Vous êtes sur la page 1sur 62

Chemical Engineering Program

Universiti Teknologi PETRONAS


May 2018

5/25/2018 Process Instrumentation and Control 1


5/25/2018 Process Instrumentation and Control 2
• End of the chapter, you should be able to:
1. describe basic components of P & ID
2. Describe basic control instruments
• Sensors and transmitters
• Controller
• Final control elements

5/25/2018 Process Instrumentation and Control 3


Piping & Instrumentation Diagram (P &ID)
• A piping and instrumentation diagram/drawing
(P&ID) is a diagram in the process industry which
shows the piping of the process flow together with
the installed equipment and instrumentation.
• P & ID shows the interconnection of process
equipment and the instrumentation used to control
the process.

5/25/2018 Process Instrumentation and Control 4


Piping and Instrument Diagram (P&ID)

Each instrument may be represented on diagram by a


symbol which follows specific standard representation

1. Petronas Technical Standard (PTS)


2. Standard ISA-5.1
(ISA stands for International Society of Automation)

• The symbol may be accompanied by a tag number

5/25/2018 Process Instrumentation and Control 5


Example of P & ID

5/25/2018 Process Instrumentation and Control 6


Example of P & ID- Zoom in

5/25/2018 Process Instrumentation and Control 7


Example of - PFD

5/25/2018 Process Instrumentation and Control 8


Example of PFD-Zoom in

5/25/2018 Process Instrumentation and Control 9


List of P & ID Items
List of P&ID items
• Instrumentation and designations
• Mechanical equipment with names and numbers
• All valves and their identifications
• Process piping, sizes and identification
• Miscellanea - vents, drains, special fittings, sampling lines, reducers,
increasers and swagers
• Permanent start-up and flush lines
• Flow directions
• Interconnections references
• Control inputs and outputs, interlocks
• Interfaces for class changes
• Computer control system input
• Identification of components and subsystems delivered by others

5/25/2018 Process Instrumentation and Control 10


P & ID Components
• P & ID is composed of
– Equipment symbols
– Basic Instrument or Function Symbols
– Instrument Line Symbols
– Tag Numbers

5/25/2018 Process Instrumentation and Control 11


Equipment symbols

Heat exchanger
Kettle Reboiler

Tray
column
Centrifugal
Cooling Tower Control valve
pump

5/25/2018 Process Instrumentation and Control 12


Basic Instrument or Function Symbols

5/25/2018 Process Instrumentation and Control 13


Equipment Symbols
the device is field mounted (located in the process
area of the plant)

the device is located in the primary location normally


accessible to the operator (the central control room).

the device is located in an auxiliary location, normally


accessible to the operator (a local panel or on the
starter cassette in the motor control centre).

the device is normally inaccessible to the operator


(behind the panel).

5/25/2018 Process Instrumentation and Control 14


Instrument Line Symbols

5/25/2018 Process Instrumentation and Control 15


Tag Number
TIC 103

T 103 - Loop identification


103 - Loop number
TIC - Functional Identification
T - First letter
IC - Succeeding Letters

5/25/2018 Process Instrumentation and Control 16


Identification Letters

5/25/2018 Process Instrumentation and Control 17


5/25/2018 Process Instrumentation and Control 18
5/25/2018 Process Instrumentation and Control 19
Control-Loops

5/25/2018 Process Instrumentation and Control 20


Control Instrumentation
• Control Instrumentation Includes
– Sensor
– Transmitter
– Controller
– Transducer (Signal converter)
– Final Control Element

5/25/2018 Process Instrumentation and Control 21


Sensors are the first element in the control loop to measure the
process variable, they are also called primary elements.

Process Variable Sensor


Pressure diaphragms, strain gauges,
capacitance cells
Temperature Thermocouple, resistance
thermometers,thermistors
Flow Rate Orifice, venturi, magnetic flow
meters
Liquid Level Differential pressure, float
actuated, capacitance

5/25/2018 Process Instrumentation and Control 22


Signal Transmission
Signal Transmission in Feedback Control System

Reactant A
TEMPERATURE TEMPERATURE
CONTROLLER TRANSMITTER
Ts 4-20 mA Product B
TC TT
4-20 mA
CURRENT TO
PRESSURE I/P
CONVERTER 3-15psi

Steam

CONTROL
TRANSMITTED
VALVE
SIGNALS
5/25/2018 Process Instrumentation and Control 23
Standard Transmission range
• The advantage of having a standard range or using
digital signals is that all equipment may be purchased
ready calibrated. For analogue systems the minimum
signal (Temperature, speed, force, pressure and so
on ) is represented by 4 mA or 0.2 bar and the
maximum signal is represented by 20 mA or 1.0 bar.

5/25/2018 Process Instrumentation and Control 24


Transmitter
Transmitters
A transmitter is a device that converts a reading from a senso
or transducer into a standard signal and transmits that signal
to a monitor or controller. Transmitter types include:
•Pressure transmitters
• Flow transmitters
• Temperature transmitters
• Level transmitters
• Analytic (O2, CO , and pH) transmitters

5/25/2018 Process Instrumentation and Control 25


• Transmitters are specified by their, zero, range, span and
gain:
Zero :- - The minimum input of the transmitter
Range:- The range of the input of a transmitter as identified by
its minimum and maximum value.
Example. The range of a temperature transmitter is
10oC to 100oC
Span : The maximum input(output) minus minimum input(output)
Gain :- Output span divided by input span
Output Span
Gain =
Input Span

5/25/2018 Process Instrumentation and Control 26


Transmitted Standard Signals

1 2
Electronic 5 0
4 - 20 mA
1- 5 V
12 16

9 12
Tm (psig) (mA)
Pneumatic 6 8
3 - 15 psig
3 4 Span = 100
Zero = 50

50 T (oC) 100 150

Gain = Km = span of output/ span of input

20mA − 4mA
Km = = 0 . 16 mA / o
C Tm (mA) = K m (T − 50o C ) + 4mA
150 C − 50 C
o o

5/25/2018 Process Instrumentation and Control 27


PID Controller
The controller will have knobs/buttons to adjust
• Set point
•Control Model (Automatic/manual)
• Proportional gain ( Proportional band)
• Derivative time (Rate time)
• Integral time (Reset rate)
• It will display
• the current values of CV, MV and set point
• the trend of the CV and MV

5/25/2018 Process Instrumentation and Control 28


Controller action
Text: Page 196 (Reverse or Direct Action)

Measured REVERSE Controller


Value ACTION Output
CONTROLLER
(Kc > 0 )

Measured Controller
DIRECT
Value ACTION Output
CONTROLLER
(Kc < 0 )

5/25/2018 Process Instrumentation and Control 29


Example:-
For the temperature control system shown below. Determine,
the controller action if the valve is direct acting.
Reactant A

Ts Product B
TC TT

Steam

5/25/2018 Process Instrumentation and Control 30


• Solution
• Overall action: When the temperature inside the tank increases
the steam flow rate should be decreased.
• Control Valve: It is given that the control valve is direct acting.
This means, to get a decreased steam flow rate the control output
should also decrease.
• Controller action:- the controller action should be reverse since
increase in measured output requires decrease in controller
output.

Reverse acting Direct


+ controller - Control valve -
measurement

5/25/2018 Process Instrumentation and Control 31


Final Control Elements
• Final control elements:- Part of the control system
that receives decision from the controller and adjusts
the manipulated variable.
• Examples of final control elements
– Control valves
– Variable speed motors
– Variable resistance heater
• Control valve is the most common final control
element in process industries

5/25/2018 Process Instrumentation and Control 32


Types of Control Valves

Control Valves

Sliding stem valves Rotating shaft valves


Globe valves - Butter fly valves
Gate valves - Ball valves

5/25/2018 Process Instrumentation and Control 33


Types of Control Valves

Direction of
shaft movement

Sliding shaft valve Rotating shaft valve


5/25/2018 Process Instrumentation and Control 34
Ball Valve Butterfly valve
5/25/2018 Process Instrumentation and Control 35
5/25/2018 Process Instrumentation and Control 36
Types of Control Valves

5/25/2018 Process Instrumentation and Control 37


Types of Control Valves: Comparison
• Rotary valves (butterfly valves) are generally cheaper
than linear valves in sizes above 2 in (50 mm) and
globe valves are the most effective for control
purpose in sizes< 4in.
• Bodies require minimum space for installation ( small
face to face dimension)
• They provide high capacity with low pressure loss
through the valves.
• are the most economical for larger pipe-size
applications

5/25/2018 Process Instrumentation and Control 38


Essential Features of a Control Valve
The following are the most essential features of a
valve related to control
 Valve action/ fail safe position

 Valve size

 Valve characteristic

 Rangeability

 Cavitation

5/25/2018 Process Instrumentation and Control 39


Essential Features: Valve Action
• Valve fail safe position is the position of the valve in
the emergency situation of no compressed air to the
valve.
• Fail Closed ( Air to open) valve is a valve that is
completely closed when the compressed air to the
valve fails.
• Fail open ( Air to close) valve is a valve that is
completely open when the compressed air to the
valve fails.

5/25/2018 Process Instrumentation and Control 40


Essential Features: Valve Action

Fail Open (Air to close), Fail Closed (Air to open),


reverse acting valve direct acting valve
5/25/2018 Process Instrumentation and Control 41
Essential Features: Valve Action
• Fail closed valves are direct acting since increase in
air pressure causes the valve to open more.
• Fail open valves are reverse acting since increase in
air pressure causes the valve to close.
• The main consideration in selecting the valve fail
position (action of valve) is safety.
• When the safest position of the valve is open we
order Fail Open (FO)/ Air to Close valve (ATC)
• When the safest position of the valve is closed we
order Fail closed (FC)/ Air to Open (ATO) valve

5/25/2018 Process Instrumentation and Control 42


Essential Features: Valve Action
• Examples :- Specify the appropriate fail safe position
of the valve in the following services.
– A flammable solvent is heated by steam in a heat
exchanger. The valve manipulates the flow of steam.
– A stirred tank heater contains a liquid polymer that is
heated by steam. When the temperature is low in the tank
the polymer solidifies and damages the tank, the stirrer
and pump and other components.

5/25/2018 Process Instrumentation and Control 43


Essential Features: Valve characteristics

• The inherent characteristic is the relationship


between the valve flow capacity and the valve travel
when the differential pressure drop across the valve
is held constant.

• Since valve flow is a function of both the valve travel


and the pressure drop across the valve, it is
traditional to conduct inherent valve characteristic
tests at a constant pressure drop.

5/25/2018 Process Instrumentation and Control 44


Essential Features: Valve characteristics
Typical inherent valve characteristics
– linear,
– equal percentage
– quick opening

5/25/2018 Process Instrumentation and Control 45


Essential Features: Valve characteristics

Approximating Equations
Linear
f ( x) = x

Equal percentage
f ( x) = α x −1
Quick opening
f ( x) = 1 − α −2.5 x

α = 20 to 50

5/25/2018 Process Instrumentation and Control 46


Essential Features: Valve characteristics
Under the specific conditions of constant
pressure drop, the valve flow becomes only a
function of the valve travel and the inherent
design of the valve trim.

5/25/2018 Process Instrumentation and Control 47


Essential Features: Valve characteristics
Linear Flow Characteristic
A valve with an ideal linear inherent flow
characteristic produces flow rate directly
proportional to the amount of valve plug travel,
throughout the travel range.

Select a valve with linear characteristic when


variation in the systems pressure drop is fairly
constant

5/25/2018 Process Instrumentation and Control 48


Essential Features: Valve characteristics
Equal-Percentage Flow Characteristic
• For equal increments of valve plug travel, the change in flow rate is
expressed as a constant percent of the flow rate at the time of the
change.
Example :- The following percent flow rates are given below for
an equal percentage valve. Determine the flow rate when the
valve moves to 30%.
(9.1 − 6.75)
p= 100% = 34.81%
x [%] f 6.75
10 6.75 f 3 = 1.3481× 9.1 = 12.27
20 9.10
30 f3

•Use a valve with equal percentage characteristics for systems that


have significant variation in the systems pressure drop.
5/25/2018 Process Instrumentation and Control 49
Essential Features: Valve characteristics
Quick-Opening Flow Characteristic
A valve with a quick opening flow characteristic provides
a maximum change in flow rate at low travels.

The curve is basically linear through the first 40 percent


of valve plug travel

Use control valves with quick-opening flow characteristics


for applications where valve dynamics is not essential,
they are cheaper.

5/25/2018 Process Instrumentation and Control 50


Essential Features: Rangeability
• Rangeability (turn-down ratio) is the ratio of the maximum
controllable flow to the minimum controllable flow.
• It is the measure of the width of the operating flows the
valve can control.
• Commonly used relation
Flow at 95% valve stem position
Rangeability =
Flow at 5% valve stem position

• Valves with high rangeability allow wide range of flow


adjustment

5/25/2018 Process Instrumentation and Control 51


Essential Features: Rangeability
Example: For constant pressure drop across the valve estimate the
rangeability of linear, equal percentage and quick opening valve use
α=25, 50 and 100 for equal percentage and quick opening valve.

0.95
Linear Rangeability = = 19
0.05

1 − 25 −2.5×0.95
Quick opening Rangeability = − 2.5× 0.05
= 3 .0
1 − 25
25 ( 0.95 −1)
Equal percentage Rangeability = ( 0.05 −1)
= 18
25

α 25 50 100
Quick opening 3 2.6 2.3
Equal percentage 18 33.8 63

5/25/2018 Process Instrumentation and Control 52


Essential Features: Valve Sizing
• Valve sizing is a compromise between two important
factors: pumping cost and control performance
– small valves cause high pressure drop resulting in high
pumping cost but are good for control performance
– Larger valves cause less pressure drop resulting in less
pumping cost, however, control performance is poor.
• Note that if the pump is already selected smaller valves
means they can not deliver the required flow rate

5/25/2018 Process Instrumentation and Control 53


Essential Features: Valve Sizing
The valve sizing equation for liquids

V-1

1 2

The Bernoulli equation between point 1 and 2

P1 v12 P2 v22 v22


+ + h1 = + + h2 + f
ρg 2 g ρg 2 g 2g

5/25/2018 Process Instrumentation and Control 54


Essential Features: Valve Sizing
Simplifying and rearranging
P1 − P2 v2
= f
ρg 2g

Using continuity equation Q = v A and ρ = ρw sg and rearranging

∆P ρ w f 2
= 2
Q
sg 2A

Q = flow rate (gpm)


sg = specific gravity
∆P =pressure drop (psi)

5/25/2018 Process Instrumentation and Control 55


Collecting constant terms for a given valve of a given geometry as CV
and rearranging we get the Valve Sizing Equation.

∆P sg
Q = Cv Cv = Q
sg ∆P
Cv is flow of 1 US gallon per minute of water at 60oF with a
pressure drop of 1 psi across the valve

5/25/2018 Process Instrumentation and Control 56


Essential Features: Valve Sizing
Steps for Selecting Control Valve
• STEP 1 : Determine the design flow rate and pressure drop across the
valve

• STEP 2: Calculate CV
for liquid service
Q - flow rate (gpm)
sg sg - specific gravity
Cv = Q ∆P - pressure drop (psi)
∆P
for gas and steam services formula varies from manufacturer to
manufacturer. Consult control valve manufacturer.
• STEP 3: Select the appropriate valve size from manufacturers catalogue
using Cv in consultation with the manufacturer.

5/25/2018 Process Instrumentation and Control 57


Control Valve sizing

5/25/2018 Process Instrumentation and Control 58


Flashing and Cavitation
• Flashing and cavitation involve a formation of vapor
bubbles due to a drop in pressure below the fluid
vapor pressure

Restriction

5/25/2018 Process Instrumentation and Control 59


Flashing and Cavitation
• If the pressure at the outlet of the valve is still below the vapor
pressure of the liquid, the bubbles will remain in the
downstream system creating what is known as flashing.
• If the downstream pressure recovery is sufficient to raise the
outlet pressure above the liquid vapor pressure, the bubble will
collapse, or implode, producing cavitation.
• The implosion of the vapor bubbles during cavitation releases
energy that manifests itself as noise and physical damage to the
valve.
• Flashing can also damage valves, but it will produce areas that
appear smooth and polished since flashing damage is
essentially erosion.
• The formation of millions of tiny bubbles may crowd the vena
contracta area which limits or chokes the flow.
5/25/2018 Process Instrumentation and Control 60
Choked Flow
• The chocked flow will exist in the service if ∆P is greater than the
allowable ∆Pa.
 ∆Pa is a function of the valve’s flow geometry and is specified as
the valve-recovery coefficient (Km).
∆Pa
Km =
P1 − Pvc

P1 = inlet pressure
Pvc = vena contracta pressure
at the point of chocked flow
∆Pa = the allowable
differential pressure across
the valve

5/25/2018 Process Instrumentation and Control 61


Choked Flow
• The allowable ∆Pa can be determined if the Pvc is known.
• Pvc can be estimated from the fluid vapor pressure through
the critical pressure ratio (rc) relationship.

Pvc
rc =
Pv

Pv = fluid vapor pressure

∆Pa = K m ( P1 − rc Pv )

5/25/2018 Process Instrumentation and Control 62

Vous aimerez peut-être aussi