 800-1250-1600- 4000 4000 3200-4000 3200-4000 4000-5000- 4000-5000-
2000-2500-3200 2000-2500-3200 6300 6300
690 690 690 690 690 690 690 690 690
65 75 85 75 75 100 85 100 100
65 65 65 75 80 75 75 85 85
143 165 187 165 165 220 187 220 220
E3H/E E4H/E E6H/E
E3 CS E4 CS E6 CS
3200 4000 6300
E3 MTP E4 MTP E6 MTP
3200 4000 6300
E3 MT E4 MT E6 MT
3200 4000 6300
The sheet steel structure of the Emax air circuit-breaker is The depth of the withdrawable version is suitable for installation
1
extremely compact, considerably reducing overall dimensions. in switchgear 500 mm deep.
Safety is improved by using double insulation of the live parts and The width of 324 mm (up to 2000 A) in the withdrawable version
total segregation between phases. allows the apparatus to be used in switchgear compartments
The sizes have the same height and depth for all the circuit- 400 mm wide. Their compact dimensions also mean they can
breakers in each version. replace air circuit-breakers of any size from earlier series.
1SDC200019F0001
1SDC200019F0001
1SDC200018F0001
➁ OPENING ➀ OPENING
➂ OPENING
➀ CLOSING ➁ CLOSING
1SDC200020F0001
1SDC200021F0001
Fixed version
1
Caption
1 Trademark and size of circuit-
13 breaker
2 SACE PR121, PR122 or PR123
trip unit
3 Pushbutton for manual opening
2 4 Pushbutton for manual closing
5 Lever to manually charge closing
4 springs
3 6 Electrical rating plate
7 Mechanical device to signal
1 circuit-breaker open “O” and
closed “I”
8 Signal for springs charged or
9 discharged
9 Mechanical signalling of
5 overcurrent release tripped
10 Key lock in open position
11 Key lock and padlock in racked-
7 in/racked-out position (for
8 withdrawable version only)
12 Racking-in/out device (for
6 withdrawable version only)
16 13 Terminal box (for fixed version
1SDC200032F0001
only)
14 Sliding contacts (for withdrawable
version only)
15 Circuit-breaker position indicator:
racked-in/ test isolated /racked-
out / connected/test isolated/
disconnected (for withdrawable
version only)
16 Accessories label: the label
shows the circuit-breaker S/N and
accessories mounted inside the
Withdrawable version circuit-breaker
Note:
14 “Racked-in” refers to the position in
which both the power contacts and
auxiliary contacts are connected;
“racked-out” is the position in which
both the power contacts and auxiliary
2 contacts are disconnected; “test
isolated” is the position in which the
3 4 power contacts are disconnected,
whereas the auxiliary contacts are
connected.
1
10
7 8
6
5
15
1SDC200033F0001
11 12
Caption
1 Sheet steel supporting structure
2 Single earthing clamp mounted on
7 the left for E1, E2 and E3, double
6 earthing clamps for E4 and E6
3 Safety shutters (protection rating
IP20)
1 4 4 Terminal support base
5 Terminals (rear, front or flat)
6 Contacts signalling that the circuit-
breaker is racked-in, test isolated,
8 racked-out
7 Sliding contacts
8 Padlock device for safety shutters
(on request)
5 9 Fastening points (4 for E1, E2, E3
3 and 6 for E4, E6)
1SDC200022F0001
9 8 7 6b 6a 9 8 7 6 Caption
1 Sheet steel supporting structure
2 Current transformer for protection
trip unit
3 Pole group insulating box
4 Horizontal rear terminals
5-5a Plates for fixed main contacts
5b Plates for fixed arcing contacts
5b 6-6a Plates for main moving contacts
6b Plates for moving arcing contacts
5a 5 7 Arcing chamber
8 Terminal box for fixed version -
Sliding contacts for withdrawable
10 2 10 2 version
4 4 9 Protection trip unit
10 Circuit-breaker closing and
opening control
1SDC200023F0001
11 Closing springs
1SDC200024F0001
3 3
11 11
1 1
All the circuit-breakers are available in fixed and withdrawable, The availability of various types of terminals makes it possible
three-pole or four-pole versions. to build wall-mounted switchgear, or switchgear to be 1
Each series of circuit-breakers offers terminals made accessed from behind with rear connections.
of silverplated copper bars, with the same dimensions, For special installation needs, the circuit-breakers can be
regardless of the rated currents of the circuit-breakers. fitted with various combinations of top and bottom terminals.
The fixed parts for withdrawable circuit-breakers are common Furthermore new dedicated terminal conversion kits give
to each model, regardless of the rated current and breaking Emax maximum flexibility, allowing horizontal terminals to be
capacity of the relative moving parts, except for the E2S changed to vertical or front ones and vice versa.
circuitbreaker which requires a specific fixed part.
A version with gold-plated terminals is available for special
requirements, linked to use of the circuit-breakers in corrosive
environments.
Fixed circuit-breaker
1SDC200025F0001
1SDC200026F0001
1SDC200027F0001
Withdrawable circuit-breaker
1SDC200028F0001
1SDC200029F0001
1SDC200031F0001
1SDC200030F0001
Horizontal rear terminals Vertical rear terminals Front terminals Flat terminals
The overcurrent protection for AC installations uses three The protection system is made up of:
1 types of electronic trip unit series: PR121, PR122 and PR123. • 3 or 4 new generation current sensors (Rogowsky coil);
The basic series, PR121, offers the whole set of standard • external current sensors (i.e. for external neutral, residual
protection functions, complete with a user-friendly interface. current or source ground return protection);
It allows discrimination of which fault caused the trip by • a protection unit selected among PR121/P, PR122/P or
means of the new led indications. PR123/P with optional communication module via Modbus
PR122 and PR123 trip units are of new concept modular or Fieldbus plug network (PR122/P and PR123/P only), as
architecture. It is now possible to have a complete series of well as via a wireless connection;
protections, accurate measurements, signalling or dialogue • an opening solenoid, which acts directly on the circuit-
functions, designed and customisable for all application breaker operating mechanism (supplied with the protection
requirements. unit).
1SDC200034F0001
PR121
PR122
Communication opt.
Signalling opt.
Bluetooth (wireless link) opt.
PR123
PR123/P PR123/P
Protection
Features
1
Protection functions PR121 PR122 PR123
Second selective protection against short-circuit inverse or definite short time-delay trip •
residual • • •
Protection against earth fault
source ground return • •
(1)
Residual current opt.(2) •
RV (3)
Protection against residual voltage opt. •
Rating plugs
1
Max rated In [A]
Type of
uninterrupted
circuit-breaker 400 630 800 1000 1250 1600 2000 2500 3200 4000 5000 6300
current
800 • • •
E1B 1000-1250 • • • • •
1600 • • • • • •
800 • • •
E1N 1000-1250 • • • • •
1600 • • • • • •
1600 • • • • • •
E2B
2000 • • • • • • •
1000-1250 • • • • •
E2N 1600 • • • • • •
2000 • • • • • • •
800 • • •
E2S 1000-1250 • • • • •
1600 • • • • • •
2000 • • • • • • •
1250 • • • • •
E2L
1600 • • • • • •
2500 • • • • • • • •
E3N
3200 • • • • • • • • •
1000-1250 • • • • •
1600 • • • • • •
E3S 2000 • • • • • • •
2500 • • • • • • • •
3200 • • • • • • • • •
800 • • •
1000-1250 • • • • •
1600 • • • • • •
E3H
2000 • • • • • • •
2500 • • • • • • • •
3200 • • • • • • • • •
800 • • •
1250 • • • • •
1600 • • • • • •
E3V
2000 • • • • • • •
2500 • • • • • • • •
3200 • • • • • • • • •
2000 • • • • • • •
E3L
2500 • • • • • • • •
E4S, E4S/f 4000 • • • • • • • •
3200 • • • • • • •
E4H, E4H/f
4000 • • • • • • • •
3200 • • • • • • •
E4V
4000 • • • • • • • •
4000 • • • • • • • •
E6H, E6H/f 5000 • • • • • • • • •
6300 • • • • • • • • • •
4000 • • • • • • • •
E6V 5000 • • • • • • • • •
6300 • • • • • • • • • •
SACE Emax circuit-breakers and their accessories conform certification organization, and is certified by China CCC (China
to the international IEC 60947, EN 60947 (harmonized in Compulsory Certification) 1
30 CENELEC countries), CEI EN 60947 and IEC 61000
Standards, and comply with following EC directives: Certification of conformity with the aforementioned product
– “Low Voltage Directive” (LVD) no 73/23 EEC Standards is carried out in compliance with European
– “Electromagnetic Compatibility Directive” (EMC) nr. 89/336 Standard EN 45011 by the Italian certification body ACAE
EEC. (Associazione per la Certificazione delle Apparecchiature
The main versions of the apparatus are approved by the Elettriche - Association for Certification of Electrical
following Shipping Registers: Apparatus), recognized by the European organization LOVAG
– RINA (Italian Naval Register) (Low Voltage Agreement Group), and by Swedish SEMKO
– Det Norske Veritas certification organization recognized by the International
– Bureau Veritas organization IECEE.
– Germanischer Lloyd
– Loyd’s Register of Shipping
– Polskj Rejestr Statkow
– ABS (American Bureau of Shipping)
– RMRS (Russian Maritime Register of Shipping)
– NK (Nippon Kaiji Kyokai)
1SDC200038F0001
1SDC200037F0001