Vous êtes sur la page 1sur 5

International Journal of Engineering and Techniques - Volume 3 Issue 6, Nov - Dec 2017

RESEARCH ARTICLE OPEN ACCESS

Performance Enhancement of PV Cooling System – Using


VRF Technology
Bachchu Lal Guptaa
Department of Mechanical Engineering, Govt. Engineering College Bharatpur 321001 India.

Abstract:
From the various techniques that enhances the solar fraction of solar Photovoltaic cooling system VRF
technology is most important. Use of VRF technology enhances the solar fraction along with the reduction in
the energy consumption and payback period. The solar fraction reaches up to 0.89 for hot and dry climate
(Ahmedabad), 0.95 for moderate climate (Bangalore), 0.84 for warm and humid climate (Chennai) and 0.88 for
composite climate (Delhi). It is lowest for the warm and humid climate due to highest annual cooling demand
and it is highest for the moderate climate because of the lowest annual cooling demand and higher cost of VRF
than PTAC.

1. Introduction: The main advantages of a VRF system over


the conventional multi-split system are
A Variable Refrigerant Flow (VRF) wide-range capacity modulation, individual
system is a refrigerant system that varies the room set point control, and—for the heat
refrigerant flow rate with the help of a recovery type VRF systems—the
variable speed compressor and electronic simultaneous cooling and heating capability
expansion valves (EEVs) located in each [Goetzler W 2007], which collectively lead
indoor unit to match the space cooling or to better energy performance and indoor
heating load in order to maintain the zone air comfort. The VRF systems are residential
temperature at the indoor set temperature. In systems that operate either in cooling mode
cooling mode, the outdoor unit heat or heating mode but not simultaneous
exchanger acts as condenser through the cooling and heating. Small VRF systems
four-way valve, while the indoor unit heat have one compressor, while large systems
exchanger acts as evaporator. The typically include two to three compressors
discharged refrigerant from the compressor with fitted for variable speed capability, thus
flows into the outdoor unit, releases heat, enabling wide capacity modulation. The
and becomes high-pressure low temperature inverter yields high part-load efficiency
refrigerant. It is then throttled to low because HVAC systems often operate in the
pressure by the EEV, absorbing heat from range 40% to 80% of its maximum capacity,
the indoor air through the indoor unit and while the single speed units have to cycle on
superheating. Finally, the superheated and off causing efficiency losses. Heat
refrigerant returns back to the compressors. recovery is readily accomplished when
In heating mode, the four-way valve simultaneous heating and cooling occurs,
reverses the refrigerant path and turns the which leads to energy savings. The inverter
outdoor unit into evaporator and the indoor technology used in the VRF system can
unit into condenser. Thus the indoor unit maintain precise room temperature control,
rejects heat to the indoor air and heats it up generally within ±0.55°C (±1°F) [Hong T
[Hong T 2014]. 2014].

ISSN: 2395-1303 http://www.ijetjournal.org Page 308


International Journal of Engineering and Techniques - Volume 3 Issue 6, Nov - Dec 2017

EnergyPlus version 8.1 can model systems. Fig1 shows the variation of cooling
the heat pump type and heat recovery type load for a day time calculated by the two
VRF systems. The object AirConditioner: software TRNSYS and Energy plus. It is
VariableRefrigerantFlow describes the clear from the graph that the cooling load is
outdoor unit which connects to the zone nearly same.
terminal units (indoor units). Zone terminal
units operate to meet the zone sensible TRNSYS ENERGY PLUS
cooling or heating requirements as

Peak Cooling Load kWth


35
determined by the zone thermostat schedule. 28
The actual operation mode is determined 21
based on the master thermostat priority 14
control type. There are five algorithms 7
available: LoadPriority, ZonePriority, 0
ThermostatOffsetPriority,

2617
2619
2621
2623
2625
2627
2629
2631
2633
2635
2637
2639
MasterThermostatPriority, and Scheduled.
LoadPriority uses the total zone load to Hours of a Year -Hot and Dry Climate
choose the operation mode as either cooling
or heating. ZonePriority uses the number of Fig: 1Comparsion of Cooling Load [Hot
zones requiring cooling or heating to and dry climate -Ahemedabad]
determine the operation mode.
ThermostatOffsetPriority uses the zone TRNSYS
farthest from the room set point to determine 12
Power Generation (kW)

the operation mode. The 10


MasterThermostatPriority operates the
8
system according to the zone load where the
master thermostat is located. Scheduled 6
operates the VRF system either in cooling or 4
heating based on schedule. When the system 2
is running in cooling mode, the cooling coils 0
will be enabled only in the terminal units
1
12
23
34
45
56
67
78
89
100
111
122
133
144
155
166
where cooling is required. In heating mode, Hours of Weak
the heating coils only response to the zones
with heating load. The indoor unit supply Fig.2 Comparison of Power Generation
fan can be modeled in two operation modes: [70 m2 PV Area Mono crystalline]
cycling fan cycling coil (AUTO fan mode)
or continuous fan cycling coil (Fan ON Fig.2 shows the comparison of
mode). To model the AUTO fan mode, only power generation by the two software’s
the Fan: OnOff object can be used. For the TRNSYS and ENERGY PLUS. It has been
Fan ON mode, both Fan: OnOff and Fan: observed from the graph that the power
ConstantVolume objects can be used [Hong generation is approximately same in
T 2014]. ENERGY PLUS as in TRNSYS.
2. Performance analysis of PV
Model validation cooling system with VRF
The whole building modeling was In this section performance analysis
done in the energy plus software with the of PV cooling system using variable
same building parameter and HVAC refrigerant flow presented and discussed.

ISSN: 2395-1303 http://www.ijetjournal.org Page 309


International Journal of Engineering and Techniques - Volume 3 Issue 6, Nov - Dec 2017

Solar Fraction PTAC VRF


The Power consumption of the VRF 1.00

Solar Fraction
cooling system decreases in comparison to 0.80
the PTAC system while the power 0.60
generation from the photovoltaic remains
0.40
the same. So in the day time there is good
0.20
matching between the PV generation and the
energy consumption of the VRF system that 0.00
enhances the solar fraction.
Fig 3 (a) shows the variation of solar
fraction with PV area. It has been observed Climate (City)
that the highest solar fraction is achieved for
the moderate climate Bangalore because of Fig: 3 (b) Comparison Solar Fraction (PV area-90m2)
low cooling demand resulting in low
electrical energy consumption of the VRF PV Generation
PTAC-Energy Consumption
system. In the moderate climate power

Energy consumption
VRF- Energy Consumption
generation from the photovoltaic system is 20
good and energy consumption by air 16

(kWhel)
conditioner is low so there is a good 12
matching of power generation and 8
consumption in the day time that enhances 4
the solar fraction. The lowest solar fraction 0
is for warm and humid climate (Chennai) 1 4 7 1013161922252831343740434649
because of the highest annual cooling Hours of the day May 1,2
demand. Using VRF technology the solar
fraction reaches upto 0.89 for hot and dry Fig: 4 Comparison of PV generation and
climate (Ahmedabad), 0.95 for moderate consumption [Hot and dry climate (Ahemdabad)
climate (Bangalore), 0.84 for warm and PV area 90 m2]
humid climate (Chennai) and 0.88 for
Fig.4 shows the comparison of
composite climate (Delhi). Fig.7.3 (b) shows
energy consumption and PV generation for
the comparison of solar fraction for the
hot and dry climate (Ahemdabad). It has
PTAC and VRF system. The solar fraction is
been observed from the graph that the PTAC
higher for VRF technology.
Hot and dry climate (Ahemdabad)
consumption is very high in comparison to
Moderate climate (Bangalore) the PV generation. The difference between
Warm and humid climate (Chennai) the two is taken by grid supply that is the
100
reason why the solar fraction is lower in the
PTAC system. The consumption of the VRF
Solar Fraction

80
system follows the same trends as the
60
generation of PV power so only a small
40
amount of grid supply is required resulting
20 in the high solar fraction. In the PTAC
0 system there is condition in the day time
70 80 90 100 110 when the thermostat OFF the compressor in
PV Area m2
that case the PV generates power but
Fig: 3(a) Variation of Solar Fraction with PV area consumption is zero and solar fraction is not
calculated.

ISSN: 2395-1303 http://www.ijetjournal.org Page 310


International Journal of Engineering and Techniques - Volume 3 Issue 6, Nov - Dec 2017

Although using VRF system the solar Conclusion


fraction achieved is very high in comparison Use of VRF technology enhances the
to the conventional system but the total solar fraction along with the reduction in the
energy consumption is reduced 11- energy consumption and payback period.
28%.Fig.5 shows the comparison of annual The solar fraction reaches up to 0.89 for hot
electrical energy consumption for the four and dry climate (Ahmedabad), 0.95 for
different climates with the VRF and moderate climate (Bangalore), 0.84 for
conventional PTAC system. warm and humid climate (Chennai) and 0.88
for composite climate (Delhi). The payback
PTAC Energy Consumption time come down to 13, 18, 11, and 17 years
VRF Energy Consumption
for hot and dry climate, moderate climate,
warm and humid climate and composite
Annual Electrical Energy

20000 climate respectively. It is lowest for the


Consumption(kWhel)

16000 warm and humid climate due to highest


12000 annual cooling demand and it is highest for
8000 the moderate climate because of the lowest
4000 annual cooling demand and higher cost of
0 VRF than PTAC.

References
Climates
1. A TRaNsient simulation Program
Volume-1.2009. University of
Wisconsin Madison.
Fig: 5 Comparison of annual electrical 2. A TRaNsient simulation Program
energy consumption Volume-4.Mathematical References
of components 2014. University of
It has been observed from the graph Wisconsin Madison.
that the saving in the annual electrical 3. ASHRAE standard - Ventilation for
energy consumption is very high 28% for Acceptable Indoor Air quality , 2004
moderate climates because the cooling 4. ASHRAE, Handbook of
demand of moderate climates is low in fundamentals, 1997.
comparison to the other one. The low 5. Central Electricity Authrity New
cooling demand decreases the size and Delhi 2013 A Report on “Large
electrical energy consumption of the cooling Scale GridCentral integration of
system. In the hot and dry climate Renewable Energy Sources”.
(Ahemdabad) and composite climates 6. Central Electricity Regulatory
(Delhi) the peak cooling load are highest Commission New Delhi 2014
during summer season so the both systems “Benchamarks Capital Cost Norms
(PTAC and VRF) consume the electrical for Solar PV power projects and
energy at almost same level. In the warm Solar Thermal power projects”
and humid climate the cooling load remains Petition No. SM/353/2013.
same throughout the year so in this 7. ClimatechAircon Engineering Pvt.
condition the VRF system can save the Ltd. Jaipur Jaipur. 2014 “Quotation
electrical energy consumptions. for supplying the packaged air
conditioner and pumps” at

ISSN: 2395-1303 http://www.ijetjournal.org Page 311


International Journal of Engineering and Techniques - Volume 3 Issue 6, Nov - Dec 2017

Government Engineering College Climatic Zone of India”. In 2nd Asia


Bharatpur (Raj.) India. Conference of International Building
8. Daikin World’s leading air Performance Simulation
conditioner catalogue.DAIKIN http://www.cea.nic.in
AIRCONDITIONER INDIA PVT. 15. http://www.inflation.eu/inflation-
LTD. rates/india/historic-inflation/cpi-
9. Duffie J.A., Backman W.A. 2006 inflation-india-2014.aspx
“Solar engineering of thermal 16. http://www.photon.info
process” Third edition Published by 17. http://www.sundanzer.com. Last
John Wiley & Sons Inc, Hobokan consulted on 25 November 2013..
New Jersey. 18. Kim D.S., Infante Ferreira C.A. 2008
10. Emphase M 250 Microinverter Data “Solar refrigeration options – a state-
sheet available on of-the-art review” International
www.emphase.com Journal of Refrigeration Vol. 31, pp.
11. Energy Conservation Building Code 3–15.
(ECBC) User Guide, Bureau of
Energy Efficiency(2009). 19. Ministry of Environment and Forests
12. Energy Plus Documentation, DOE India 2009 “Road map for phase out
2012, Engineering Reference version HCFCs in India”.
8 U.S. Department of Energy, 20. Modi A., Chaudhuri A., Vijay B.,
Washington D.C. Mathur J. 2009 “Performance
13. Goetzler, W. 2007. Variable Analysis of a Photovoltaic operated
Refrigerant Flow Systems. ASHRAE domestic refrigerator”. Applied
Journal, 49(4): 24-31. Energy Vol. 86, pp. 2583-2591.
14. Gupta H., Sharma S., Mathur S., 21. State Bank of India 2014 “Average
Mathur J. 2014. “Comparison of interest rates on fixed deposits
Different Type of Configurations for schemes”.
Photovoltaic Façade in Composite

ISSN: 2395-1303 http://www.ijetjournal.org Page 312

Vous aimerez peut-être aussi