RAM Concrete
Shear Wall Design Verification
Example
This document is intended to provide technical verification for the analysis and design results within the
RAM Concrete Shear Wall design module for a sample RAM Structural System model. This example
utilizes RAM Structural System v8i, SELECTseries1, Release 14.00.00.00, which is available for
download on Bentley SELECT.
The scope of this document is limited to providing sufficient technical background so that the user may
reproduce the design results and calculations performed in the design module. This document does not
intend to exhaustively report the design results for the entire model.
Figure 1 – RAM Frame 3D view showing wall and floor slab mesh
Model Overview:
(4) full stories plus (1) partial story (62”-0” total height)
195’ long by 75’ wide footprint
9” concrete flat slab floors
12” + 18” interior concrete shear walls
Perimeter special moment frames: 20” wide by 24” deep beams with 20” square columns
20” square gravity columns, plus 24” diameter circular columns at curved perimeter
Design Criteria:
IBC 2006
o Bearing Wall System – Special Reinforced Concrete Shear Walls
o Occupancy Category “I”
o Site Class “C”
ACI 318-08
o Special Reinforced Concrete Walls & Special Moment Resisting Frames
Floor Loads:
Office: 25 psf superimposed dead, 60 psf reducible live, 12 psf superimposed mass
Storage: 5 psf superimposed dead, 150 psf storage, 12 psf superimposed mass
Roof: 20 psf superimposed dead, 20 psf roof, 10 psf superimposed mass
Wind Loads:
Exposure: B
Basic Wind Speed: 90 mph
Topographical Factor, Kzt = 1.0
Directionality Factor, Kd = 0.85
Seismic Loads:
Equivalent Lateral Force Procedure
Response Modification Coefficient, R = 5.0
Displacement Amplification Factor, Cd = 5.0
Importance Factor, I = 1.0
Ss = 1.00, S1 = 0.30
Analysis Assumptions:
All floors treated as two-way, semi-rigid diaphragms with maximum mesh node spacing of 4 ft
P-Delta effects considered with scale factor of 1.0
Out-of-plane wall stiffness ignored
Rigid end zone effects ignored
Columns braced against sidesway by walls
Effective length factor K = 0.9 used for columns supporting bare slab only
Material Properties:
Strengths
Floor slabs & beams: f’c = 5,000 psi, fy = 60 ksi
Columns: f’c = 5,000 psi, fy = 60 ksi
Walls: f’c = 5,000 psi, fy = 60 ksi (8,000 psi at lower levels of center core)
Crack Factors
Beams: 1.00 (axial), 0.35 (flexure), 0.10 (torsion)
Columns: 1.00 (axial), 0.70 (flexure), 1.00 (torsion)
Walls: 0.35
Headers: 0.20
2 Wall Design Forces used by RAM Concrete
Figure 3 shows a screen shot of the View/Update dialog for Wall Design Group 2. The currently selected
Section Cut is SC2H:20 (at the base of the wall) and the tabular data in the Results page reflect this Section
Cut, as does the cross-section view at the bottom center. The worst case interaction value for axial/flexural
design is produced by Load Combination 336, 0.9D – 1.4E7, as shown directly above the tabular data
sheet. Vertical reinforcement within wall boundaries is colored red in the 3D view box (upper left).
Confinement ties are shown in boundary regions in the cross section sketch.
The term E7 in the controlling load combination 0.9D – 1.4E7 represents the load case EQ_IBC06_-
X_+E_0.3Y_+E_F from the RAM Frame analysis. The applied story forces for this load case are shown in
the RAM Frame Loads and Applied Forces report below.
Figure 4 – RAM Frame Loads and Applied Forces report
Load case E7 coincides with the full negative X-Direction seismic story force applied coincidentally with
30% of the positive Y-direction seismic story force, with both loads applied at an eccentricity that generates
a positive Z-axis moment. This is illustrated in Figure 5.
Figure 5 – Orientation of applied loads with respect to mass center for seismic load case E7
The design forces at the Section Cut SC2H:20 can be verified, among other means, by forming a Wall
Group in RAM Frame of the same extents as the Section Cut. The resultant forces at the base of the Wall
Group for each load case or load combination can then be processed.
The forces at the base of RAM Frame Wall Group 2 are listed in Table 1.
Note: The RAM Frame Wall Group forces listed above are taken at the wall base, and thus the moments
will be slightly larger in magnitude than the corresponding moments at Section Cut SC2H:20, which is
located 6 in above the base. These forces can be viewed in Figure 3 immediately below the spreadsheet
area.
Figure 7 through Figure 12 show RAM Frame screen shots for Wall Group 2 forces for each load case for
axial loads and moments.
Figure 7 – Wall Group axial forces for Dead Load case from RAM Frame
Figure 8 – Wall Group major moments for Dead Load case from RAM Frame
Figure 9 – Wall Group minor moments for Dead Load case from RAM Frame
Figure 10 – Wall Group axial forces for seismic load case from RAM Frame
Figure 11 – Wall Group major moments for seismic load case from RAM Frame
Figure 12 – Wall Group minor moments for seismic load case from RAM Frame
Design shear forces can be verified in a similar manner. For Section Cut Segment SC2H:20A, the
controlling load combination is 156, 1.2D + 0.5Lp + 1.4E7. For Section Cut Segment SC2H:20B, the
controlling load combination is 303, 0.9D + 1.4E10. The design shear forces are summarized in Table 2.
The term E10 represents the load case EQ_IBC06_0.3X_+E_-Y_+E_F from RAM Frame.
The shear strength calculation is per ACI 318-08, Sections 11.9.6 (as specified in the design criteria setting)
and 11.9.9. The relevant parameters are summarized in Table 3:
Equation (11-27):
Nud 1381.79 × 16.0
Vc = 3.3λ f c' hd + = 3.3 × 1.0 × 8,000 × 18.0"×16.0'×12 / 1000 + = 1296.44
4l w 4 × 20.0
Equation (11-28):
N
l w 1.25 f c' + 0.2 u
lw h
Vc = 0.6λ f c' + hd
M u lw
−
Vu 2
240.0 × (111.80 + 63.97 )
Vc = 53.67 + × 18.0 × 16.0 × 12 = 1073.37
227.25 − 120.0
Thus,
φVn = 0.75 x 2803.64 = 2102.73 kips
Since this system is considered a Special Reinforced Concrete Shear Wall per ACI 318, the shear strength
per Section 21.9.4.1 is also evaluated,
Equation (21-7):
(
Vn = Acv α c λ f c' + ρ t f y )
hw/Lw = 14’/20’ = 0.7 < 1.5
thus, αc = 3.0
Equation (10-2):
φ = 0.65
Ag = 20.5’x12x18” + 8.25’x12x12” = 5616 in2
As = 84.0 in2 (see table below)
Total 84.0
φPn ,max = 0.80 × 0.65 × [0.85 × 8.0 × (5616.0 − 84.0 ) + 60.0 × 84.0] = 22,181.95 kips
The worst case axial-flexural interaction is produced by load combination 336, 0.9D - 1.4E7, which
produces the following design forces on the section:
Pu = 240.05 kips
Verify Section SC2H:20 under load combination 113, 1.2D + 0.5Lp – 1.4E3.
From ACI 318-08, Section 21.9.6.2, compression zones shall be reinforced with special boundary elements
where:
lw
c≥ ACI Equation (21-8)
δu
600
hw
RAM Concrete calculates δu as the average horizontal displacement at the top of the Wall Design Group
minus the average horizontal displacement at the Section Cut under consideration. The average horizontal
displacement at the top of Wall Design Group 2 can be verified from the RAM Frame nodal displacements
report. Figure 15 shows the node numbers at the top of Wall Design Group 2. Table 5 lists the
displacements at these nodes for load combination 1.2D + 0.5Lp – 1.4E3.
Table 5 – Nodal deflections from RAM Frame for controlling seismic load combination
δu/hw = 3.4837/(62x12) = 0.00468 < 0.007, thus use δu/hw = 0.007 in ACI equation (21-8):
11.93 × 12
c≥ = 34.09 in = 2.840 ft
600 × 0.007
The required length of the boundary is specified in ACI 318-08, Section 21.9.6.4, and is equal to the lesser
of:
Figure 16 – Boundary element evaluation for load combination 1.2D + 0.5Lp - 1.4E3
In this example, boundary regions have been assigned to the Wall Panels using the Assign -> Manual
Reinforcement command. They have been laid out so that the resulting boundary length exceeds the
minimum required length for each load combination as solved for above. In Figure 16, each of the
boundary regions is tied off as shown in the cross section sketch at the bottom. The point of maximum
compression within the Section Cut for the selected load combination is denoted with a black dot. The
required boundary length is then dimensioned from that point as shown in the screen shot. If any
reinforcing zones not designated as boundaries lie within this region, a design failure will be issued on the
Design Warnings tab. In the scenario above, a boundary has been assigned so that the requirement is
fulfilled.
The Tie/Link Design sheet provides the transverse reinforcement calculations for the each of the boundary
zones that intersect the selected Section Cut.
6 Special Boundary Tie Design
The design of transverse reinforcement in confinement zones is per ACI 318-08, Section 21.6.4.
Equation (21-5),
The spacing of transverse reinforcing shall also conform to ACI 318-08, Section 21.6.4.3, which states the
spacing of transverse reinforcing shall not exceed the smallest of:
Therefore, the controlling maximum tie spacing for reinforcing zone 1 is 2.05 in.
Figure 17 – Boundary zone tie design for Section Cut