Académique Documents
Professionnel Documents
Culture Documents
OPERATIONS
BOILER EMERGENCIES – Various Emergency
situations during operation with a special emphasis
on the safety aspect like boiler protection systems
controls and interlocks
Drum level lo and lo-lo
Drum level high and high high
Furnace Draft high and high high
Flame Failure
Boiler feed pump failure
Boiler pressure high
Furnace Explosion
Water wall / screen tube / evaporator tube failure
Coal feeder trip / burner trip
APH tube failure
Fan Failure
Super heater tube failure
High super heater temperature
Low Super heater temperature
Bed Temperature High
Bed Temperature Low
PA fan trip
PSH O/L steam temperature high
Economizer O/L FW temperature high
High negative draught
Hot bed material leakage from PA lines or bed ash drain
O/L steam pressure too low
Back fire in PA lines
1. DRUM LEVEL LOW AND LOW-LOW
A. CAUSE :-
Failure of boiler feed pump.
Failure of drum level controller.
Inadvertent opening of C.B.D.
Extraordinary change in load.(Sudden reduction in load)
Water tube failure.
B. EFFECT:-
Boiler may damage badly.
C. ACTION:-
Run the boiler if drum level is within safe limit (Lo alarm
and lo-lo alarm came). If it goes beyond safe limit allow
boiler to trip.
Check FW control valves position in DCS and in field, if
feed valve is stuck up open parallel line valve or bypass
valve.
Take care while increasing feed flow that running B.F.P.
do not trip on feed flow high.
If low level is due to tripping of feed pump start stand by
pump, if it is on manual.
Check position of all MOVs and operate them
accordingly.
Check for any abnormal sound from furnace.
If water level is below safe level, allow to trip the boiler
on drum level lo-lo to protect the boiler drum and tubes.
2. DRUM LEVEL HIGH AND HIGH HIGH :-
A. CAISE
Failure of drum level controller.
Extra ordinary increase in load
Sudden increase in firing rate.
B. EFFECT:-
Water may enter turbine and serious damages to turbine may
occur.
Joint valve on main steam pipe work leaks.
Carry over with sharp fall in super heater temperature
C. ACTION :-
Run the boiler if drum level is within safe limit (drum level
high and high high alarm came). If goes beyond limit allow
boiler to trip.
Attempt to control with feed valve.
Check FW control valves position in DCS and in field, if feed
valve is stuck up close isolating valve.
Attempt to control drum level by opening C.B.D.
Close Economizer inlet valve as per requirement and allow
feed pump to run in Recirculation.
If above measures fail trip the feed pump.
If level is due to sudden rise in load. If high level rises above
normal level – allow boiler to trip on drum level high high.
Operate IBD as per requirement...
Observe Final steam temperature and if it starts dropping,
close Boiler stop valve immediately.
3. FURNACE DRAFT HIGH AND HIGH HIGH
A. CAUSE :-
Due to faulty operation of fan control.
Disturbed combustion
Un-controlled fuel entry
B. EFFECT:-
Boiler may damage due to high furnace pressure.
Weak parts of furnace (ducting and enclosures) may explode
due to high furnace pressure.
C. ACTION :-
Confirm that the draught indication is correct.
If it is due to faulty operation of I.D./P.A./S.A. fan control,
take it on manual and maintain the furnace in suction.
If furnace pressure has increased beyond limit allow boiler to
trip on furnace draught high high.
4. FLAME FAILURE :-
A. CAUSE :-
Dirty Oil Burner
Furnace Pressure High
Low Combustion Air
B. EFFECT :-
Boiler will trip on flame failure
Chances of furnace explosion, if unburnt oil / coal mixture entered in
furnace.
Boiler steam pressure may fall down.
Super Heater Steam Temp. drop sharply.
Variation observed in drum level. (drum level low)
C. ACTION :-
Purge the boiler before putting burner back and purge burner as per
cycle time given by supplier.
Clean the burner tip, if nozzles (holes) are found chocked.
Check the air fan and maintain air fuel ratio.
Check the explosion doors, close it if opened.
5. BOILER FEED PUMP FAILURE :-
A. CAUSE :-
Motor protection relay operates
Lube oil temperature high
Discharge flow high
Motor bearing temperature high
B. EFFECT :-
If standby pump is available, it will start on auto or start it
manually.
If standby pump does not start on auto & manual, drum level
may go very low, which may trip the boiler.
C. ACTION :-
Start the stand by pump, if it does not start on auto. Adjust the
load to maintain the drum level as well as to prevent the
tripping of this pump on high feed water flow.
See the proper operation of recirculation valve and C.W.
Valve.
Analyze and rectify the fault in the main feed pump. Put it on
auto.
Restore the bus supply, if it has lost and make the pump
available.
Monitors drum level (Increase dumping CV opening, if drum
level starts dropping).
If both the BFP tripped and standby has not taken over
because of any common problem, trip both TG and box – up
the boiler.
6. BOILER PRESSURE HIGH
A. CAUSE :-
Sudden drop in load / steam flow.
Un-controlled fuel entry.
Turbine / prime mover trips.
B. EFFECT :-
Disturbance in drum water level.
Safety valves may life if pressure rise is up to that extent.
Boiler may trip on high pressure.
C. ACTION :-
Open start up vent valve.
Control fuel input and drum level.
Check coal feeder feeding rate.
Adjust the load on unit, if it has dropped.
7. FURNACE EXPLOSIOIN
A. CAUSE :-
Accumulation of unburnt fuel during light up / start up of
boiler.
Improper burning.
Inadequate air.
Secondary combustion.
B. EFFECT :-
Furnace explosion can cause extensive damage.
C. ACTION :-
Always purge the boiler with 40% full load air for about five
minutes. No cut short in purging allowed.
Adjust fuel air ratio.
8. WATER WALL / SCREEN TUBE / EVAPORATOR
TUBE FAILURE
A. CAUSE :-
Starved water wall.
Block tube, eroded tube, pitted tube, salt deposits.
Circulation affected due to open low point drains.
B. EFFECT :-
Hissing steam leakage noise from boiler.
Unstable flame fluctuating draught.
Bed temperature drops sharply.
High feed water flow for given steam generation / increase in
make up water.
Increase in I.D. Fan loading.
Below screen temperature drops sharply.
Flue gas outlet temperature decreased.
C. ACTION :
Every shift check low point drain valve are fully closed.
Every shift check the furnace listen furnace to detect steam
noise.
At first diagnostics of tube failure, start load reduction; trip
out unit before damage become serious. Quicker shutdown
reduces extensive damage.
Try to locate tube at low load .
Don’t allow the drum level to go beyond a danger level.
Start another BFP, if drum level is not maintained by
running BFP.
9. COAL FEEDER / BURNER FAILURE :-
A. CAUSE :-
Electrical supply failed
V.F.D. fault
Bed temperature high
Furnace draft high
Furnace draft low
Drum level high
Drum level low
B. EFFECT :-
Boiler pressure may fall down
SH steam temp fall sharply.
Bed temp. will decrease.
Variation in furnace pressure (LOW)
Variation in drum level (Low)
C. ACTION :-
Increase feeding in other compartments or boiler.
In case of any one DCF tripping, observe final steam pr. And
temperature and if require isolate attemparator.
Reduce PA / SA flow to control bed temp.
Check PA header pr. If it is less increase it.
Control furnace draft and drum level.
Check for reason of DCF tripping.
Check electrical fault or emergency stop push button &
restart coal feeder.
Check VFD fault, if any.
Restart coal feeder after checking cause of Boiler tripping &
put the burner in service.
Take burner support according to requirement.
If the problem persists for longer time and pressure drops,
reduce load on turbine.
10. APH TUBE FAILURE
A. CAUSE :-
Erosion of tube.
Corrosion of tube.
B. EFFECT :-
Flue gas temp after APH will fall down.
Increases in O2 percentage at ESP inlet.
PA / FD Fan overloaded.
Bed temp may be increased.
C. ACTION :-
Control flue gas temp by passes APH.
Reduce coal feeding to maintain O2 percentage.
Control bed temp.
If leakage of tubes are more stop the boiler and plug /
replaced.
11. LOSS OF FANS
I. ID FAN
A. CAUSE :-
Electrical motor protection
Fan bearing temp becomes high high
Motor bearing temp becomes very high
Drive fault (MCC fault)
Boiler trip
B. EFFECT :-
Furnace may get pressurized
Boiler will trip on boiler furnace pressure high.
C. ACTION :-
Check emergency or field stop.
Rectify electrical fault, if any.
Check cause for boiler trip & normalize it.
Check fan / motor-bearing temp.
Restart I.D. Fan after checking cause of tripping and
taking corrective actions.
Cut down air flow by operating FD dampers.
Slump two compartments.
Reduce load on turbine according to requirement.
II. P.A. FAN
A. CAUSE :-
Electrical motor protection.
Fan bearing temp. becomes high high.
Motor bearing temp. becomes very high.
MCC fault.
Boiler trip.
Run feed back off.
ID Fan trip.
B. EFFECT :-
Boiler will trip on
Furnace draft low
P.A. flow low.
C. ACTION :-
Rectify electrical fault, if any.
Check cause for boiler trip and normalize it.
Check fan / motor-bearing temp.
Restart the P.A. Fan after checking the cause of tripping
and taking corrective actions.
Check that whether all DCF got tripped or not. Otherwise
stop them immediately.
Reduce the load on turbine according to requirement
See that the standby fan is started. Otherwise start it and
increase the PA header pr.
Check PA lines for jamming and clear them accordingly.
III. FD FAN :-
A. CAUSE :-
Electrical motor protection.
Fan bearing temp becomes high high.
Motor bearing temp becomes very high.
MCC fault.
Boiler trip.
Run feed back off.
I.D. Fan trip.
PA Fan trip.
B. EFFECT :-
Boiler will trip on low furnace draft.
A. ACTIONS :-
Rectify electrical fault, if any.
Check cause for boiler, trip & normalize it.
Check fan / motor-bearing temp.
Stop coal feeding.
Reduce load on Turbine according to requirement
Observe Bed temperature
Restart the FD Fan after checking the cause of tripping and
taking corrective actions
12. SUPER HEATER TUBE FAILURE :-
A. CAUSE :-
Sustaining high metal temp due to water wall slugging or
inadequate steam flow and high gas temp during hot start.
Erosion on tubes due to high excess air.
Blocked tubes.
Starvation of tubes.
Salt deposition due to high water level in drum. Poor quality
of spray water.
B. EFFECT :-
Hissing noise notices.
Flue gas temp drops.
High feed water consumption compared to steam flow.
Over loading on I.D. Fan.
Erosion of other tubes and damages to other APH tubes.
C. ACTION :-
As soon as leakages noticed start reducing the load and trip
the boiler.
Listen the SH region for steam leakage.
Try to locate leakage through manholes before the boiler is
depressurized.
13. HIGH SUPER HEATER TEMP
A. CAUSE :-
High excess air.
Low feed water temp HP Heater not in service at constant
firing / load.
Sudden increase in firing rate to increase steam pressure.
In adequate spray.
Lodging of soot on the water walls considerably.
B. EFFECT :-
Rise in (+ve) positive turbine expansion.
Creep rate increase in tube metal, turbine parts, steam
piping.
C. ACTION :-
Check feed water temp. If HP heaters are available, put in
service and if not reduce the load.
Slow down firing rate.
Reduce excess air, if more.
Check attemparator control valve position in DCS and in
field, Take attemparator by – pass into service.
Increase load on boiler.
Observe the TG inlet steam temperature.
Ensure that none of drum safety valve has popped.
14. LOW SUPER HEATER TEMP. :-
CAUSE :-
Dirty super heater
Inadequate air flow.
High Spray
Too high feed water temp.
Sharp increase in load and pressure drop.
High Drum level.
EFFECT :-
Turbine expansion may be negative.
May induce thermal stresses in S.H.
C. ACTION :-
Check air flow – increase, if necessary.
Isolate attemparator and check for passing/opening of attemparator
by – pass..
Check feed water temp.
Avoid sharp rise in load to boiler pressure drop.
If, it is due to high drum level – allow unit to trip and open main
steam drains.
If main steam temperature drop takes place open steam pipe drains.
Observe constantly the TG inlet steam temperature. Trip the turbine /
prime mover when steam temperature falls.
Reduce load on boiler.
Check bed temperatures and increase coal feeding accordingly.
Check for jamming of coal hopper, PA lines and clear them
accordingly.
Take burner support if required.
Ensure that DCF chain is rotating (no shear pin failure).
Ensure that air flow is sufficient.
Drain bed material slowly, if bed height is more.
15. BED TEMP. HIGH :-
A. CAUSE :-
High CV and low ash coal used.
Low P.A. flow / FD flow
Sudden change in load
Faulty bed temp thermocouple.
Ash recalculating system trouble
B. EFFECT :-
Chances of clinker formation
Chances of refractory failure
Chances of screen tube failure
C. ACTION :-
Control bed temp by recirculation ash through
recirculation feeder.
Charge bed material if bed height permits.
Increase P.A. flow up and increase FD flow.
Constantly observe the wind box pr.
Reduce the load by cutting coal feeder.
Coal feeders trip, if temp rises above limit and allow
boiler to trip, if temp exceeds beyond safe limit to
save bed from clinker formation.
Check the bed temp thermocouple.
Check for wind box damper position.
Stop the boiler if temperatures still not controlled.
16. BED TEMP LOW :-
A. CAUSE :-
High PA with respect to load / high FD flow
w.r.t. load.
Low CV high ash coal used.
Coal interruption or coal feeder trips or
overfeeding of coal into furnace.
Recirculation ash feeder speed may increase.
Faulty bed temp. Thermocouple.
Water tube / screen tube / evaporator tube failure.
B. EFFECT :-
Boiler steam flow will reduce.
Super heater temp drops.
Furnace draft will fluctuate.
C. ACTION :-
Reduce P.A. Fan flow, if excessive / reduce FD. flow, if
excessive.
Reduce speed of recirculation ash feeder.
Stop bed material supply, if running.
Check bed temp thermocouple.
Check any leakage sound from furnace.
Check coal feeder and coal supply.
17. PSH O/L steam temperature high
• Turbine trip
• Load throw off
• UAT trip
• CEP trip
• Hotwell level high
• Hotwell level low
• Vacuum drop
• Fire/smoke at turbine area
• Turning gear trip
• Oil temperature high
• Bearing temperature high
• Bearing vibration high
• Steam pressure high after first stage
Turbine trip (sharing mode)