Académique Documents
Professionnel Documents
Culture Documents
This article was published in ASHRAE Journal, October 2014. Copyright 2014 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or
distributed electronically or in paper form without permission of ASHRAE. For more information about ASHRAE Journal, visit www.ashrae.org.
Simplified Chiller
Sequencing
For a Primary/Secondary Variable Chilled Water Flow System
BY MARSHALL SEYMORE, P.E., MEMBER ASHRAE
To fully automate the central chilled water plant operation at the University of West
Florida in Pensacola, Florida, the challenge was to control the primary (production)
chilled water flow to equal the secondary (distribution) chilled water flow demand for
a variable primary flow and variable secondary flow system.
The central chilled water plant consists of four 1,200 •• The chillers were selected based on an entering chilled
ton (4,220 kW) centrifugal chillers, four dedicated pri- water temperature of 60°F (15.56°C) and a leaving chilled
mary chilled water pumps (PCWP), three secondary water temperature of 42°F (5.56°C) (18°F (10°C) DT).
chilled water pumps (SCWP) and an automation control •• The campus chilled water coil designs ranged from
system. The chilled water system was a classic primary- 10°F (5.56°C) DT to 15.0°F (8.34°C) DT with entering
secondary-decoupler piping arrangement with a check chilled water temperatures from 42°F (5.56°C) to 45.0°F
valve, temperature sensor and flow measurement ele- (7.22°C).
ment in the decoupler piping. The campus air-handling •• Over pumping through the decoupler piping.
unit chilled water coils use two-way control valves. The Actions taken to address these issues:
chilled water plant had all the automation controls •• Remove the check valve from the decoupler piping.
needed for full automatic control but was being manu- This was necessary to hydraulically decouple the primary
ally operated. and secondary pumping to allow flow through the de-
In addition to fully automating the sequencing of chill- coupler piping in both directions to facilitate this control
ers, actions were also needed to address: approach.
•• Underuse of installed chiller capacity. Chillers could •• Install a set of matched temperature sensors indi-
only reach 70% of full load capacity. cated in Figure 1.
•• Unable to maintain the secondary chilled water •• Develop a temperature based flow approach by ana-
design supply temperature equal to or less than 42°F lyzing and determining the flow dynamics in the decou-
(5.56°C). pler piping shown in Figure 2.
Marshall Seymore, P.E., is director of utilities and environmental sustainability at the University of West Florida in Pensacola, Fla.
24 A S H R A E J O U R N A L a s h r a e . o r g O CT O B E R 2 0 1 4
TECHNICAL FEATURE
Primary Flow % =
100 × [1-(T2-T1)/(T3-T1)] (Eq. 5)
Secondary (Distribution) Secondary (Distribution)
Secondary Flow % = Chilled Water Return Chilled Water Supply
100 × [1 – (T3 – T4)/(T3 – T1)] (Eq. 6)
O CT O B E R 2 0 1 4 a s h r a e . o r g A S H R A E J O U R N A L 25
TECHNICAL FEATURE
O CT O B E R 2 0 1 4 a s h r a e . o r g A S H R A E J O U R N A L 27
TECHNICAL FEATURE
secondary chilled water supply temperature equal to or requirements while maintaining secondary chilled
less than design. water supply temperature equal to or less than
design.
Primary Flow % = 100 × (Secondary Flow minus
Decoupler Flow)/Secondary Flow Secondary Flow % = 100 ×
(Primary Flow minus Decoupler Flow)/Primary Flow
Primary Flow % = 100 × (1 – x1)
Secondary Flow % = 100 × (1- x2)
x1 = (T2 – T1)/(T3-T1) (Eq. 2)
Primary Flow % = 100 × [1 – (T2 – T1)/(T3 – T1)] (Eq. 5) x2 = (T3 – T4)/(T3 – T1) (Eq. 4)
•• When Primary Flow % is less than 100%, secondary Secondary Flow % = 100 ×[1 – (T3 – T4)/ (T3 – T1)]
flow is greater than primary flow; (Eq. 6)
•• When Primary Flow % is greater than 100%, primary
flow is greater than secondary flow; and •• When Secondary Flow % is less than 100%, primary
•• When Primary Flow % is equal to 100%, primary flow flow is greater than secondary flow;
equals secondary flow with zero flow through decoupler. •• When Secondary Flow % is greater than 100%, sec-
ondary flow is greater than primary flow; and
Secondary Flow % Calculation •• When Secondary Flow % is Equal to 100%, second-
The Secondary Flow % calculated value is used ary flow equals primary flow with zero flow through
to subtract chillers to meet secondary cooling load decoupler.
O CT O B E R 2 0 1 4 a s h r a e . o r g A S H R A E J O U R N A L 29
TECHNICAL FEATURE
30 A S H R A E J O U R N A L a s h r a e . o r g O CT O B E R 2 0 1 4
TECHNICAL FEATURE
Primary Flow % and Secondary Flow % flow calculations. for zero flow through the Decoupler piping would be
Control primary and secondary pump VFD speeds by 100%. The best Primary Flow % setpoint would be for T1
using a step speed control with a time delay to prevent to Equal T2 and T3 to equal T4 and T5 to equal T3. This
unstable flow condition in the chilled water piping that should be a field determined setpoint.
can be caused by using a modulating VFD speed con- Chiller discharge temperature controls must be
trol scheme. stable with small variations from setpoint.
The ideal Secondary Flow % setpoint to subtract a chiller
for an ideal system would be 95%. When one chiller is Conclusion
subtracted, the Primary Flow % calculation should not be Each action item was completed and these control
less than the Primary Flow % add chiller setpoint. This is a approach principles are currently being successfully
system specific value that must be determined by system used at the University of West Florida.
observation and should be a field determined setpoint. These control approach principles have been
The ideal Primary Flow % setpoint to add a chiller applied and have allowed:
for an ideal system would be 95%. When one chiller •• Chillers to be loaded to 100% capacity if required;
is added, the Secondary Flow % calculation should •• Secondary chilled water distribution temperature
not be less than the Secondary Flow % subtract chiller to be controlled to less than 42°F (5.56°C);
setpoint. This is a system specific value that must be •• Chillers to be automatically sequenced;
determined by system observation and should be a •• Decoupler flow to be minimized; and
field determined setpoint. •• Production flow to equal distribution flow by
The ideal Primary Flow % setpoint for an ideal system controlling primary pump VFD speed.
32 A S H R A E J O U R N A L a s h r a e . o r g O CT O B E R 2 0 1 4