Motor Condition And Reliability

Evaluation Program (MOTOCARETM)

Aditya Korde
Diagnostic Technologies India Pvt. Ltd.

www.diatechindia.com
MOTOCARETM The MOTOCARETM advantage – no fault area left
uncovered!!

On-Line Package: Off-Line Package:

• Electrical Signature Analysis • Tan Delta & Capacitance Analysis


Rotor bar degradation Oil & grease in insulation
Stator core degradation Moisture in insulation
Eccentricity Overall aging
Interturn insulation degradation
• Partial Discharge Analysis
De-bonding of insulation
• Vibration Analysis Voids in insulation
Mechanical faults Loss of corona shield
Localized defects

• Acoustic Emission Analysis • Motor Circuit Analysis


Bearing degradation Interturn shorts
Lubrication problems Loose connections

• DC Tests
Moisture ingress
Surface contamination

www.diatechindia.com
MOTOCARETM What have we found?

www.diatechindia.com
MOTOCARETM What are the typical faults detected?

PERCENTAGE FAULT TYPES SEEN IN CASE OF SEVERE PROBLEMS


Stator Core
Degradation Loose Bent
4% Windings Shafts
4% 2%
Housing Weak Insulation
Resonance
Wear 34%
4%
5%

Foundation
Problems
6%

Broken bars
8%

Unbalance
9% Misalignment Bad Bearings
11% 14%

www.diatechindia.com
MOTOCARETM Typical ESA spectrum – rotor bar degradation

Identical 2300 KW motors. LHS is excellent, RHS had 7 broken bars.

www.diatechindia.com
MOTOCARETM Typical ESA spectrum – stator core degradation

Identical 410 KW motors. LHS is excellent, RHS had severe hot spots in the stator.

www.diatechindia.com
MOTOCARETM Typical VA spectrum – motor with insufficient rigidity

1 6 .9 4 7 9
O /A ll 1 7 .2 2 8 m m /s r m s

R W P um p 5
M o to r N D E
R a d ia l 2
V e l F re q 1 6 0 0 H z
2 /6 /2 0 0 3 6 :2 1 :1 8 P M
O / A ll 1 . 9 8 9 m m / s r m s
9 8 3 .3 9 3 R P M
< a d d n o te >
- 0 .8 0 7
16

14

12
S t r o n g 1 X p e a k , in o n e R a d ia l d ir e c t io n o n ly . In d ic a t iv e o f la c k o f s t r u c t u r a l r ig id it y in t h is d ir e c t io n .
10
mm/s rms

6 R W P u m p 2
M o to r N D E
4 R a d ia l 2
V e l F re q 1 0 0 0 H z
2
2 /6 /2 0 0 3 3 : 5 2 : 0 0 P M
O /A ll 1 7 .2 2 8 m m /s r m s
5 8 8 .5 2 1 R P M
0
< a d d n o te >
0 2 4 6 8 10 12 14 16 18
orders

This 335 KW vertical motor had a weak foundation, causing vibration.


Attempts to balance it had failed in reducing the vibration.

www.diatechindia.com
MOTOCARETM High vibration…. & no solutions!

• 630 KW, 2 pole motor had high vibration, between 7 to 13 mm/sec at


standstill (at 1X & harmonics).

• Coupled vibration was over 30 mm/sec, RMS (mostly at 1X).

• Identical adjoining motor had relatively low vibration.

• Relative phase was oscillating between 20 & 240 degrees on


foundation, steady on mat .

• Bump test revealed multiple natural frequencies between 150 Hz &


250 Hz.

• The rotor bars had recently been repaired, the rotor balanced &
bearings replaced. False brinelling marks were seen on the discarded
bearing.

• We diagnosed loose components & foundations problems. Motor


dismantled & inspected. Rotor core was badly damaged & loose on
the shaft. Repair reduced vibration levels but still high.

• Foundation (6 feet PCC) broken, wooden logs found inside! Vibration


levels are now below 3 mm/sec, RMS.

www.diatechindia.com
MOTOCARETM High vibration…. & no solutions (contd.)!!

• Brand new 2 MW, 2 pole motor had high vibration, over 9 mm/sec
uncoupled. Coupled vibration over 25 mm/sec, RMS.

• 1X & multiples present, 3X component dominated.

• Bearings replaced, vibration increased. Cut taken on stator bore,


vibration increased still further.

• Motor rejected by client!

• Our investigations showed unstable phase values & a natural frequency


at 149 Hz, coinciding with the 3X component.

• Motor dismantled again & short-circuiting rings de-brazed. Rotor bars


are supposed to be tight in the slots, these were removed by hand.

• New, re-sized bars manufactured and end-shields stiffened to change


the natural frequency. Vibration is now below 3 mm/sec in coupled
condition.

www.diatechindia.com
MOTOCARETM AE charts – faulty plain bearing

The CM – 2EF’s DE bearing was badly degraded & had to be replaced.

www.diatechindia.com
MOTOCARETM AE charts – faulty bearing in a low speed motor

The 428 RPM CWP – 1A motor’s NDE bearing had a high DISTRESS™ reading, indicating
a faulty bearing. The same was confirmed on opening the motor.

(MSEB, Bhusaval)

www.diatechindia.com
MOTOCARETM Tan delta curves – high moisture contamination & voids

CEP – A has high tan delta values, indicative of moisture contamination.


CEP – B has low tan delta values but a high tip-up, indicative of insulation voids.

(Jindal Power, Bellary)

www.diatechindia.com
MOTOCARETM Tan Delta Curves – high grease/dirt contamination
(900 kW motor)

Motor has a -ve tip-up, typical of grease/dirt contamination.

www.diatechindia.com
MOTOCARETM Tan delta curves – severe deterioration & discharges

TAN DELTA CURVES FOR HYPER COMPRESSOR MOTORS CAPACITANCE CURVES FOR HYPER-COMPRESSOR MOTORS

4.5 116

4
114

3.5

112

CAPACITANCE (nF)
TAN DELTA (%)

110
2.5
1 1
1 1
- -
K K
B B
2
108

1.5

106

104
0.5

0 102

0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 0 0.5 1 1.5 2 2.5 3 3.5 4 4.5

APPLIED VOLTAGE (KV) APPLIED VOLTAGE (KV)

11-KBX-203 motor has very high tip-ups, typical of severe deterioration. Failed 4 months later.

(IPCL, Baroda - LDPE)

www.diatechindia.com
MOTOCARETM MCA results – interturn short in synchronous motor’s rotor

• 5100 KW, 200 RPM Synchronous Motor – 30 rotor coils and 224 stator
coils.

• Rotor poles were being replaced based on manufacturer’s


recommendations, new poles supplied by manufacturer.

• Manufacturer’s test report indicated that all new poles were with
healthy windings, having matching impedances.

• MCA testing indicated faults in two of the new rotor coils.

• Faults were confirmed by manufacturer & defective poles


replaced.

www.diatechindia.com
MOTOCARETM Internal discharges + Corona – 210 MW, 15.75 kV
Generator

R Phase – 1400 nC Y Phase – 6 nC B Phase – 7 nC

+ve pulses dominate; plus high amplitude


low repetition rate activity on top

www.diatechindia.com
MOTOCARETM Insulation delamination & surface contamination –
30 MW , 11 kV Generator

GTG 1 – 252 nC GTG 8 – 18.6 nC

+ve & -ve pulses equal, asymmetric

www.diatechindia.com
MOTOCARETM Poor contact between stress grading & slot corona
protection – 2.4 MW , 6.6 kV Motor

Before overhaul – 4050 nC After overhaul – 23 nC

www.diatechindia.com