DSEPOWER
®

SHARING
WITH
SIMPLICITY.
DSE5560 SPECIFICATION
AUTO TRANSFER SWITCH & MAINS CONTROL MODULE

DC SUPPLY
8V to 35V continuous

CRANKING DROPOUTS
Able to survive 0V for 50mS, providing supply
was at least 10V before dropout and supply
recovers to 5V. This is achieved without the
need for internal batteries

MAXIMUM OPERATING CURRENT


460mA at 12V. 245mA at 24V

MAXIMUM STANDBY CURRENT


375mA at 12V. 200mA at 24V

GENERATOR BUS INPUT RANGE


15V(L-N) to 333V AC (L-N) absolute maximum

MAINS (UTILITY) CT BURDEN


0.5VA

GENERATOR BUS INPUT FREQUENCY


50Hz - 60Hz at rated engine speed
(Minimum: 15V AC L-N)

MAINS SENSING INPUT RANGE


15V(L-N) to 333V AC (L-N) absolute maximum

MAINS SENSING INPUT FREQUENCY


50Hz - 60Hz (Minimum: 15V AC L-N)

AUXILIARY RELAY OUTPUTS


5A DC at supply voltage

GENERATOR BUS LOADING RELAY


OUTPUT
8A AC 250V – normally open

MAINS LOADING RELAY OUTPUT


8A AC 250V – normally closed

DIMENSONS
240mm x 172mm x 57mm
9.4” x 6.8” x 2.2”

The DSE5560 is an Automatic FEATURES BENEFITS PANEL CUTOUT


220mm x 160mm
Transfer Switch and Mains Control • Multiple language options • On-site module configuration 8.7” x 6.3”
Module, designed to automatically • Back-lit 4-line text LCD display • Remote module configuration via
synchronise multiple DSE5510s • Configurable timers PC software
with single or multiple mains • Configurable inputs (9) • In-built diagnostics removes the
(utility) supplies. • Configurable outputs (5) requirement for service equipment
• Automatic hours run balancing • Transfers between mains and
• Peak lopping control for DSE5510 generator
The module instructs the
controlled generator bus • Remote control and monitoring of
DSE5510s to make precise
• Peak shaving the module using comprehensive
changes to the generating set • No break return DSE PC software
outputs. This makes the module • PIN protected programming • License free PC software
suitable for many applications • Full remote control and telemetry
including peak lopping, peak • Mains (utility) fail monitoring OPERATION
shaving and no break return. • Load demand scheme The module is operated using the
• Multiple mains (utility) monitoring front STOP/RESET, MANUAL,
The module has the ability to • System lock input AUTO, TEST and START push
monitor the mains (utility) supply • Load switching control push- buttons.
and start and stop the generating button inputs
sets (being controlled by a • Engine history event log The first four of these push buttons
DSE5510) upon removal or • LED indicators include LED indicators. Additional
detection of the mains (utility) • PC configurable push buttons provide LCD page
supply. The modules operational display scroll, lamp test, mute and
load switching functionality.
status is indicated on the LCD
display and the front panel LEDs.
INSTRUMENTATION COMMUNICATIONS
ENVIRONMENTAL TESTING The DSE5560 module provides advanced metering functionality, displaying The DSE5560 includes a number of
STANDARDS the information on the LCD display. The information can be accessed using different communication capabilities.
the scroll push button located next to the LCD display.
ELECTRO MAGNETIC CAPABILITY Remote Communications
BS EN 61000-6-2 Bus Volts (L1-N, L2-N, L3-N) When the module detects an alarm
EMC Generic Emission Standard for the Bus Volts (L1-L2, L2 –L3, L3-L1) condition, it dials out to a PC
Industrial Environment
BS EN 61000-6-4
Bus Hz notifying the user of the exact alarm
EMC Generic Emission Standard for the Bus kW % of full capacity condition (modem required).
Industrial Environment Bus Phase Sequence
Load Amps, pf Building Management
ELECTRICAL SAFETY
BS EN 60950
Load kW, kVA, kVAr The module has been designed to
Safety of Information Technology Equipment, Mains (utility) Volts (L1-N, L2-N, L3-N) be integrated into new and existing
including Electrical Business Equipment Mains (utility) Volts (L1-L2, L2-L3, L3-L1) building management systems.
Mains (utility) Hz
TEMPERATURE
BS EN 60068-2-2
Mains (utility) Amps PC Software
Test Ab to +70oC 60067-2-2 Hot Mains (utility) kW The module has the ability to be
Test Ab to -30oC 60068-2-1 Cold Mains (utility) Kw % of full capacity controlled, configured and monitored
Mains (utility) kVA from a remote PC, using the
VIBRATION
BS EN 60068-2-6
Mains (utility) pf DSE810 interface.
Ten sweeps in each of three major axes Mains (utility) kVAr
5Hz to 8Hz @ +/-7.5mm, 8Hz to 500Hz @ 2gn Mains (utility) kVAr % of full capacity
Mains (utility) kWh
HUMIDITY
BS 2011 part 2.1 60068-2-30
Mains (utility) kVAh
Test Cb Ob Cyclic Mains (utility) kVArh
93% RH @ 40oC for 48 hours Mains (utility) Phase Sequence
Sycnchroscope
SHOCK
BS EN 60068-2-27
System Battery Voltage
Three shocks in each of three major axes
15gn in 11mS EVENT LOG
The module includes a comprehensive event log that shows the 25 most
recent alarm conditions and the date and time that they occurred. This
function assists the user when fault finding and maintaining a generating set.

TYPICAL LOAD SHARE EXPANSION MODULES


APPLICATION DSE157 Relay Input Expansion Module
DSE545 & DSE548 Remote Annunciation Expansion Module
DSE130 Input Expansion Module

M1 LOAD 1

G1

G2

G3

M2 LOAD 2
®

DSE5560
TO LOAD

P2

S2
S1
P1
AUTOMATIC MCCB AUTOMATIC MCCB
AUTOMATIC ACB AUTOMATIC ACB
CTs MUST BE 5 AMP or CONTACTOR or CONTACTOR
SECONDARY 3 or 4 POLE 3 or 4 POLE
P1 P2
L1 L1
S1 S2

L2 L2

COMMON
L3 L3
BUS
FROM
MAINS

N N
TO MAIN SWITCHING

2 AMP 2 AMP
TO GEN SWITCHING
DEVICE CIRCUITRY

DEVICE CIRCUITRY

FUSES FUSES

49 50 51 53 45 46 47 48 39 40 37 38 54 55 29 30 31 41 42 43 44

CT1 CT2 CT3 COM L1 L2 L3 N L1S2 L1S1 SCR B A L1 L2 L3 N


L151 L251 L351
MAINS CLOSE P810 CLOSE RS485
LOAD CT
MAINS CURRENT BUS MAINS

MODULE 5560 SCR 26


RS232

MSC H 27
157
BATTERY 3 OUTPUTS L 28
PLANT +VE
9 INPUTS
+VE

-VE

2 1 10 11 12 13 14 15 16 17 18 6 7 8 19
USER CONFIGURATION INPUT +VE OUTPUT

USER CONFIGURATION INPUT +VE OUTPUT

USER CONFIGURATION INPUT +VE OUTPUT


REMOTE START ON LOAD (PEAK LOP)

TO OTHER 5510
MSC CONNECTIONS
USER CONFIGURATION INPUT 5

USER CONFIGURATION INPUT 6

USER CONFIGURATION INPUT 7

USER CONFIGURATION INPUT 8

USER CONFIGURATION INPUT 9

MAX 250 METERS


120 OHM SCREENED CABLE
MAINS CLOSED AUXILIARY

THE FIRST AND LAST


BUS CLOSED AUXILIARY
ANTI-SURGE FUSE

AUXILIARY MAINS FAIL

UNITS MSC MUST BE FITTED


WITH A 120 OHM RESISTOR
MAX 20 AMP
MIN 2 AMPS

ACROSS H 9270 AND L (28)

BATTERY +VE BATTERY +VE


(12 OR 24 )

RELATED MATERIALS
TITLE PART NO’S
DSE5560 Manual 057-017
DSE5510 Data Sheet 055-039
DSE5510 Manual 057-015
Guide to Synchronising and
Load Sharing 057-045/6
55xx Software Manual 057-007
CAN & DSE Wiring Guide 057-004
Load Share Design and
Commissioning 057-047
DEEP SEA ELECTRONICS PLC TELEPHONE EMAIL ®
Highfield House +44 (0)1723 890099 sales@deepseaplc.com
Hunmanby Industrial Estate
Hunmanby, North Yorkshire FACSIMILE WEBSITE
YO14 0PH England +44 (0)1723 893303 www.deepseaplc.com

Registered in England & Wales No.01319649 VAT No.316923457

DEEP SEA ELECTRONICS INC TELEPHONE EMAIL


3230 Williams Avenue +1 (815) 316 8706 sales@deepseausa.com
Rockford
IL 61101-2668 USA FACSIMILE WEBSITE
+1 (815) 316 8708 www.deepseausa.com

YOUR LOCAL DISTRIBUTOR.

DEEP SEA ELECTRONICS PLC maintains a policy of continuous development and reserves the right to
change the details shown on this data sheet without prior notice. The contents are intended for guidance only.

This data sheet is printed on 9lives 55 Silk, which is produced with 55% recycled fibre
from both pre and post-consumer sources, together with 45% virgin ECF fibre.
055-041/02/08 (2)