Vous êtes sur la page 1sur 5

International Journal of Engineering and Techniques - Volume 3 Issue 5, Sep - Oct 2017

RESEARCH ARTICLE OPEN ACCESS

Simulation of Solar Thermal Cooling System for an Office Building


in Indian Climates using Evacuated Tube Collector
Bachchu Lal Gupta1
1
Department of Mechanical Engineering, Govt. Engineering College Bharatpur 321001 India.

Abstract:
The performances analysis of solar thermal cooling system for an office building using evacuated tube type collector
has been analyzed. The simulation was carried out for a typical office building considered to be located in four different
cities, representing four climatic zones of India namely Ahmedabad (Hot and dry), Bangalore (Moderate), Chennai (Warm
and humid) and Delhi (Composite). Results indicate that the highest solar fraction has been observed as 0.89, 0.94, 0.88,
and 0.93 for hot and dry, moderate, warm and humid and composite climate respectively. The primary energy savings are
higher for the moderate climate (Bangalore) and lowest for the warm and humid climate (Chennai).
Keywords — Solar thermal, Evacuated Tube Collector, Solar Fraction, Primary Energy Savings.

1. Introduction environmental assessment of an optimized solar cooling


system for a medium sized benchmark office building in
To reduce environmental pollution and global warming Los Angeles (California) having the floor area 4983 m2. In
Balghouthi et al. [2005] suggested the solar power air this building 150 kW capacity absorption chiller was used
conditioning in place of conventional vapour compression with varying collector area of 80-490 m2. The Payback is
air conditioning systems. Assilzadeh et al. (2005) carried calculated as 13.8 years when the 40% subsidy is provided
out the modeling and simulation of absorption solar on capital investment.
cooling system with TRNSYS program. Eicker et al. (2014) performed the primary energy analysis
Pongtornkulpanich et al. (2008) share the experience with and economic evaluation of solar thermal cooling and
fully operational solar driven 10 ton LiBr/H2O single solar photovoltaic cooling system, the comparison is made
effect absorption cooling system in Thailand. They for three different climates corresponding to the Palermo,
analyzed the data collected during 2006 and show that 72 Madrid and Stuttgart. The cooling systems while in the
m2 evacuated tube solar collector delivered a yearly case of solar thermal system relative primary energy
average solar fraction of 81%, while LPG –fired backup savings reaches 37% in Palermo, 36% in Madrid and 29%
unit supplied the 19% thermal energy. Eicker et al. (2009) in the Stuttgart. Various literature conclude that the
develops a full simulation model for absorption cooling primary energy saving and, economic analysis are
systems, combined with a stratified storage tank, dynamic different for different climates, countries and electric
collector model and hourly building loads. They found prices.
that depending on control strategy, location and cooling In the present work parametric study and performance
load time series, between 1.7 and 3.6 m2 vacuum tube analysis of solar thermal cooling systems has been
collector per kW cooling load are required to cover 80% performed considering the annual solar fraction and
of the cooling load. Tsoutsos et al. (2010) take for granted relative primary energy savings. In the solar thermal
that the air conditioning is responsible for a large cooling system Evacuated tube Collector was used with
percentage of the greenhouse and ozone depletion effects. wide variance of area ranging from 70 m2-110 m2 have
They suggest the solar cooling system for zero emission been considered. For performance analysis, Ahmedabad
technologies and to reduce energy consumption and CO2 represents hot and dry climate, Bangalore represents
emission. Y Hang et al. (2011) carried out economical and moderate climate, Chennai represents warm and humid

ISSN: 2395-1303 http://www.ijetjournal.org Page 244


International Journal of Engineering and Techniques - Volume 3 Issue 5, Sep - Oct 2017

climate and Delhi represents composite climate. The 4 Annual Cooling Load Analyses
cooling load of the building is different due to the climatic
condition and consequently the system performance also The cooling load of the five zone buildings determined
differs. using TRNSYS program. From the building cooling
model the cooling load can be determined partly as
2 Solar Thermal Cooling Systems
infiltration gain, ventilation gain, sensible gain and latent
gain. In this study the building load is calculated by using
This system is simulated using a configuration SCH 601
TRNSYS simulation program for four cities situated in
from the program schematic diagram can be seen in
four different climate conditions.
previous publication [9] This configuration shows the
Tthe annual cooling demand and peak cooling load for the
complete heating, cooling and domestic hot water
different cities selected from different climate zones. It is
application. In this study only cooling is considered for
clear that the peak cooling load is 31.59 kW for Delhi
analysis purpose. The solar thermal cooling system is
(composite climate) whereas the lowest 20.85 kW is for
composed of a solar collector field, solar storage tank,
Bangalore (Moderate climate) while annual cooling
heat exchanger, cold storage tank and vapour absorption
demand per square meter of building area is highest
chiller. The simulation parameter and their values are
225.64 kWhth/m2 for Chennai (Warm and humid). This
shown in table 1.
Table 1: Parameters considered for simulation of solar thermal indicates that the peak cooling load is higher in composite
cooling system climate (Delhi) and hot and dry climate (Ahmedabad)
Component Parameter Solar thermal Source because the variation of temperature is higher there
Solar 2 2 Henning resulting in the peak load but the total cooling load is
Collector Surface Area m 70-110 m 2007 highest for warm and humid climate (Chennai) where the
Solar Storage Type Vertical Eicker et al. warm and humid climate increases the latent heat load
2014 than others resulting in highest cooling demand. Hot and
Volume 5000 ltr
Thermal Type Absorption Mateous dry climate (Ahmedabad) is the second highest cooling
Chiller et.al 2009 load city because of longer cooling period.
Nominal Cooling 35 kW
power
Nominal COP 0.7 5 Solar Fraction
Pump power 210 W It is the ratio of the annual cooling produced by the solar
Compression Nominal cooling 10.5 kW (Back Eicker et al. to the total annual cooling demand of the building.
Chiller power up ) 2014 Solar Fraction
Annual cooling produced by solar absorption chiller
Nominal COP 3.5 =
Annual coling demand of building
Fig 4 shows the variation of solar fraction for different
3 Specification of Building coupled with Solar climates and various collector areas. It is clear from the
Thermal Air Conditioning. graph 4 that as the collector area increases the solar
fraction also increases because more heat is collected by
The building being used in this research work is an office the collector and supplied to the solar thermal cooling
building with square envelope of 15m length and 15 m system that produce the more amount of solar cooling.
width. The height of the Building is 3.5 meters and total The solar fraction is highest for the moderate climate
floor area is 225 m2. Building is divided in the five zones (Bangalore) and lowest for the warm and humid climate
having orientation towards north. The entire building is (Chennai) because the cooling load of the building is
used for office purpose in the day time only and whole 131kWhth/m2 in the moderate climate is 42% less than the
area is conditioned. Windows on all four sides together warm and humid climate while the solar radiation is 2094
constitute a WWR of 26%. The detail dimension of kWh/m2 in the moderate climate that is 2% more than the
Building is given in previous publication [9]. warm and humid climate.
In the case of ETC highest solar fraction is at collector

ISSN: 2395-1303 http://www.ijetjournal.org Page 245


International Journal of Engineering and Techniques - Volume 3 Issue 5, Sep - Oct 2017

area of 100 m2 in the hot and dry climate (Ahmedabad), to the FPC. The change in the primary energy savings in
warm and humid climate (Chennai) and composite climate the ETC and CPC type collector is very low in
(Delhi) where as it is 90 m2 for moderate climate comparison to the FPC because in the case of ETC and
(Bangalore). In the Bangalore city the cooling load of the CPC even the low collector area produce the higher heat
building is quite low in comparison to other cities so 90 in comparison to the FPC and saved the higher primary
m2 collector area possesses the highest solar fraction. In energy savings. At high collector area the collected heat is
the case of CPC highest solar fraction occurs in the hot increased in all the type of collector but in the case of
and dry (Ahmedabad) and warm and humid (Chennai) at ETC and CPC the heat losses also increase, so with the
90m2 collector area, for moderate (Bangalore) it is 70m2 increase in the collector area the increment in the primary
and for composite climate (Delhi) it is 100 m2. As the energy savings are higher for the FPC and lower for the
collector area increases the solar fraction also gets ETC and CPC. In the ETC and CPC after an optimum
increased but after an optimum collector area it starts collector area the primary energy savings gets decreased.
decreasing because at elevated temperature heat losses are consumption is done by the compressor, condenser fan
also higher. If we use a high collector area then we have and blower. The primary energy savings is the difference
to increase either the capacity of storage tank or the between the primary energy consumption by the solar
cooling load of the building otherwise there will be no thermal cooling system and the primary energy
effect of collector area after an optimum value. The consumption by the compression based cooling system
highest solar fraction has been observed as 0.89, 0.94, operated by grid power.
0.88, and 0.93 for hot and dry, moderate, warm and humid
and composite climate respectively.
Hot and Dry (Ahmedabad)
Moderate (Bangalore)
Hot and Dry (Ahmedabad) Warm and Humid (Chennai)
Moderate (Bangalore) Composite (Delhi)
Warm and Humid (Chennai) 80
Primary energy

Composite (Delhi)
savings(%

1.00 60
0.90
Solar Fraction

0.80 40
0.70
20
0.60
0.50 0
0.40 70 80 90 100 110
70 80 90 100 110
Collector area m2
Collector area m2

Fig. 4 Variation of Solar Fraction with collector area


6. Primary Energy Savings Fig. 5 Variation of Primary Energy Savings with
collector area
Fig 5 shows the variation of primary energy savings for It is observed from the graph 5 that the primary energy
the evacuated type collector with the collector area. It is savings are increased with the increase in collector area ,
observed from the graph that as the collector area because more heat is collected by the solar thermal
increases the primary energy savings also increase similar collector for the same cooling demand. The primary

ISSN: 2395-1303 http://www.ijetjournal.org Page 246


International Journal of Engineering and Techniques - Volume 3 Issue 5, Sep - Oct 2017

energy savings are higher for the moderate climate 5. Eicker U., Pietruschka D. 2009 “Design and
(Bangalore) 55-62 % and lowest for the warm and humid performance of solar powered absorption cooling
climate (Chennai) 44-55%. It is between 54- 62 % for the systems in office buildings” Energy and Building,
hot and dry climate (Ahmedabad) and 51 - 61 % for the Vol. 41, pp. 81-91.
composite climate (Delhi). The primary energy savings
6. Energy Conservation Building Code (ECBC)
are highest for moderate climate due to very low cooling
User Guide, Bureau of Energy Efficiency
demand of 131 kwhth/m2 and the primary energy savings
(2007).
are lowest for the warm and humid climate (Chennai)
because of the very high cooling demand of 225 kwhth/m2. 7. Enibe S.O. 1997 “Solar refrigeration for rural
applications” J Renew Energy, Vol. 12, pp. 157-
67.
7. Conclusions 8. Fan Y., Luo L., Souyri B. 2007 “Review of solar
The solar thermal cooling system is a feasible sorption refrigeration technologies: Development
solution to reduce the environmental pollution and and applications” Renewable & Sustainable
global warming. The highest solar fraction has been Energy Reviews, Vol. 11, issue 8, pp. 1758-1775.
9. Gupta.B.L,Jha N, Vyas D.,Daiya A., Performance
observed as as 0.89, 0.94, 0.88, and 0.93 for hot and
Analysis of solar thermal cooing system using
dry, moderate, warm and humid and composite Flat Plate Collector IJET Vol 3 Issue 4 2017. Pp
climate respectively. The primary energy savings are 36-40.
higher for the moderate climate (Bangalore) 73 % 10. Hammad M.A., Audi M.S.1992 “Performance of
and lowest for the warm and humid climate a Solar LiBr-Water absorption refrigeration
(Chennai) 65%. It is between 71 % for the hot and system” Renewable Energy, Vol. 2, No. 3, pp.
dry climate (Ahmedabad) and 73 % for the 275 -282.
composite climate (Delhi). 11. Hang Y., Qu M., Zhao Fu. 2011 “Economical and
environmental assessment of an optimized solar
8. References cooling system for a medium-sized benchmark
office building in Los Angeles, California”
1. Assilzadeh F., Kalogirou S. A., Alia Y.,, Sopiana
Renewable Energy, Vol. 36, pp. 648-658.
K., 2005 “Simulation and optimization of a LiBr
12. Henning H.M. 2007 “Solar assisted air
solar absorption cooling system with evacuated
conditioning of buildings – an overview” Applied
tube collectors” Renewable Energy Vol.30., pp.
Thermal Engineering, vol. 27 pp. 1734–1749.
1143–1159.
2. Balghouthi M., Chahbani M. H., Guizani A., 2005 13. Kim D.S., Infante Ferreira C.A. 2008 “Solar
“Solar powered air conditioning as a solution to refrigeration options – a state-of-the-art review”
reduce environmental pollution in Tunisia” Int. Journal of Refrigeration, Vol. 31, pp. 3–15.
Desalination Vol. 185, pp.105-110. 14. Mateus T., Oliveira A.C. 2009 “Energy and
3. Bongs C. 2009 “Benchmarks for comparison of economic analysis of an integrated solar
system simulation tools – Absorption chiller absorption cooling and heating system in different
simulation comparison” A technical report of building types and climates” Applied energy, Vol.
subtask C, Task 38 Solar Air-Conditioning and 86, pp. 949-957.
Refrigeration. 15. Mazloumi M., Naghashzadegan M., Javaherdeh
4. Eicker U., Colmenar-Santos A., Teran L., Cotrado K. 2008 “Simulation of solar lithium bromide –
M. 2014 “Economic evaluation of solar thermal water absorption cooling system with parabolic
and photovoltaic cooling systems through trough collector” Energy Conversion and
simulation in different climatic conditions: An Management, Vol. 49, pp. 2820-2832.
analysis in three different cities in Europe” 16. TRANSOL, http://aiguasol.coop/en/transol-solar
Energy and Buildings, Vol. 70, pp. 207-223. thermal -energy-software/ (accessed July 2014).

ISSN: 2395-1303 http://www.ijetjournal.org Page 247


International Journal of Engineering and Techniques - Volume 3 Issue 5, Sep - Oct 2017

17. Tsoutsos T., Aloumpi E., Gkouskos Z.,


Karagiorgas M. 2010 “Design of a solar
absorption cooling system in a Greek hospital”
Energy and Building, Vol. 42, pp. 265-272.

ISSN: 2395-1303 http://www.ijetjournal.org Page 248

Vous aimerez peut-être aussi