Académique Documents
Professionnel Documents
Culture Documents
6, NOVEMBEIUDECEMBER 1993
I. INTRODUCTION
I ..I..;i
\-:fvrw
~ i
.......... ...................... ........... !..I
L;. “.I..............................................t...
D ISTRIBUTION feeders constitute the major links be-
tween the power supply and the consumers. Normally, Fig. 2. An actual recorded waveform for a short-duration single-line-to-
when a temporary fault occurs, the feeder breaker trips and
ground fault.
GIRGIS et al.: A FAULT LOCATION TECHNIQUE FOR RURAL DISTRIBUTION FEEDERS 1171
4-Q
Fig. 4. Example one-line diagram
where TABLE I
AND CURRENT
SELECTEDVOLTAGE PAIRSOF A THREE-PHASE
FEEDER FOB IMPUTATION
Rapp is the apparent resistance seen at the recording device
Fault Type Eomp
xapp is the apparent reactance seen at the recording device. SLGF A 310
SLGF B 310
Thus for a single line to ground fault on phase A
SLGF C 310
Vselect = Vn
Iselect = ( I n + IO) = 181 + j I s ~ . (7 LLF (AB) AIa - AIb
or ABG
Making the proper substitutions yields
-
LLF (BC) AIb -AIc
or BCG
LLF (CA) AI, - AIa
or CAG
where Z1 is the total positive sequence impedance to the fault 3-Phase DLGF
point.
To compensate for the unknown fault resistance, the current
fed into the fault must be considered. For this particular
example, a single line to ground fault, the compensating
current is assumed to be proportional to the total zero sequence
current. The equation for apparent impedance may now be
expressed as
Single
(9) Lateral
Load
where
Fig. 5. Example of a single-phase lateral.
Icomp = the compensating current
Rf = the fault resistance form and can be applied to any fault type. Table I summarizes
z1 = the positive sequence impedance of the the necessary values required to calculate a fault location for
transmission line in (ohms or ps.)/mile each fault type.
D = the distance to the fault in miles.
A. Fault on a Single-phase Lateral
Equation (9) may be rewritten in terms of real and imaginary For single phase laterals, the possible fault types are limited
components [15]. Now (9) may be expressed as to single line to ground faults, as shown in Fig. 5.
The fault boundary condition may be described as
where The voltage drop and current changes are iteratively updated
for each line section.
lid, = the load current vector at bus i
V , = the voltage vector at bus i
C. Fault Location Test Case
xd, = the matrix representing the load admittance at bus i .
The fault location approach presented in this paper was
The matrix representing the load admittance may be given as tested using EMTP simulated data of a distribution system.
[: 2 $cl-
Figs. 7 and 8 show the faulted phase voltage and current
Ya 0 0
waveforms obtained from an EMTP simulation of a single
[xd,l= (20)
line to ground fault on phase A at seven miles along the main
feeder. Figs. 9 and 10 show the phasor magnitude and angle
The values of the diagonal elements represent the admit- estimates of the faulted phase voltage as a function of time
tance of that phase at bus i. The value of any diagonal element after the fault occurence. Figs. 1 1 and 12 show the phasor
may equal zero if that phase is not present at the load tap. magnitude and angle estimates of the faulted phase current as
In order to accurately calculate the load current at each bus, a function of time after the fault occurence. Fig. 13 shows
the updated bus voltages must be known. The updated voltage the fault location estimate as a function of time after the fault
vectors are calculated as follows occurence compared to the exact fault location. Fig. 14 shows
the fault location estimate for a fault along a single phase
[vi] = [Vabcl]- [V&] (21) lateral. For this case there were two possible fault locations,
where one at two miles along a single phase tap and the second was
approximately 3.4 to 3.5 mi along the main feeder. In Fig.
Vabcl is the voltage measured at the line terminal 14 the dashed line denoted with the letter M represents the
Vd, is the total voltage drop in the line sections up to bus i . fault location estimate along the main feeder. The solid line
denoted by the letter T represents the fault location estimate
The equation for the total voltage drop may be stated as from the tap location. The actual fault location is 3.5 mi from
the substation, 1.5 mi along the main feeder and 2 mi from the
tap location. The technique was tested for all types of faults at
different locations. Some of the results are shown in Table 11.
where
111. CONCLUSION
Zabcj is the series impedance of line section j
Fault location techniques are essential to speed system
Iabc, is the current flow in line section j. restoration and minimize power outages. Single-phase, two-
The current flow in line section j may be determined as phase, and three-phase branches should be considered in the
fault location technique. Unbalance, fault resistance, and load
currents are sources of inaccuracy. However, in the technique
1174 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 29, NO. 6, NOVEMBEFUDECEMBER1993
2;of. ,. , . , . , ., . , . ,. , .I
0 5 10 15 20 25 3 0 35 4 0 45
0.015 0.030 0.045 0.060 Time (msec)
Time (sec)
Fig. 12. Faulted phase current phasor angle estimate.
Fig. 8. Faulted phase current waveform.
- 4
6.5
10 15 20 25 30 35 40 I 5
Time (msec)
0 5 10 15 20 25 30 35 40 45
Time (msec) Fig. 13. Fault location estimate versus post-fault time.
3.30 I
-
8 3.25
3.20
3.15
3.10
3.05 j 1
3 . 0 0 - 1
0 5 10 15 20 25 30 35 40
Time (msec) 12 17 22 27 32
Fig. 10. Faulted phase voltage phasor angle estimate. Time (msec)
Fig. 14. Fault location estimates along the main feeder and lateral.
,
TABLE II
FAULTLOCATION
ESTIMATES
Location
7.03
0 5 10 1 5 20 2 5 30 35 4 0 4 5 REFERENCES
Time (msec)
Fig. 11. Faulted phase current phasor magnitude estimate,
[I] R. A. Fernandes et al., “Evaluation of conceptual distribution automa-
tion,” IEEE Trans. Power Apparat. Syst., vol. PAS-101, no. 7, pp.
2024-203 1, July 1982.
[2] IEEE Committee Report, ‘The distribution system of the year 2000,”
presented here, these errors were reduced by accounting for IEEE Trans. PowerApparat. Syst., vol. PAS-101, no. 8, pp. 2485-2490,
Aug. 1982.
loads, single phase branches, and the fault resistance. The [3] L. V. McCall, “Distribution automation demonstration project”, IEEE
results shown in this paper are promising. The authors are Trans. PowerApparat. Syst., vol. PAS-100, no. 4, pp. 1744-1751, Apr.
planning a comprehensive research program in this area. 1981.
[4] J. B. Bunch et al., “Generalized algorithms for distribution feeder
Further development will consider multiple single-phase and deployment and sectionalizing,” IEEE Trans. Power Apparat. Syst., vol.
multiphase branches. PAS-99, pp. 549-557, MadApr. 1980.
GIRGIS et al.: A FAULT LOCATION TECHNIQUE FOR RURAL DISTRIBUTION FEEDERS 1175
[5] P. C. Lyons and S . A. Thomas, “Microprocessor-based control of Christopher M. Fallon was born in 1966 in
distribution systems,” IEEE Trans. Power Apparat. Syst., vol. PAS-100, Audubon, NJ. He received the B.S. and M.S.
no. 12, pp. 48934899, Dec. 1981. ’ degrees in electrical engineering from Clemson
[6] EPRI, “Study of distribution system surge and harmonic characteristics,” University, Clemson, SC, in 1989 and 1990,
EPRI EL1627, Project 10241, Final Report, Nov. 1980. respectively.
[7] N. B. Johnson, “A quantitative study on current and voltage distortion in He is presently with the Duke Power Company,
a primary distribution feeder,” M.Sc. Thesis, NC State Univ., Raleigh, Charlotte, NC, working in the System Power Quality
1985. Section. His areas of interest include power system
[8] T. Takagi, Y. Yamakoshi, M. Yamaura, R. Kondow, and T. Matushima, protection and control and computer applications in
“Development of a new type fault locator using the one-terminal voltage power systems.
and current data,” IEEE Trans. Power Apparat. Syst., vol. PAS-101, no. He is a member of Eta Kappa Nu.
8, pp. 2892-2898, Aug. 1982.
(91 E. 0. Schweitzer, “A review of impedance-based fault locating expe-
rience,” presented at the 15th Ann. Western Protective Relay Conf.,
Spokane, WA, Oct. 1988.
[IO] A. A. Girgis and E. B. Makram, “Application of adaptive Kalman David L. Lubkeman (S’80-M’83-SM’92) was
filtering in fault classification, distance protection, and fault location born in St. Louis, MO, in 1957. He received the
using microprocessors,” IEEE Trans. Power Apparat. Sysr., vol. PAS- B.S., M.S.,and Ph.D. degrees in electrical engi-
106, no. 2, pp. 198-209, Feb. 1988. neering from Purdue University, West Lafayette,
[ l I] L. Erikson, M. M. Saha, and G. D. Rockefeller, “An accurate fault IN, in 1979, 1980, and 1983, respectively.
locator with compensation for apparent reactance in the fault resistance He joined the faculty of Clemson University,
resulting from remote-end infeed,” IEEE Trans. Power Apparat. Syst., Clemson, SC, in 1989, where he is presently
vol. PAS-104, no. 2, pp. 424435, Feb. 1985. Associate Professor of Electrical and Computer
[ 121 M. S. Sachdev and R. Agarwal, “A technique for estimating transmission Engineering. Prior to this he was an Assistant
line fault locations from digital impedance relay measurements” IEEE Professor at North Carolina State University,
Trans. Power Syst., vol. PWRD-1, no 2, pp. 242-251, Apr. 1986. Raleigh. His research focus is on computer
[13] A. A. Girgis, “A new Kalman filtering based digital distance relay,” applications in power distribution system analysis and design and computer-
IEEE Trans. Power Apparat. Syst., vol. PAS-101, no. 9, pp. 3471-3480, aided instruction.
Sept. 1982. Dr. Lubkeman is a member of the IEEE Power Engineering Society, the
[I41 K. Srinivasan and A. St-Jacques, “A new fault location algorithm for IEEE Computer Society, and the Association €or Computing Machinery.
radial transmission lines with loads,” IEEE Trans. Power Delivery, vol.
4, no. 3, pp. 16761682, July 1989.