Vous êtes sur la page 1sur 37

Summary Bolt Design

Bolt Design
Alt 1
ID Height
Tank Description (m) (m) Bolt Bolt Bolt
Bolt Dia
Number Distance Length
(inch)
(ea) (mm) (mm)

Jawa 2 - Service/Fire Water Storage Tank 15.52 12.35 1 50 990 650


Jawa 2 - Make Up Water Tank 10.8 9.65 1 26 1330 650
Muara Karang - Service Water Storage Tank 12.5 10.7 1 36 1110 650
Muara Karang - Make Up Water Tank 8.5 7.83 7/8 20 1370 570
Muara Karang - Fire Fighting Water Tank 12.2 10.67 1 32 1220 650

Preliminary only
As per civil calculation, anchorage is not required
For exact bolt result, need data sheet from mechanical
Bolt Design
Alt 2

Bolt Bolt Bolt


Bolt Dia
Number Distance Length
(inch)
(ea) (m) (m)

1 1/2 22 2250 845


1 1/2 12 2890 845
1 1/2 16 2500 845
1 16 1710 650
1 1/2 14 2790 845
JAWA 2 - SERVICE/FIRE WATER STORAGE TANK

Attachment G - Page 3 of 37
Data:
Inner Dia = 15.52 m
Outside Dia = 15.55 m
Height = 12.35 m
Steel Unit Weight = 7,650.00 kg/m3
Water Unit Weight = 1,000.00 kg/m3
Operation Capacity = 1,900.00 m3
Design Capacity = 2,148.00 m3
Roof Inclination = 1 : 12 m/m (assumed)
Plate thickness = 13.00 mm (assumed)
D/H = 1.26
Cone Roof Height = 0.65 m

Raw Estimated Weight


Bottom = 18,876.96 kg
Sheel = 59,758.28 kg (assume: no increment of shell thickness)
Roof = 18,942.39 kg +
97,577.62 kg (assume: including support, column, etc)

Weight
Empty / Shut Down DE = 957.24 kN
Operating DO = 19,596.24 kN
Test DT = 22,029.12 kN

Wind Load
Wind Speed = 32.00 m/s (assumed)
Exposure = C
Structure Category = III
Topographic Factor = 1.00
Importance Factor = 1.15
wind directionality factor = 1.00
Wind Pressure = 752.61 N/m2
Gust Factor = 0.85
Height above top of fdn. = 13.00 m
thickness of footing = 0.50 m (assumed)
Force Coefficient = 0.50
Tank Projected Area = 202.06 m2
Wind Load = 64.63 kN
Moment due to wind load = 420.04 kN.m

Seismic Load
- weight of water in Op. = 18,639.00 kN

effective impulsive portion


- = 13,532.73 kN
of the liquid weight

effective convective
- (sloshing) portion of the = 5,356.12 kN
liquid weight
- sloshing period coefficient = 0.58

388332305.xlsx
natural period of the
- convective (sloshing) mode = 4.11 s
of behavior of the liquid

regional dependent Attachment G - Page 4 of 37


- transition period for longer = 4.00 s
period ground motion

convective design response


- spectrum accelearation = 0.21 %g
coefficient
- Importance factor = 1.25
- SDS = 0.56
- R = 3.00

Impulsive design response


- spectrum acceleration = 0.23 %g
coefficient
Seismic Load Empty Condition
- Vi in empty condition = 221.38 kN.m

Design base shear due to


- convective component of = 0.00 kN.m
the effective sloshing
weight (empty condition)

- Total design base shear in 221.38 kN.m


empty condition =

Seismic Load Opr. Condition


- Vi in operating condition = 3,351.11 kN.m
- Vc in operating condition = 1,117.37 kN.m

- total design base shear in = 3,532.48 kN.m


operating condition

Slab Moment:

height from the bottom of


- the tank shell to the shell's = 6.18 m
center of gravity

height from the bottom of


- the tank shell to the roof = 12.56 m
and roof appurtenaces
center of gravity

height from the bottom of


the tank shell to the center
- of action of the lateral = 7.11 m
seismic force related to the
impulsive liquid force for the
slab moment

height from the bottom of


the tank shell to the center
- of action of the lateral = 8.98 m
seismic force related to the
convective liquid force for
the slab moment

388332305.xlsx
● Slab moment in empty = 1,377.13 kN.m
condition
● Slab moment in Opr. = 25,661.68 kN.m
condition Attachment G - Page 5 of 37

388332305.xlsx
E.6 Anchor Bolt Design
Use: Anchor Bolt ASTM A307 Attachment G - Page 6 of 37
Bolt Circle Diameter, BCD = 15.75 m
db = = 1 1/2 in
= 38.1 mm
Ab = 1140.1 mm2
ft = 137.3 MPa
fv = 68.6 MPa

nb = 22 ea
min distance to edge (E) = 230 mm
min bolt pitch (F) = 160 mm
min bolt embedment (Le) = 640 mm

BCD

Zp bolt = ( S n * ( BCDn / 2 )^2 ) / most outer BCD


Zp bolt = (22 x (15,746/2)^2 )/15,746
= 86.60 m

Unfactored Load Combination for anchor bolt design


Axial Horizontal Moment
Load Combination Condition
( kN ) ( kN ) ( kN.m )
LC 2-1 957.2 - - Permanent
Empty LC 2-2 957.2 64.6 420.0 Temporary
LC 2-3 957.2 155.0 964.0 Temporary
LC 2-4 19,596.2 - - Permanent
Operation LC 2-5 19,596.2 64.6 420.0 Temporary
LC 2-6 19,596.2 2,472.7 17,963.2 Temporary
LC 2-7 22,029.1 - - Testing
Testing
LC 2-8 22,029.1 21.5 140.0 Testing

Maximum Unfactored Forces Applied to Single Anchor Bolt:


P/n H/n M/Zp P/n - M/Zp
Load Combination Condition
( kN ) ( kN ) ( kN ) (kN)
LC 2-1 43.51 - - 43.51 Permanent
Empty LC 2-2 43.51 2.94 19.09 24.42 Temporary
LC 2-3 43.51 7.04 43.82 -0.31 Temporary
LC 2-4 890.74 - - 890.74 Permanent
Operation LC 2-5 890.74 2.94 19.09 871.65 Temporary
LC 2-6 890.74 112.40 816.51 74.23 Temporary
LC 2-7 1,001.32 - - 1,001.32 Testing
Testing
LC 2-8 1,001.32 0.98 6.36 994.96 Testing

Anchor Bolt for Sliding Resistance


Hmax = 2472.74 kN
Vs = µ*(Ws + Wr + Wf + Wp) (resistance to sliding)
where:
µ = 0.40 (friction coefficient)
Vs = 7838.49 kN > Hmax = 2472.74 kN
resistance sliding > calculated shear, so no need anchor bolt for sliding resistance

388332305.xlsx
Anchor Bolt for Tension Resistance
Bolt shear and tension combination for A307:
ft allowable = 26 - 1.8fv <= 20 (ksi) or (179 - 1.8fv < 137 [MPa])
fv = H/(n x Abolt) Attachment G - Page 7 of 37
Tall = Ft allowable x Abolt

Anchor bolt capacity check


fv Tall T
Load Combination Remark
( MPa ) ( kN ) ( kN )
LC 2-1 0.000 156 COMP. No Tension - OK
Empty LC 2-2 0.003 156 COMP. No Tension - OK
LC 2-3 0.006 156 -0.307 OK
LC 2-4 0.000 156 COMP. No Tension - OK
Operation LC 2-5 0.003 156 COMP. No Tension - OK
LC 2-6 0.099 156 COMP. No Tension - OK
LC 2-7 0.000 156 COMP. No Tension - OK
Testing
LC 2-8 0.001 156 COMP. No Tension - OK

Anchor Bolt for Uplift Resistance

Mechanical Calc. For Tank (these cell should be taken from mechanical data sheet, all this
value are only assumption)
D = 51.003 ft (tank OD)
P = 69.120 inches H2O (design pressure)
Pt = 86.400 inches H2O (test pressure = 1.25 P)
th = 0.315 in (roof plate thicknesss)
Mw = 309,802.625 ft-lbf (wind moment)
Mrw = 2,605,424.041 ft-lbf (seismic ringwall moment)
W1 = 131,744.293 lbf (corroded shell + shell insulation)
W2 = 173,505.062 lbf (corroded shell + shell insulation + corroded
roof plates)
W3 = 164,829.809 lbf (new shell + shell insulation)

Uplift (U) Case 1: Design Pressure Only


U = [(P-8*th)*D^2*4.08]-W1
= [(69,12-8*0,315)*51,003^2*4.08]-131744,29253994
= 575,112.168 lbf
Uplift per anchor (bt) = U/nb
= 575112,168/
= 26,141 lbf
Sd = 15,000 psi (allowable anchor bolt stress)
Asr = Bolt Root Area Req'd
= bt/Sd
= 1.74 in2
db-needed = 1.49 in > db = 1 1/2 in OK!

Uplift (U) Case 2: Test Pressure Only


U = [(Pt-8th)*D^2*4.08]-W1
= [(86,4-8*0,315)*51,003^2*4.08]-131744,29253994
= 758,512.763 lbf
Uplift per anchor (bt) = U/nb
= 758512,763/
= 34,478 lbf
Sd = 20000 psi (allowable anchor bolt stress)

388332305.xlsx
Asr = Bolt Root Area Req'd
= bt/Sd
= 1.72 in2
db-needed = 1.48 in > db = 1 1/2 in OK!
Attachment G - Page 8 of 37

Uplift (U) Case 3: Failure Pressure Only


Not applicable since if there is a knuckle on tank roof, or tank roof is not frangible.

Uplift (U) Case 4: Wind Load Only


PWR = Wind Uplift /5.208
= 0/5.208
= 0.00 in. H2O
PWS = vF*18
= 0.36*18
= 6.48 lbf/ft^2
MWH = PWS*(D+t_ins/6)*H^2/2
= 6,48*(51,003+2/6)*52.4934^2/2
458333.86 ft-lbf
U = PWR*D^2*4.08+(4*MWH/D)-W2
= 0*51,003^2*4.08+(4*458333,86/51,003)-173505,062
= (137,559.646) lbf
Uplift per anchor (bt) = U/nb
= -137559,646/
= (6,253) lbf
Sd = 0.8*36000 (allowable anchor bolt stress)
= 28800 psi
Asr = Bolt Root Area Req'd
Not Applicable since load per bolt is zero

Uplift (U) Case 5: Seismic Load Only


U = [4*Mrw/D]-W2*(1-0.4*Av)
= [4*2605424/51,003]-173505,062140306*(1-0.4*0)
= 30,828.633 lbf
Uplift per anchor (bt) = U/nb
= 30828,633/
= 1,401 lbf
Sd = 0.8*fy (allowable anchor bolt stress)
= 0.8*36000
= 28800 psi
Asr = Bolt Root Area Req'd
= bt/Sd
= 0.05 in2
db-needed = 0.25 in > db = 1 1/2 in OK!

Uplift (U) Case 6: Design Pressure + Wind Load


U = [(0.4*P+PWR-8*t_h)*D^2*4.08]+[4*MWH/D]-W1
= [(0.4*69+0-8*0.315)*51^2*4.08]+[4*458334/51]-131744
= 170,896.155 lbf
Uplift per anchor (bt) = U/nb
= 170896,155/
= 7,768 lbf
Sd = 20000 psi (allowable anchor bolt stress)
Asr = Bolt Root Area Req'd
= bt/Sd
= 0.39 in2

388332305.xlsx
db-needed = 0.70 in > db = 1 1/2 in OK!

Uplift (U) Case 7: Design Pressure + Seismic Load


U = [(0.4*P-8*t_h)*D^2*4.08]+[4*Mrw/D]-W1*(1-0.4*Av)Attachment G - Page 9 of 37
= [(0.4*69-8*0.315)*51^2*4.08]+[4*2605424/51]-131744*(1-0.4*0)
= 339,284.434 lbf
Uplift per anchor (bt) = U/nb
= 339284,434/
= 15,422 lbf
Sd = 28800 psi (allowable anchor bolt stress)
Asr = Bolt Root Area Req'd
= bt/Sd
= 0.54 in2
db-needed = 0.83 in > db = 1 1/2 in OK!

Uplift (U) Case 8: Frangibility Pressure


Not applicable since if there is a knuckle on tank roof, or tank roof is not frangible

388332305.xlsx
JAWA 2 - MAKE UP WATER STORAGE TANK

Attachment G - Page 10 of 37
Data:
Inner Dia = 10.80 m
Outside Dia = 10.82 m
Height = 9.65 m
Steel Unit Weight = 7,650.00 kg/m3
Water Unit Weight = 1,000.00 kg/m3
Operation Capacity = 700.00 m3
Design Capacity = 793.00 m3
Roof Inclination = 1 : 12 m/m (assumed)
Plate thickness = 10.00 mm (assumed)
D/H = 1.12
Cone Roof Height = 0.45 m

Raw Estimated Weight


Bottom = 7,034.06 kg
Sheel = 24,995.47 kg (assume: no increment of shell thickness)
Roof = 7,058.44 kg +
39,087.97 kg (assume: including support, column, etc)

Weight
Empty / Shut Down DE = 383.45 kN
Operating DO = 7,250.45 kN
Test DT = 8,162.78 kN

Wind Load
Wind Speed = 32.00 m/s (assumed)
Exposure = C
Structure Category = III
Topographic Factor = 1.00
Importance Factor = 1.15
wind directionality factor = 1.00
Wind Pressure = 720.64 N/m2
Gust Factor = 0.85
Height above top of fdn. = 10.10 m
thickness of footing = 0.50 m (assumed)
Force Coefficient = 0.50
Tank Projected Area = 109.29 m2
Wind Load = 33.47 kN
Moment due to wind load = 169.05 kN.m

Seismic Load
- weight of water in Op. = 6,867.00 kN

effective impulsive portion


- = 5,191.59 kN
of the liquid weight

effective convective
- (sloshing) portion of the = 1,762.62 kN
liquid weight
- sloshing period coefficient = 0.58

388332305.xlsx
natural period of the
- convective (sloshing) mode = 3.42 s
of behavior of the liquid

regional dependent Attachment G - Page 11 of 37


- transition period for longer = 4.00 s
period ground motion

convective design response


- spectrum accelearation = 0.29 %g
coefficient
- Importance factor = 1.25
- SDS = 0.56
- R = 3.00

Impulsive design response


- spectrum acceleration = 0.23 %g
coefficient
Seismic Load Empty Condition
- Vi in empty condition = 88.68 kN.m

Design base shear due to


- convective component of = 0.00 kN.m
the effective sloshing
weight (empty condition)

- Total design base shear in 88.68 kN.m


empty condition =

Seismic Load Opr. Condition


- Vi in operating condition = 1,289.35 kN.m
- Vc in operating condition = 515.73 kN.m

- total design base shear in = 1,388.66 kN.m


operating condition

Slab Moment:

height from the bottom of


- the tank shell to the shell's = 4.83 m
center of gravity

height from the bottom of


- the tank shell to the roof = 9.80 m
and roof appurtenaces
center of gravity

height from the bottom of


the tank shell to the center
- of action of the lateral = 5.47 m
seismic force related to the
impulsive liquid force for the
slab moment

height from the bottom of


the tank shell to the center
- of action of the lateral = 7.13 m
seismic force related to the
convective liquid force for
the slab moment

388332305.xlsx
● Slab moment in empty = 430.54 kN.m
condition
● Slab moment in Opr. = 7,908.32 kN.m
condition Attachment G - Page 12 of 37

388332305.xlsx
E.6 Anchor Bolt Design
Use: Anchor Bolt ASTM A307 Attachment G - Page 13 of 37
Bolt Circle Diameter, BCD = 11.02 m
db = = 1 1/2 in
= 38.1 mm
Ab = 1140.1 mm2
ft = 137.3 MPa
fv = 68.6 MPa

nb = 12 ea
min distance to edge (E) = 230 mm
min bolt pitch (F) = 160 mm
min bolt embedment (Le) = 640 mm

BCD

Zp bolt = ( S n * ( BCDn / 2 )^2 ) / most outer BCD


Zp bolt = (12 x (11,02/2)^2 )/11,02
= 33.06 m

Unfactored Load Combination for anchor bolt design


Axial Horizontal Moment
Load Combination Condition
( kN ) ( kN ) ( kN.m )
LC 2-1 383.5 - - Permanent
Empty LC 2-2 383.5 33.5 169.1 Temporary
LC 2-3 383.5 62.1 301.4 Temporary
LC 2-4 7,250.5 - - Permanent
Operation LC 2-5 7,250.5 33.5 169.1 Temporary
LC 2-6 7,250.5 972.1 5,535.8 Temporary
LC 2-7 8,162.8 - - Testing
Testing
LC 2-8 8,162.8 11.2 56.4 Testing

Maximum Unfactored Forces Applied to Single Anchor Bolt:


P/n H/n M/Zp P/n - M/Zp
Load Combination Condition
( kN ) ( kN ) ( kN ) (kN)
LC 2-1 31.95 - - 31.95 Permanent
Empty LC 2-2 31.95 2.79 14.09 17.87 Temporary
LC 2-3 31.95 5.17 25.11 6.84 Temporary
LC 2-4 604.20 - - 604.20 Permanent
Operation LC 2-5 604.20 2.79 14.09 590.12 Temporary
LC 2-6 604.20 81.01 461.32 142.89 Temporary
LC 2-7 680.23 - - 680.23 Testing
Testing
LC 2-8 680.23 0.93 4.70 675.54 Testing

Anchor Bolt for Sliding Resistance


Hmax = 972.06 kN
Vs = µ*(Ws + Wr + Wf + Wp) (resistance to sliding)
where:
µ = 0.40 (friction coefficient)
Vs = 2900.18 kN > Hmax = 972.06 kN
resistance sliding > calculated shear, so no need anchor bolt for sliding resistance

388332305.xlsx
Anchor Bolt for Tension Resistance
Bolt shear and tension combination for A307:
ft allowable = 26 - 1.8fv <= 20 (ksi) or (179 - 1.8fv < 137 [MPa])
fv = H/(n x Abolt) Attachment G - Page 14 of 37
Tall = Ft allowable x Abolt

Anchor bolt capacity check


fv Tall T
Load Combination Remark
( MPa ) ( kN ) ( kN )
LC 2-1 0.000 156 COMP. No Tension - OK
Empty LC 2-2 0.002 156 COMP. No Tension - OK
LC 2-3 0.005 156 COMP. No Tension - OK
LC 2-4 0.000 156 COMP. No Tension - OK
Operation LC 2-5 0.002 156 COMP. No Tension - OK
LC 2-6 0.071 156 COMP. No Tension - OK
LC 2-7 0.000 156 COMP. No Tension - OK
Testing
LC 2-8 0.001 156 COMP. No Tension - OK

Anchor Bolt for Uplift Resistance

Mechanical Calc. For Tank (these cell should be taken from mechanical data sheet, all this
value are only assumption)
D = 35.498 ft (tank OD)
P = 69.120 inches H2O (design pressure)
Pt = 86.400 inches H2O (test pressure = 1.25 P)
th = 0.315 in (roof plate thicknesss)
Mw = 124,686.292 ft-lbf (wind moment)
Mrw = 1,024,225.426 ft-lbf (seismic ringwall moment)
W1 = 55,105.519 lbf (corroded shell + shell insulation)
W2 = 70,666.692 lbf (corroded shell + shell insulation + corroded
roof plates)
W3 = 67,133.357 lbf (new shell + shell insulation)

Uplift (U) Case 1: Design Pressure Only


U = [(P-8*th)*D^2*4.08]-W1
= [(69,12-8*0,315)*35,498^2*4.08]-55105,5185373417
= 287,306.048 lbf
Uplift per anchor (bt) = U/nb
= 287306,048/
= 23,942 lbf
Sd = 15,000 psi (allowable anchor bolt stress)
Asr = Bolt Root Area Req'd
= bt/Sd
= 1.60 in2
db-needed = 1.43 in > db = 1 1/2 in OK!

Uplift (U) Case 2: Test Pressure Only


U = [(Pt-8th)*D^2*4.08]-W1
= [(86,4-8*0,315)*35,498^2*4.08]-55105,5185373417
= 376,147.968 lbf
Uplift per anchor (bt) = U/nb
= 376147,968/
= 31,346 lbf
Sd = 20000 psi (allowable anchor bolt stress)

388332305.xlsx
Asr = Bolt Root Area Req'd
= bt/Sd
= 1.57 in2
db-needed = 1.41 in > db = 1 1/2 in OK!
Attachment G - Page 15 of 37

Uplift (U) Case 3: Failure Pressure Only


Not applicable since if there is a knuckle on tank roof, or tank roof is not frangible.

Uplift (U) Case 4: Wind Load Only


PWR = Wind Uplift /5.208
= 0/5.208
= 0.00 in. H2O
PWS = vF*18
= 0.36*18
= 6.48 lbf/ft^2
MWH = PWS*(D+t_ins/6)*H^2/2
= 6,48*(35,498+2/6)*52.4934^2/2
319904.60 ft-lbf
U = PWR*D^2*4.08+(4*MWH/D)-W2
= 0*35,498^2*4.08+(4*319904,602/35,498)-70666,692
= (34,619.332) lbf
Uplift per anchor (bt) = U/nb
= -34619,332/
= (2,885) lbf
Sd = 0.8*36000 (allowable anchor bolt stress)
= 28800 psi
Asr = Bolt Root Area Req'd
Not Applicable since load per bolt is zero

Uplift (U) Case 5: Seismic Load Only


U = [4*Mrw/D]-W2*(1-0.4*Av)
= [4*1024225/35,498]-70666,6917205314*(1-0.4*0)
= 44,744.660 lbf
Uplift per anchor (bt) = U/nb
= 44744,66/
= 3,729 lbf
Sd = 0.8*fy (allowable anchor bolt stress)
= 0.8*36000
= 28800 psi
Asr = Bolt Root Area Req'd
= bt/Sd
= 0.13 in2
db-needed = 0.41 in > db = 1 1/2 in OK!

Uplift (U) Case 6: Design Pressure + Wind Load


U = [(0.4*P+PWR-8*t_h)*D^2*4.08]+[4*MWH/D]-W1
= [(0.4*69+0-8*0.315)*35^2*4.08]+[4*319905/35]-55106
= 110,132.800 lbf
Uplift per anchor (bt) = U/nb
= 110132,8/
= 9,178 lbf
Sd = 20000 psi (allowable anchor bolt stress)
Asr = Bolt Root Area Req'd
= bt/Sd
= 0.46 in2

388332305.xlsx
db-needed = 0.76 in > db = 1 1/2 in OK!

Uplift (U) Case 7: Design Pressure + Seismic Load


U = [(0.4*P-8*t_h)*D^2*4.08]+[4*Mrw/D]-W1*(1-0.4*Av)
Attachment G - Page 16 of 37
= [(0.4*69-8*0.315)*35^2*4.08]+[4*1024225/35]-55106*(1-0.4*0)
= 189,496.792 lbf
Uplift per anchor (bt) = U/nb
= 189496,792/
= 15,791 lbf
Sd = 28800 psi (allowable anchor bolt stress)
Asr = Bolt Root Area Req'd
= bt/Sd
= 0.55 in2
db-needed = 0.84 in > db = 1 1/2 in OK!

Uplift (U) Case 8: Frangibility Pressure


Not applicable since if there is a knuckle on tank roof, or tank roof is not frangible

388332305.xlsx
MUARA KARANG - SERVICE WATER STORAGE TANK

Attachment G - Page 17 of 37
Data:
Inner Dia = 12.50 m
Outside Dia = 12.52 m
Height = 10.70 m
Steel Unit Weight = 7,650.00 kg/m3
Water Unit Weight = 1,000.00 kg/m3
Operation Capacity = 1,000.00 m3
Design Capacity = 1,192.00 m3
Roof Inclination = 1 : 12 m/m (assumed)
Plate thickness = 10.00 mm (assumed)
D/H = 1.17
Cone Roof Height = 0.52 m

Raw Estimated Weight


Bottom = 9,418.03 kg
Sheel = 32,084.30 kg (assume: no increment of shell thickness)
Roof = 9,450.67 kg +
50,953.00 kg (assume: including support, column, etc)

Weight
Empty / Shut Down DE = 499.85 kN
Operating DO = 10,309.85 kN
Test DT = 12,193.37 kN

Wind Load
Wind Speed = 32.00 m/s (assumed)
Exposure = C
Structure Category = III
Topographic Factor = 1.00
Importance Factor = 1.15
wind directionality factor = 1.00
Wind Pressure = 733.08 N/m2
Gust Factor = 0.85
Height above top of fdn. = 11.22 m
thickness of footing = 0.50 m (assumed)
Force Coefficient = 0.50
Tank Projected Area = 140.50 m2
Wind Load = 43.77 kN
Moment due to wind load = 245.60 kN.m

Seismic Load
- weight of water in Op. = 9,810.00 kN

effective impulsive portion


- = 7,311.66 kN
of the liquid weight

effective convective
- (sloshing) portion of the = 2,626.04 kN
liquid weight
- sloshing period coefficient = 0.58

388332305.xlsx
natural period of the
- convective (sloshing) mode = 3.69 s
of behavior of the liquid

regional dependent Attachment G - Page 18 of 37


- transition period for longer = 4.00 s
period ground motion

convective design response


- spectrum accelearation = 0.25 %g
coefficient
- Importance factor = 1.25
- SDS = 0.56
- R = 3.00

Impulsive design response


- spectrum acceleration = 0.23 %g
coefficient
Seismic Load Empty Condition
- Vi in empty condition = 115.60 kN.m

Design base shear due to


- convective component of = 0.00 kN.m
the effective sloshing
weight (empty condition)

- Total design base shear in 115.60 kN.m


empty condition =

Seismic Load Opr. Condition


- Vi in operating condition = 1,806.57 kN.m
- Vc in operating condition = 663.27 kN.m

- total design base shear in = 1,924.48 kN.m


operating condition

Slab Moment:

height from the bottom of


- the tank shell to the shell's = 5.35 m
center of gravity

height from the bottom of


- the tank shell to the roof = 10.87 m
and roof appurtenaces
center of gravity

height from the bottom of


the tank shell to the center
- of action of the lateral = 6.10 m
seismic force related to the
impulsive liquid force for the
slab moment

height from the bottom of


the tank shell to the center
- of action of the lateral = 7.85 m
seismic force related to the
convective liquid force for
the slab moment

388332305.xlsx
● Slab moment in empty = 622.55 kN.m
condition
● Slab moment in Opr. = 12,114.28 kN.m
condition Attachment G - Page 19 of 37

388332305.xlsx
E.6 Anchor Bolt Design
Use: Anchor Bolt ASTM A307 Attachment G - Page 20 of 37
Bolt Circle Diameter, BCD = 12.72 m
db = = 1 in
= 25.4 mm
Ab = 506.7 mm2
ft = 137.3 MPa
fv = 68.6 MPa

nb = 36 ea
min distance to edge (E) = 160 mm
min bolt pitch (F) = 110 mm
min bolt embedment (Le) = 480 mm

BCD

Zp bolt = ( S n * ( BCDn / 2 )^2 ) / most outer BCD


Zp bolt = (36 x (12,72/2)^2 )/12,72
= 114.48 m

Unfactored Load Combination for anchor bolt design


Axial Horizontal Moment
Load Combination Condition
( kN ) ( kN ) ( kN.m )
LC 2-1 499.8 - - Permanent
Empty LC 2-2 499.8 43.8 245.6 Temporary
LC 2-3 499.8 80.9 435.8 Temporary
LC 2-4 10,309.8 - - Permanent
Operation LC 2-5 10,309.8 43.8 245.6 Temporary
LC 2-6 10,309.8 1,347.1 8,480.0 Temporary
LC 2-7 12,193.4 - - Testing
Testing
LC 2-8 12,193.4 14.6 81.9 Testing

Maximum Unfactored Forces Applied to Single Anchor Bolt:


P/n H/n M/Zp P/n - M/Zp
Load Combination Condition
( kN ) ( kN ) ( kN ) (kN)
LC 2-1 13.88 - - 13.88 Permanent
Empty LC 2-2 13.88 1.22 6.82 7.06 Temporary
LC 2-3 13.88 2.25 12.11 1.78 Temporary
LC 2-4 286.38 - - 286.38 Permanent
Operation LC 2-5 286.38 1.22 6.82 279.56 Temporary
LC 2-6 286.38 37.42 235.56 50.83 Temporary
LC 2-7 338.70 - - 338.70 Testing
Testing
LC 2-8 338.70 0.41 2.27 336.43 Testing

Anchor Bolt for Sliding Resistance


Hmax = 1347.14 kN
Vs = µ*(Ws + Wr + Wf + Wp) (resistance to sliding)
where:
µ = 0.40 (friction coefficient)
Vs = 4123.94 kN > Hmax = 1347.14 kN
resistance sliding > calculated shear, so no need anchor bolt for sliding resistance

388332305.xlsx
Anchor Bolt for Tension Resistance
Bolt shear and tension combination for A307:
ft allowable = 26 - 1.8fv <= 20 (ksi) or (179 - 1.8fv < 137 [MPa])
fv = H/(n x Abolt) Attachment G - Page 21 of 37
Tall = Ft allowable x Abolt

Anchor bolt capacity check


fv Tall T
Load Combination Remark
( MPa ) ( kN ) ( kN )
LC 2-1 0.000 69 COMP. No Tension - OK
Empty LC 2-2 0.002 69 COMP. No Tension - OK
LC 2-3 0.004 69 COMP. No Tension - OK
LC 2-4 0.000 69 COMP. No Tension - OK
Operation LC 2-5 0.002 69 COMP. No Tension - OK
LC 2-6 0.074 69 COMP. No Tension - OK
LC 2-7 0.000 69 COMP. No Tension - OK
Testing
LC 2-8 0.001 69 COMP. No Tension - OK

Anchor Bolt for Uplift Resistance

Mechanical Calc. For Tank (these cell should be taken from mechanical data sheet, all this
value are only assumption)
D = 41.076 ft (tank OD)
P = 69.120 inches H2O (design pressure)
Pt = 86.400 inches H2O (test pressure = 1.25 P)
th = 0.315 in (roof plate thicknesss)
Mw = 181,144.598 ft-lbf (wind moment)
Mrw = 1,419,425.501 ft-lbf (seismic ringwall moment)
W1 = 70,733.690 lbf (corroded shell + shell insulation)
W2 = 91,568.833 lbf (corroded shell + shell insulation + corroded
roof plates)
W3 = 86,990.391 lbf (new shell + shell insulation)

Uplift (U) Case 1: Design Pressure Only


U = [(P-8*th)*D^2*4.08]-W1
= [(69,12-8*0,315)*41,076^2*4.08]-70733,6902882112
= 387,727.484 lbf
Uplift per anchor (bt) = U/nb
= 387727,484/
= 10,770 lbf
Sd = 15,000 psi (allowable anchor bolt stress)
Asr = Bolt Root Area Req'd
= bt/Sd
= 0.72 in2
db-needed = 0.96 in > db = 1 in OK!

Uplift (U) Case 2: Test Pressure Only


U = [(Pt-8th)*D^2*4.08]-W1
= [(86,4-8*0,315)*41,076^2*4.08]-70733,6902882112
= 506,679.573 lbf
Uplift per anchor (bt) = U/nb
= 506679,573/
= 14,074 lbf
Sd = 20000 psi (allowable anchor bolt stress)

388332305.xlsx
Asr = Bolt Root Area Req'd
= bt/Sd
= 0.70 in2
db-needed = 0.95 in > db = 1 in OK!
Attachment G - Page 22 of 37

Uplift (U) Case 3: Failure Pressure Only


Not applicable since if there is a knuckle on tank roof, or tank roof is not frangible.

Uplift (U) Case 4: Wind Load Only


PWR = Wind Uplift /5.208
= 0/5.208
= 0.00 in. H2O
PWS = vF*18
= 0.36*18
= 6.48 lbf/ft^2
MWH = PWS*(D+t_ins/6)*H^2/2
= 6,48*(41,076+2/6)*52.4934^2/2
369699.30 ft-lbf
U = PWR*D^2*4.08+(4*MWH/D)-W2
= 0*41,076^2*4.08+(4*369699,299/41,076)-91568,833
= (55,567.006) lbf
Uplift per anchor (bt) = U/nb
= -55567,006/
= (1,544) lbf
Sd = 0.8*36000 (allowable anchor bolt stress)
= 28800 psi
Asr = Bolt Root Area Req'd
Not Applicable since load per bolt is zero

Uplift (U) Case 5: Seismic Load Only


U = [4*Mrw/D]-W2*(1-0.4*Av)
= [4*1419426/41,076]-91568,8326525452*(1-0.4*0)
= 46,656.776 lbf
Uplift per anchor (bt) = U/nb
= 46656,776/
= 1,296 lbf
Sd = 0.8*fy (allowable anchor bolt stress)
= 0.8*36000
= 28800 psi
Asr = Bolt Root Area Req'd
= bt/Sd
= 0.05 in2
db-needed = 0.24 in > db = 1 in OK!

Uplift (U) Case 6: Design Pressure + Wind Load


U = [(0.4*P+PWR-8*t_h)*D^2*4.08]+[4*MWH/D]-W1
= [(0.4*69+0-8*0.315)*41^2*4.08]+[4*369699/41]-70734
= 138,244.298 lbf
Uplift per anchor (bt) = U/nb
= 138244,298/
= 3,840 lbf
Sd = 20000 psi (allowable anchor bolt stress)
Asr = Bolt Root Area Req'd
= bt/Sd
= 0.19 in2

388332305.xlsx
db-needed = 0.49 in > db = 1 in OK!

Uplift (U) Case 7: Design Pressure + Seismic Load


U = [(0.4*P-8*t_h)*D^2*4.08]+[4*Mrw/D]-W1*(1-0.4*Av)
Attachment G - Page 23 of 37
= [(0.4*69-8*0.315)*41^2*4.08]+[4*1419426/41]-70734*(1-0.4*0)
= 240,468.080 lbf
Uplift per anchor (bt) = U/nb
= 240468,08/
= 6,680 lbf
Sd = 28800 psi (allowable anchor bolt stress)
Asr = Bolt Root Area Req'd
= bt/Sd
= 0.23 in2
db-needed = 0.54 in > db = 1 in OK!

Uplift (U) Case 8: Frangibility Pressure


Not applicable since if there is a knuckle on tank roof, or tank roof is not frangible

388332305.xlsx
MUARA KARANG - MAKE UP WATER TANK

Attachment G - Page 24 of 37
Data:
Inner Dia = 8.50 m
Outside Dia = 8.52 m
Height = 7.83 m
Steel Unit Weight = 7,650.00 kg/m3
Water Unit Weight = 1,000.00 kg/m3
Operation Capacity = 300.00 m3
Design Capacity = 390.00 m3
Roof Inclination = 1 : 12 m/m (assumed)
Plate thickness = 10.00 mm (assumed)
D/H = 1.09
Cone Roof Height = 0.36 m

Raw Estimated Weight


Bottom = 4,361.45 kg
Sheel = 15,954.43 kg (assume: no increment of shell thickness)
Roof = 4,376.56 kg +
24,692.44 kg (assume: including support, column, etc)

Weight
Empty / Shut Down DE = 242.23 kN
Operating DO = 3,185.23 kN
Test DT = 4,068.13 kN

Wind Load
Wind Speed = 32.00 m/s (assumed)
Exposure = C
Structure Category = III
Topographic Factor = 1.00
Importance Factor = 1.15
wind directionality factor = 1.00
Wind Pressure = 699.09 N/m2
Gust Factor = 0.85
Height above top of fdn. = 8.19 m
thickness of footing = 0.50 m (assumed)
Force Coefficient = 0.50
Tank Projected Area = 69.74 m2
Wind Load = 20.72 kN
Moment due to wind load = 84.79 kN.m

Seismic Load
- weight of water in Op. = 2,943.00 kN

effective impulsive portion


- = 2,246.53 kN
of the liquid weight

effective convective
- (sloshing) portion of the = 733.11 kN
liquid weight
- sloshing period coefficient = 0.58

388332305.xlsx
natural period of the
- convective (sloshing) mode = 3.04 s
of behavior of the liquid

regional dependent Attachment G - Page 25 of 37


- transition period for longer = 4.00 s
period ground motion

convective design response


- spectrum accelearation = 0.37 %g
coefficient
- Importance factor = 1.25
- SDS = 0.56
- R = 3.00

Impulsive design response


- spectrum acceleration = 0.23 %g
coefficient
Seismic Load Empty Condition
- Vi in empty condition = 56.02 kN.m

Design base shear due to


- convective component of = 0.00 kN.m
the effective sloshing
weight (empty condition)

- Total design base shear in 56.02 kN.m


empty condition =

Seismic Load Opr. Condition


- Vi in operating condition = 575.58 kN.m
- Vc in operating condition = 272.68 kN.m

- total design base shear in = 636.90 kN.m


operating condition

Slab Moment:

height from the bottom of


- the tank shell to the shell's = 3.92 m
center of gravity

height from the bottom of


- the tank shell to the roof = 7.95 m
and roof appurtenaces
center of gravity

height from the bottom of


the tank shell to the center
- of action of the lateral = 4.43 m
seismic force related to the
impulsive liquid force for the
slab moment

height from the bottom of


the tank shell to the center
- of action of the lateral = 5.81 m
seismic force related to the
convective liquid force for
the slab moment

388332305.xlsx
● Slab moment in empty = 220.62 kN.m
condition
● Slab moment in Opr. = 2,976.95 kN.m
condition Attachment G - Page 26 of 37

388332305.xlsx
E.6 Anchor Bolt Design
Use: Anchor Bolt ASTM A307 Attachment G - Page 27 of 37
Bolt Circle Diameter, BCD = 8.72 m
db = = 1 in
= 25.4 mm
Ab = 506.7 mm2
ft = 137.3 MPa
fv = 68.6 MPa

nb = 16 ea
min distance to edge (E) = 160 mm
min bolt pitch (F) = 110 mm
min bolt embedment (Le) = 480 mm

BCD

Zp bolt = ( S n * ( BCDn / 2 )^2 ) / most outer BCD


Zp bolt = (16 x (8,72/2)^2 )/8,72
= 34.88 m

Unfactored Load Combination for anchor bolt design


Axial Horizontal Moment
Load Combination Condition
( kN ) ( kN ) ( kN.m )
LC 2-1 242.2 - - Permanent
Empty LC 2-2 242.2 20.7 84.8 Temporary
LC 2-3 242.2 39.2 154.4 Temporary
LC 2-4 3,185.2 - - Permanent
Operation LC 2-5 3,185.2 20.7 84.8 Temporary
LC 2-6 3,185.2 445.8 2,083.9 Temporary
LC 2-7 4,068.1 - - Testing
Testing
LC 2-8 4,068.1 6.9 28.3 Testing

Maximum Unfactored Forces Applied to Single Anchor Bolt:


P/n H/n M/Zp P/n - M/Zp
Load Combination Condition
( kN ) ( kN ) ( kN ) (kN)
LC 2-1 15.14 - - 15.14 Permanent
Empty LC 2-2 15.14 1.29 5.30 9.84 Temporary
LC 2-3 15.14 2.45 9.65 5.49 Temporary
LC 2-4 199.08 - - 199.08 Permanent
Operation LC 2-5 199.08 1.29 5.30 193.78 Temporary
LC 2-6 199.08 27.86 130.24 68.84 Temporary
LC 2-7 254.26 - - 254.26 Testing
Testing
LC 2-8 254.26 0.43 1.77 252.49 Testing

Anchor Bolt for Sliding Resistance


Hmax = 445.83 kN
Vs = µ*(Ws + Wr + Wf + Wp) (resistance to sliding)
where:
µ = 0.40 (friction coefficient)
Vs = 1274.09 kN > Hmax = 445.83 kN
resistance sliding > calculated shear, so no need anchor bolt for sliding resistance

388332305.xlsx
Anchor Bolt for Tension Resistance
Bolt shear and tension combination for A307:
ft allowable = 26 - 1.8fv <= 20 (ksi) or (179 - 1.8fv < 137 [MPa])
fv = H/(n x Abolt) Attachment G - Page 28 of 37
Tall = Ft allowable x Abolt

Anchor bolt capacity check


fv Tall T
Load Combination Remark
( MPa ) ( kN ) ( kN )
LC 2-1 0.000 69 COMP. No Tension - OK
Empty LC 2-2 0.003 69 COMP. No Tension - OK
LC 2-3 0.005 69 COMP. No Tension - OK
LC 2-4 0.000 69 COMP. No Tension - OK
Operation LC 2-5 0.003 69 COMP. No Tension - OK
LC 2-6 0.055 69 COMP. No Tension - OK
LC 2-7 0.000 69 COMP. No Tension - OK
Testing
LC 2-8 0.001 69 COMP. No Tension - OK

Anchor Bolt for Uplift Resistance

Mechanical Calc. For Tank (these cell should be taken from mechanical data sheet, all this
value are only assumption)
D = 27.952 ft (tank OD)
P = 69.120 inches H2O (design pressure)
Pt = 86.400 inches H2O (test pressure = 1.25 P)
th = 0.315 in (roof plate thicknesss)
Mw = 62,541.402 ft-lbf (wind moment)
Mrw = 469,755.440 ft-lbf (seismic ringwall moment)
W1 = 35,173.453 lbf (corroded shell + shell insulation)
W2 = 44,822.113 lbf (corroded shell + shell insulation + corroded
roof plates)
W3 = 42,581.008 lbf (new shell + shell insulation)

Uplift (U) Case 1: Design Pressure Only


U = [(P-8*th)*D^2*4.08]-W1
= [(69,12-8*0,315)*27,952^2*4.08]-35173,4534066135
= 177,137.839 lbf
Uplift per anchor (bt) = U/nb
= 177137,839/
= 11,071 lbf
Sd = 15,000 psi (allowable anchor bolt stress)
Asr = Bolt Root Area Req'd
= bt/Sd
= 0.74 in2
db-needed = 0.97 in > db = 1 in OK!

Uplift (U) Case 2: Test Pressure Only


U = [(Pt-8th)*D^2*4.08]-W1
= [(86,4-8*0,315)*27,952^2*4.08]-35173,4534066135
= 232,224.012 lbf
Uplift per anchor (bt) = U/nb
= 232224,012/
= 14,514 lbf
Sd = 20000 psi (allowable anchor bolt stress)

388332305.xlsx
Asr = Bolt Root Area Req'd
= bt/Sd
= 0.73 in2
db-needed = 0.96 in > db = 1 in OK!
Attachment G - Page 29 of 37

Uplift (U) Case 3: Failure Pressure Only


Not applicable since if there is a knuckle on tank roof, or tank roof is not frangible.

Uplift (U) Case 4: Wind Load Only


PWR = Wind Uplift /5.208
= 0/5.208
= 0.00 in. H2O
PWS = vF*18
= 0.36*18
= 6.48 lbf/ft^2
MWH = PWS*(D+t_ins/6)*H^2/2
= 6,48*(27,952+2/6)*52.4934^2/2
252535.31 ft-lbf
U = PWR*D^2*4.08+(4*MWH/D)-W2
= 0*27,952^2*4.08+(4*252535,306/27,952)-44822,113
= (8,684.227) lbf
Uplift per anchor (bt) = U/nb
= -8684,227/
= (543) lbf
Sd = 0.8*36000 (allowable anchor bolt stress)
= 28800 psi
Asr = Bolt Root Area Req'd
Not Applicable since load per bolt is zero

Uplift (U) Case 5: Seismic Load Only


U = [4*Mrw/D]-W2*(1-0.4*Av)
= [4*469755/27,952]-44822,1134309831*(1-0.4*0)
= 22,400.046 lbf
Uplift per anchor (bt) = U/nb
= 22400,046/
= 1,400 lbf
Sd = 0.8*fy (allowable anchor bolt stress)
= 0.8*36000
= 28800 psi
Asr = Bolt Root Area Req'd
= bt/Sd
= 0.05 in2
db-needed = 0.25 in > db = 1 in OK!

Uplift (U) Case 6: Design Pressure + Wind Load


U = [(0.4*P+PWR-8*t_h)*D^2*4.08]+[4*MWH/D]-W1
= [(0.4*69+0-8*0.315)*28^2*4.08]+[4*252535/28]-35173
= 81,068.910 lbf
Uplift per anchor (bt) = U/nb
= 81068,91/
= 5,067 lbf
Sd = 20000 psi (allowable anchor bolt stress)
Asr = Bolt Root Area Req'd
= bt/Sd
= 0.25 in2

388332305.xlsx
db-needed = 0.57 in > db = 1 in OK!

Uplift (U) Case 7: Design Pressure + Seismic Load


U = [(0.4*P-8*t_h)*D^2*4.08]+[4*Mrw/D]-W1*(1-0.4*Av)
Attachment G - Page 30 of 37
= [(0.4*69-8*0.315)*28^2*4.08]+[4*469755/28]-35173*(1-0.4*0)
= 112,153.183 lbf
Uplift per anchor (bt) = U/nb
= 112153,183/
= 7,010 lbf
Sd = 28800 psi (allowable anchor bolt stress)
Asr = Bolt Root Area Req'd
= bt/Sd
= 0.24 in2
db-needed = 0.56 in > db = 1 in OK!

Uplift (U) Case 8: Frangibility Pressure


Not applicable since if there is a knuckle on tank roof, or tank roof is not frangible

388332305.xlsx
MUARA KARANG - FIRE FIGHTER WATER TANK

Attachment G - Page 31 of 37
Data:
Inner Dia = 12.20 m
Outside Dia = 12.22 m
Height = 10.67 m
Steel Unit Weight = 7,650.00 kg/m3
Water Unit Weight = 1,000.00 kg/m3
Operation Capacity = 950.00 m3
Design Capacity = 1,192.00 m3
Roof Inclination = 1 : 12 m/m (assumed)
Plate thickness = 10.00 mm (assumed)
D/H = 1.14
Cone Roof Height = 0.51 m

Raw Estimated Weight


Bottom = 8,972.09 kg
Sheel = 31,226.32 kg (assume: no increment of shell thickness)
Roof = 9,003.19 kg +
49,201.60 kg (assume: including support, column, etc)

Weight
Empty / Shut Down DE = 482.67 kN
Operating DO = 9,802.17 kN
Test DT = 12,176.19 kN

Wind Load
Wind Speed = 32.00 m/s (assumed)
Exposure = C
Structure Category = III
Topographic Factor = 1.00
Importance Factor = 1.15
wind directionality factor = 1.00
Wind Pressure = 732.72 N/m2
Gust Factor = 0.85
Height above top of fdn. = 11.18 m
thickness of footing = 0.50 m (assumed)
Force Coefficient = 0.50
Tank Projected Area = 136.61 m2
Wind Load = 42.54 kN
Moment due to wind load = 237.79 kN.m

Seismic Load
- weight of water in Op. = 9,319.50 kN

effective impulsive portion


- = 6,996.53 kN
of the liquid weight

effective convective
- (sloshing) portion of the = 2,442.87 kN
liquid weight
- sloshing period coefficient = 0.58

388332305.xlsx
natural period of the
- convective (sloshing) mode = 3.64 s
of behavior of the liquid

regional dependent Attachment G - Page 32 of 37


- transition period for longer = 4.00 s
period ground motion

convective design response


- spectrum accelearation = 0.26 %g
coefficient
- Importance factor = 1.25
- SDS = 0.56
- R = 3.00

Impulsive design response


- spectrum acceleration = 0.23 %g
coefficient
Seismic Load Empty Condition
- Vi in empty condition = 111.63 kN.m

Design base shear due to


- convective component of = 0.00 kN.m
the effective sloshing
weight (empty condition)

- Total design base shear in 111.63 kN.m


empty condition =

Seismic Load Opr. Condition


- Vi in operating condition = 1,729.72 kN.m
- Vc in operating condition = 632.47 kN.m

- total design base shear in = 1,841.73 kN.m


operating condition

Slab Moment:

height from the bottom of


- the tank shell to the shell's = 5.34 m
center of gravity

height from the bottom of


- the tank shell to the roof = 10.84 m
and roof appurtenaces
center of gravity

height from the bottom of


the tank shell to the center
- of action of the lateral = 6.07 m
seismic force related to the
impulsive liquid force for the
slab moment

height from the bottom of


the tank shell to the center
- of action of the lateral = 7.86 m
seismic force related to the
convective liquid force for
the slab moment

388332305.xlsx
● Slab moment in empty = 599.34 kN.m
condition
● Slab moment in Opr. = 11,540.58 kN.m
condition Attachment G - Page 33 of 37

388332305.xlsx
E.6 Anchor Bolt Design
Use: Anchor Bolt ASTM A307 Attachment G - Page 34 of 37
Bolt Circle Diameter, BCD = 12.42 m
db = = 1 1/2 in
= 38.1 mm
Ab = 1140.1 mm2
ft = 137.3 MPa
fv = 68.6 MPa

nb = 14 ea
min distance to edge (E) = 230 mm
min bolt pitch (F) = 160 mm
min bolt embedment (Le) = 640 mm

BCD

Zp bolt = ( S n * ( BCDn / 2 )^2 ) / most outer BCD


Zp bolt = (14 x (12,42/2)^2 )/12,42
= 43.47 m

Unfactored Load Combination for anchor bolt design


Axial Horizontal Moment
Load Combination Condition
( kN ) ( kN ) ( kN.m )
LC 2-1 482.7 - - Permanent
Empty LC 2-2 482.7 42.5 237.8 Temporary
LC 2-3 482.7 78.1 419.5 Temporary
LC 2-4 9,802.2 - - Permanent
Operation LC 2-5 9,802.2 42.5 237.8 Temporary
LC 2-6 9,802.2 1,289.2 8,078.4 Temporary
LC 2-7 12,176.2 - - Testing
Testing
LC 2-8 12,176.2 14.2 79.3 Testing

Maximum Unfactored Forces Applied to Single Anchor Bolt:


P/n H/n M/Zp P/n - M/Zp
Load Combination Condition
( kN ) ( kN ) ( kN ) (kN)
LC 2-1 34.48 - - 34.48 Permanent
Empty LC 2-2 34.48 3.04 16.98 17.49 Temporary
LC 2-3 34.48 5.58 29.97 4.51 Temporary
LC 2-4 700.15 - - 700.15 Permanent
Operation LC 2-5 700.15 3.04 16.98 683.17 Temporary
LC 2-6 700.15 92.09 577.03 123.13 Temporary
LC 2-7 869.73 - - 869.73 Testing
Testing
LC 2-8 869.73 1.01 5.66 864.07 Testing

Anchor Bolt for Sliding Resistance


Hmax = 1289.21 kN
Vs = µ*(Ws + Wr + Wf + Wp) (resistance to sliding)
where:
µ = 0.40 (friction coefficient)
Vs = 3920.87 kN > Hmax = 1289.21 kN
resistance sliding > calculated shear, so no need anchor bolt for sliding resistance

388332305.xlsx
Anchor Bolt for Tension Resistance
Bolt shear and tension combination for A307:
ft allowable = 26 - 1.8fv <= 20 (ksi) or (179 - 1.8fv < 137 [MPa])
fv = H/(n x Abolt) Attachment G - Page 35 of 37
Tall = Ft allowable x Abolt

Anchor bolt capacity check


fv Tall T
Load Combination Remark
( MPa ) ( kN ) ( kN )
LC 2-1 0.000 156 COMP. No Tension - OK
Empty LC 2-2 0.003 156 COMP. No Tension - OK
LC 2-3 0.005 156 COMP. No Tension - OK
LC 2-4 0.000 156 COMP. No Tension - OK
Operation LC 2-5 0.003 156 COMP. No Tension - OK
LC 2-6 0.081 156 COMP. No Tension - OK
LC 2-7 0.000 156 COMP. No Tension - OK
Testing
LC 2-8 0.001 156 COMP. No Tension - OK

Anchor Bolt for Uplift Resistance

Mechanical Calc. For Tank (these cell should be taken from mechanical data sheet, all this
value are only assumption)
D = 40.091 ft (tank OD)
P = 69.120 inches H2O (design pressure)
Pt = 86.400 inches H2O (test pressure = 1.25 P)
th = 0.315 in (roof plate thicknesss)
Mw = 175,382.351 ft-lbf (wind moment)
Mrw = 1,358,386.747 ft-lbf (seismic ringwall moment)
W1 = 68,842.160 lbf (corroded shell + shell insulation)
W2 = 88,690.776 lbf (corroded shell + shell insulation + corroded
roof plates)
W3 = 84,256.237 lbf (new shell + shell insulation)

Uplift (U) Case 1: Design Pressure Only


U = [(P-8*th)*D^2*4.08]-W1
= [(69,12-8*0,315)*40,091^2*4.08]-68842,1601434253
= 367,911.262 lbf
Uplift per anchor (bt) = U/nb
= 367911,262/
= 26,279 lbf
Sd = 15,000 psi (allowable anchor bolt stress)
Asr = Bolt Root Area Req'd
= bt/Sd
= 1.75 in2
db-needed = 1.49 in > db = 1 1/2 in OK!

Uplift (U) Case 2: Test Pressure Only


U = [(Pt-8th)*D^2*4.08]-W1
= [(86,4-8*0,315)*40,091^2*4.08]-68842,1601434253
= 481,231.069 lbf
Uplift per anchor (bt) = U/nb
= 481231,069/
= 34,374 lbf
Sd = 20000 psi (allowable anchor bolt stress)

388332305.xlsx
Asr = Bolt Root Area Req'd
= bt/Sd
= 1.72 in2
db-needed = 1.48 in > db = 1 1/2 in OK!
Attachment G - Page 36 of 37

Uplift (U) Case 3: Failure Pressure Only


Not applicable since if there is a knuckle on tank roof, or tank roof is not frangible.

Uplift (U) Case 4: Wind Load Only


PWR = Wind Uplift /5.208
= 0/5.208
= 0.00 in. H2O
PWS = vF*18
= 0.36*18
= 6.48 lbf/ft^2
MWH = PWS*(D+t_ins/6)*H^2/2
= 6,48*(40,091+2/6)*52.4934^2/2
360912.00 ft-lbf
U = PWR*D^2*4.08+(4*MWH/D)-W2
= 0*40,091^2*4.08+(4*360912/40,091)-88690,776
= (52,681.835) lbf
Uplift per anchor (bt) = U/nb
= -52681,835/
= (3,763) lbf
Sd = 0.8*36000 (allowable anchor bolt stress)
= 28800 psi
Asr = Bolt Root Area Req'd
Not Applicable since load per bolt is zero

Uplift (U) Case 5: Seismic Load Only


U = [4*Mrw/D]-W2*(1-0.4*Av)
= [4*1358387/40,091]-88690,7759877116*(1-0.4*0)
= 46,838.296 lbf
Uplift per anchor (bt) = U/nb
= 46838,296/
= 3,346 lbf
Sd = 0.8*fy (allowable anchor bolt stress)
= 0.8*36000
= 28800 psi
Asr = Bolt Root Area Req'd
= bt/Sd
= 0.12 in2
db-needed = 0.38 in > db = 1 1/2 in OK!

Uplift (U) Case 6: Design Pressure + Wind Load


U = [(0.4*P+PWR-8*t_h)*D^2*4.08]+[4*MWH/D]-W1
= [(0.4*69+0-8*0.315)*40^2*4.08]+[4*360912/40]-68842
= 131,952.667 lbf
Uplift per anchor (bt) = U/nb
= 131952,667/
= 9,425 lbf
Sd = 20000 psi (allowable anchor bolt stress)
Asr = Bolt Root Area Req'd
= bt/Sd
= 0.47 in2

388332305.xlsx
db-needed = 0.77 in > db = 1 1/2 in OK!

Uplift (U) Case 7: Design Pressure + Seismic Load


U = [(0.4*P-8*t_h)*D^2*4.08]+[4*Mrw/D]-W1*(1-0.4*Av)
Attachment G - Page 37 of 37
= [(0.4*69-8*0.315)*40^2*4.08]+[4*1358387/40]-68842*(1-0.4*0)
= 231,472.798 lbf
Uplift per anchor (bt) = U/nb
= 231472,798/
= 16,534 lbf
Sd = 28800 psi (allowable anchor bolt stress)
Asr = Bolt Root Area Req'd
= bt/Sd
= 0.57 in2
db-needed = 0.85 in > db = 1 1/2 in OK!

Uplift (U) Case 8: Frangibility Pressure


Not applicable since if there is a knuckle on tank roof, or tank roof is not frangible

388332305.xlsx