HINDALCO INDUSTRIES LIMITED

6 x 150 MW ADITYA AND MAHAN ALUMINIUM PROJECT

Technical Data
TURBINE & AUXILIARIES:
Sl. Unit of
Description Data To be Filled by vendor
No. Measurement

15.0 Generator
15.1 Design Code of Generator To specify TARI 1080-36Q
15.2 Maximum Continuous apparent power output at Cooling Water MVA 187.5
Temperature of 33 36 deg. C.
15.3 Maximum Continuous active power output at Cooling Water MW 150
Temperature of 33 36 deg. C.
15.4 Maximum Continuous Generator capability under one cooler out MW 150
of operation
15.5 Rated Voltage Volt 15.75
15.6 Permissible Voltage Variation +/- % +5, -5
15.7 Rated Stator Current Amp. 6873
15.8 Rated Power Factor LAG 0.8
15.9 Nominal Operating Frequency Hz. 50
15.10 Allowable Frequency band with respect to nominal 50 Hz. +/- % +3, -5
for continuous full load operation
15.11 Maximum reactive capability at rated speed & voltage As per reactive capability curve
15.11.1 At Rated power factor To specify TAC-3853
15.11.2 At Unity power factor To specify
15.12 Number of Terminal Broughtout No. 6 nos. from bottom
15.13 Class of Insulation for Stator Winding Class F
15.14 Class of Insulation for Rotor Winding Class F
15.15 Temp.-Rise of Winding Stator at MER Class B
Page 1 of 3
Sl. Unit of
Description Data To be Filled by vendor
No. Measurement
15.16 Type of Cooling Hydrogen/Air Air
Cooled
15.17 Declared total losses of machine 2245 KW
15.18 Guaranteed efficiency at 100% rated load:
15.18.1 At Rated power factor % 98.52
15.18.2 At Unity power factor % 98.8
15.19 Short Circuit Ratio 0.43
15.20 Synchronous reactance (sat/unsat) % 228.2 / 426.7
15.21 Transient reactance (sat/unsat) % 22.4 / 24.9
15.22 Sub-transient reactance (sat/unsat) % 15.18 / 18.75
15.23 Negative sequence reactance - sat % 17.22
15.24 Zero sequence reactance - unsat % 11.48
15.25 Permissible motoring time Seconds Not clear
15.26 Amount of unbalance in load it can safely carry % 8
15.27 Maximum value of sudden short circuit current kA 129.5 (no load)
15.28 Sustained three phase short circuit current, time in sec. kA-sec. 9.465 - 3 sec
15.29 Requirement of excitation power at MER kW 358.4
15.30 Material of stator core To specify CRNGO steel
15.31 Material of retaining ring To specify 18 18 Mn Cr
15.32 Weight of stator (maximum weight for erection) Kg. 185 tons
15.33 V/Hz PU Refer curve TAC-6840
15.34 Generator Losses:
15.34.1 At no load, Iron loss kW 325.4
15.34.2 At full load, Iron loss kW 325.4
15.34.4 Stator Copper loss kW 703.2
15.34.5 Rotor Copper loss
15.34.5.1 At no load kW LATER
15.34.5.2 At full load kW 313.5
15.34.6 Stray load loss kW Incl in iron loss
15.34.7 Friction and windage loss kW 885
15.35 Stator current % full load (overload performance) % As per curve TAC-5101

16.0 Exciter & AVR


16.1 Type of Exciter To specify Overhand brushless

Page 2 of 3
Sl. Unit of
Description Data To be Filled by vendor
No. Measurement
16.2 Rating kW Later
16.3 Rated Voltage Volt
16.4 Rated Current Amp.
16.5 Exciter loss kW
16.6 Voltage Rise during sudden rejection of full load at rated power
factor:
16.6.1 With AVR % 15
16.6.2 Without AVR % 42.96

Page 3 of 3